Professional Documents
Culture Documents
GREEN TERRAMESH
INSTALLATION MANUAL
AUTHOR: MACCAFERRI (REFERRED TO OFFICINE MACCAFERRI S.p.A.)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 1
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 2
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 3
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
MACCAFERRI (also the “Company”) supplies all components and accessories which shall be used
for construction of the GREEN TERRAMESH reinforced soil structures described in detail in the
Construction Designs approved and accepted by the Contractor.
This manual (hereinafter referred to as the “Manual”) represents a guide to the construction of Green
Terramesh and gives practical guidance for the organization and control of the related operations.
The Contractor’s personnel (site agent, foreman in charge of the works, etc..) and the Engineer’s staff
shall be aware of the contents of the manual before the delivery of the materials to site.
The Manual is addressed to the Contractor only. The content is confidential and, save as provided
below, is for discussion with, and use by, the Contractor (and no one else) and the latter shall not be
entitled to assign, transfer or charge any information and/or interest it may have in the Manual. No
other person/entity is entitled to rely on the Manual for any purpose whatsoever and MACCAFERRI
accepts no responsibility, duty or liability to any other person with respect to the contents of the
Manual.
Neither this Manual nor the data contained herein shall be reproduced, used or disclosed to anyone
without the written authorization of MACCAFERRI; in this regard the Manual should not be provided,
without our prior written specific consent, to anyone other than the Contractor and only on the basis
that it is strictly confidential; it being understood that MACCAFERRI accepts no liability to them, they
should not rely on it and they should not provide copies of it to any other person.
The instructions given in the Manual are of a general nature, and do not, therefore, exempt the
Contractor from the obligations and responsibilities for the definition and correct execution of all the
specific operations required for implementation of the project (construction sequence, loading and
unloading procedures, safety plans, etc.). In such respect, MACCAFERRI will not be liable for any
inaccuracies or omissions in the execution results and will not bear the consequences of any
connected liability. The details given in this manual do not exempt the Contractor from compliance
with the Construction Designs, Technical Specifications, Conditions of Contract provided by third
parties and safety requirements related to the site. In any case, the Manual does not replace the
Construction Designs realized by the appointed project designer.
When the structure to be installed has some special details, these will be defined in the Construction
Design drawings. In the case of ambiguities or discrepancies between the Construction Design
documents and this manual, the former documents will take priority.
If requested, MACCAFERRI will send a technician to site at the start of construction to assist the
Contractor in setting up the correct execution procedures, being understood that such activity shall
not result in an obligation for MACCAFERRI.
This installation Manual is not intended to provide to the Contractor an exhaustive summary of
guidance for the organization and control of the related operations regarding GREEN TERRAMESH.
All possible issues which may arise in connection with this Manual shall not be attributed to
MACCAFERRI.
Where the installation Manual reproduces or summarizes any information and/or description
concerning the GREEN TERRAMESH, MACCAFERRI does not accept any responsibility, duty or
liability for the truth, accuracy or completeness of such information or opinion in any way whatsoever
(including whether or not such information or opinion is misleading, by omission or otherwise).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 4
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
1. INTRODUCTION
The Green Terramesh is a reinforced soil structure with an inclined facing and functions through the
interaction between a soil with friction properties and reinforcement made of steel DT wire meshes.
The tensile forces are transferred to the reinforcement by friction. Green Terramesh is an
environmentally friendly modular system used for soil reinforcement. Green Terramesh units are
produced in compliance with CPR - Construction Product Regulation 305/2011, having CE marking
in compliance with ETA-16/0767. The management and production system is certified in compliance
with ISO 9001 and ISO 14001.
Fig. 1 – Green Terramesh, where h(m) is vertical height and α is inclination angle
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 5
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
2. IMPORTANT INFORMATION
2.1 RESPONSIBILITIES
The Contractor is responsible for a correct execution of the works in compliance with the Construction
Design documents, the Technical Specifications and the Contract Documents (not provided by
MACCAFERRI). In order to assist the Contractor, MACCAFERRI provides the recommendations
contained in this manual, but they in no case relieve the Contractor of the responsibility to comply
with all the current safety regulations and procedures. MACCAFERRI will not be liable for any
inaccuracies or omissions in the execution results and will not bear the consequences of any
connected liability.
The Contractor and the Client must check that the site personnel appointed for performance
of the works are in possession of a copy of this Manual and are aware of its contents.
If previously agreed with the Contractor, the Technical Representative of MACCAFERRI will be
present on site during the initial phases of the works. The Technical Representative will assist the
Contractor in planning the deliveries and will provide advice on the installation procedures
recommended for the Green Terramesh as described in this Manual. It is understood that the
Technical Representative’s assistance shall be considered as mere support to the Contractor and
shall not be binding for the latter, which shall assume all responsibility connected to installation and
execution procedures.
This Technical Representative will not be present on site for the entire duration of the works,
and shall not be considered as a substitute of the supervision and quality control staff
appointed by the Contractor and the Client.
The Contractor shall also carry out topographical survey checks to ensure that the structure is
constructed in the required position.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 6
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Ring fasteners
To increase the installation productivity, steel ring fasteners are used to connect units and to close
and secure them (Fig. 3).
The rings shall comply with EN 10223-3 and are supplied in box (1600 rings/box); these rings are
available Galmac coated for the use with the corresponding type of material or stainless steel. The
indicative amount of rings is shown in Table 1.
20 cm
Max Ring before fastening
Alternatively, lacing wire can be used to interconnect the units; sufficient Galmac and polymer coated
lacing wire (2.2/3.2 mm diameter) is supplied in coils with each unit to enable assembly (Fig. 4).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 7
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Structural fill
Reinforced soil structures shall be made of a good quality, free draining, granular and/or selected fill.
The structural soil shall be in accordance with the geotechnical characteristics specified by the
engineer and used in the calculations. Further conditions required for structural soil are those given
in the Technical Specifications as well as from the ones given in the actual codes (EN 14475).
Vegetative soil
Vegetative soil should be sandy clay or clay like sand, with 3% to 20% of organic material. The soil
should be fertile and friable and should come from 20 cm to 30 cm depths in the field. Vegetative soil
should be free from wood and stones larger than 5 cm in maximum dimension. Placement is made to
the specified thickness and profile into the face unit.
Tools
Available tools suitable for fasteners rings are shown in Figure 5: pneumatic (to be connected to a 6-
7 bar air compressor, air pipe Φ max 10 mm and max length 30 m) or manual lacing guns.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 8
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
4. Promptly report any anomaly for the acceptance of the goods.
The delivered material is labelled so that the characteristics can be read and the products can be
properly identified and used by the staff responsible for installation.
The height of Terramesh Green is variable between 70 and 76 cm, the maximum thickness of soil
compaction layers shall be half unit height.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 9
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The Certificate of conformity for the above-mentioned materials are supplied by MACCAFERRI. It is,
however, the Contractor’s responsibility to check that all the materials received comply with the
Delivery Documentation and the Construction design requirements.
Any discrepancy must be recorded on the Delivery Documentation (or proof of delivery) at the
time of unloading and immediately notified to MACCAFERRI.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 10
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
3. FOUNDATION
Note: The assessment of the foundation soil and its bearing capacity is within the Construction
Manager’s responsibility. Foundation soil which is unsuitable has to be removed and replaced with
a suitable material and compacted in accordance with the Construction Manager. Monitoring and
evaluation of foundation soil are essential.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 11
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
3.2 SETTING OUT
Points marked should be the start of the wall, end of wall and any internal/external angle changes or
steps. Points required to be marked out must be at the front of the toe wall i.e. front base of wall at
top of foundation level (Fig. 7).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 12
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 8 - Opening and flattening of GTM to restore the original correct shape
Front side
To assemble and connect all the elements, pneumatic or manual lacing gun, C rings, compressor
system (6-8 bar) will be required as an alternative to lacing wire.
Two adjacent GTM units shall be connected with rings with maximum spacing of 200 mm (Fig. 12),
in order to guarantee a homogenous soil reinforced structure.
Further details on the installation are shown at Figures 10-18.
Green Terramesh® units can be assembled on the jobsite with variable slope angles:
70° - vertical spacing 0.76 m (5 meshes facing) or 0.61 m (4 meshes facing)
65° - vertical spacing 0.73 m (5 meshes facing) or 0.58 m (4 meshes facing)
60° - vertical spacing 0.70 m (5 meshes facing) or 0.55 m (4 meshes facing)
45° - vertical spacing 0.58 m (5 meshes facing) or 0.45 m (4 meshes facing)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 13
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The following table allows for a quick check on the correct installation of the units, by providing the
fundamental geometrical H, L and S values for the different units:
Vertical
Spacing H Slope Facing S Horizontal Length L
(cm) (cm)
76 70° 28
GREEN 73 65° 34
TERRAMESH 70 60° 40
58 45° 58
Each Green Terramesh® unit is provided with 2 steel triangular brackets (pre-connected at the factory
to the facing) and 4 steel ties whose function is to assure the required facing inclination.
In order to assure the required slope, the ties have to be installed on the jobsite as per the following
instructions.
The facing welded panel presents an asymmetric pattern of wires in order to allow for the installation
of the ties at the proper horizontal bar, thus assuring the required slope.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 14
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
60°
65°
70°/45°
Fig. 10a – Front view of the welded panel: Correct positioning of the connecting ties (5 meshes facing).
60°
65°
70°/45°
Fig. 10b – Front view of the welded panel: correct positioning of the connecting ties (4 meshes facing).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 15
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
In the following figures, the ties positioning is shown for 5 meshes facing units with slope at 70°.
Fig. 12 –For each unit 3 m wide there are 2 brackets and 4 ties.
The side tie shall be installed in the position indicated by green arrow, the other 2 ties as per Fig. 10
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 16
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 13 – Stiffening of front side by rings that connect two adjacent welded mesh in order to avoid longitudinal movement
and sliding of GTM units during compaction step: 4/5 rings along the lateral edges of the units will assure the connection.
On the facing, ties have to be connected in correspondence of the welding point of the welded panel
using their U-shaped edge (Fig. 14 a) while the opposite shaped extremity shall be connected at the
transverse bar of the wire mesh base panel, by assuring to hook the tie to the closest double twist for
a stiffer connection (Fig. 14 b).
a b
c d
Fig. 14 – Detail of the hooking of the tie to the welded panel (a) and detail of the hooking of the tie to the bar of the wire
mesh base panel (b). Placement of bracket connected with welded panel (c) and wire mesh (d).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 17
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Standard inclination of GTM facing is 70°. In this case the brackets on the welded panel is
perpendicular (Fig. 15).
When the front side inclination is 65° or 60°, the same bracket used for 70° slope is rotated and it is
no longer perpendicular to the facing (the bracket is hinged to the vertical bar of the welded panel) so
that it fits the new configurations.
The procedure for a correct assembly is the following:
1) The bracket is rotated provisionally in order to support the front side.
2) The tie is hooked to the welded panel and to the bar of the wire mesh base panel.
3) The bracket is rotated definitively so that the tie is put in tension.
Facing inclination 70°
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 18
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 17 – Placing of rings by pneumatic lacing gun to connect two adjacent wire mesh tails
If the design requires the use of geogrid reinforcements in addition to the GTM units, geogrids are
arranged before the GTM units, from the front of facing up to the length required by the design. If the
geogrids are unidirectional, special attention will be given to the laying direction, the direction having
greater resistance has to be placed perpendicularly to the facing (Fig. 19).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 19
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The roll should be unwound, and the reinforcement layers shall be cut in segments having length
according to the project requirements. Each segment shall be placed in its final position ensuring that
no slack or undulations occur in the reinforcement as it is laid. If these do occur they should be
corrected immediately before proceeding.
The run of reinforcement should be reasonably straight, and all strip elements should be flat and not
twisted. No undulations in the reinforcement should be evident.
Structural Fill in direct contact with the geogrid reinforcement should be placed and spread exclusively
perpendicularly to the direction of the resisting strips of the geogrid reinforcement. If this operation
results in some undulation of the geogrids the undulation shall be removed.
We always recommend installing the geogrids on a horizontal surface, avoiding wrinkles and vertical
steps. Furthermore, no longitudinal gaps must be left between 2 adjacent installed rolls and the edges
of the 2 grids should be placed in contact (i.e. no gaps).
a b
Fig. 19 a, b, c – Mistakes to be avoided when installing geogrids: wrinkles (a) no contact between geogrids along
longitudinal joints (b), geogrids away from the front face (c)
Note: Particular care must be taken to ensure that geogrids are installed without wrinkles.
Wooden stakes can be used to keep the geogrid flat during installation. An overlap of 15 to 20
cm between adjacent rolls has to be provided.
c)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 20
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
4.4 PLACING THE UNITS
Place a number of individually laced units side by side in the required position. Care must be taken
not to damage the polymer coated wire mesh.
All GTM structures should be aligned and constructed accurately using standard engineering methods
and procedures e.g. fishing lines, dumpy levels or formwork; alignment of each layer should be done
before the units are filled, as the units are almost impossible to move afterwards.
Note: All GTM units to be laced to each other on all contact surfaces. Each GTM layer must be
securely laced to the GTM layer below.
Fig. 20 – First row of GTM ready to be laced by using wire before being filled by structural soil.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 21
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 23 – Front view of staggered and non-staggered Terramesh units in case of variable height and sloped foundation
If the lacings and the Terramesh units filling are made in accordance with the requirements, offsetting
Terramesh units will have the same performance, from a structural point of view. The offset can only
improve the vegetation growth on the facing of the Green Terramesh units since it provides further
room to the vegetation to develop plant roots. Usually, the offset between two Terramesh layers is in
the order of 2-3 cm. Furthermore, the stepped face favours rainwater penetration to keep the soil
moisturized and ease germination.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 22
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 24 – Cross sections of non-offset (above) and offset (below) Terramesh units
When placing the last (top) row of Green Terramesh units care should be taken ensuring the top
return of the units is fixed. This could be achieved by using the following scheme:
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 23
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Compaction
order
Compaction
sense
Width
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 24
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Note: It is necessary to perform a control of the alignment of the facing once the compaction is
completed. If excessive displacement of the facing appears during compaction, the current
operations shall stop right away and the reason for the problem shall be understood.
The degree of compaction shall be verified by plate bearing tests, whose frequency and acceptable
E modulus values shall be defined by the Geotechnical Engineer.
The following values, which depend upon the adopted plate bearing test procedure, are provided as
general indication:
WARNING NOTICE: In case of bulging of the front face, compaction activities must be stopped
and procedure must be changed.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 25
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 28 – Lightweight compactors shall be used for the area close to facia (within 1.0 m)
4.7 BACKFILLING
Compaction of the backfill shall be done simultaneously at each layer of GTM (Fig. 29).
Care must be taken not to damage the geocomposite for drainage (if present) when placing and
compacting the backfill.
Fig. 29 – Backfilling
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 26
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
4.9 HYDROSEEDING
After the completion of the structure, hydroseeding shall be carried out on the sloped face of the
structure during the most suitable climatic period, by applying a proper mixture of seeds, bonding
agents, organic material and mulch.
For the selection of both the suitable hydroseeding’s design mix and its application period, a local
specialist should be consulted.
Generally, one or two interventions are necessary to hydroseed the vegetative soil.
Fig. 31 – Hydroseeding
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 27
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 28
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
5. CONSTRUCTION DETAILS
c)
a) UNIT 1 UNIT 2
OVERLAPPED EDGES
OVERLAPPED EDGES
b) d)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 29
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
To realize structures in 90°corners a procedure is suggested and then explained visually with 3D
models in Fig. 35-36.
One unit can be installed as usual along one side, and the second can be installed perpendicularly
to the previous one, cutting partially the extremity on the joint, as shown in Fig.35.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 30
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
1 1
a) b)
The two units in Fig.36 are sketched as parallelepipeds to simplify the concept.
As explained before, the block 2 can be installed as usual. The block 1 is installed cutting the
connecting side with a triangular shape, where the inclination of the hypotenuse is the same of the
block 2 frontal panel.
It is possible to realize also structures in 45° corners, as shown in the real case of Fig. 37.
In this case, the panels (upper edge, welded and DT frontal panel and DT tail) shall be cut or folded
to fit with the required geometry, as per the attached sketches (Fig. 38 a,b).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 31
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Vertical obstructions are structures that are embedded in or extend vertically through the reinforced
soil mass. Examples of vertical obstructions are a catch basin, grate inlet, sign foundation, bridge
foundation, light poles, guardrail post, or culvert. Additional consideration shall be given to
obstructions that apply loads on the wall (e.g., deep foundations, overturning of signs and light poles).
Such applications may require additional reinforcement and facing support to resist the local increase
in lateral stress. Likewise, the wall may exert lateral earth pressure or vertical downdrag stress on the
obstruction due to movement of the wall, the consequences of which for the obstruction design and
performance must also be evaluated.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 32
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Horizontal obstructions are structures which are embedded in or extend horizontally through the
reinforced soil mass for a substantial length along the wall. The horizontal obstructions are commonly
due to utilities such as storm drain pipes. In some cases, pipes must penetrate the GTM facing or
pass through the filling. Penetrations through the reinforced soil and/or the facing units maybe at skew
or perpendicular angles from the facing. If a pipe must penetrate through the face of the wall, the wall
facing elements should be designed to fit around the pipe such that the facing elements are stable
and the backfill material does not spill through the wall face where it joins the obstruction.
Bridge abutments
In the case of bridge abutments construction, it is common that the supporting piles pass through the
reinforced soil. The steel wire mesh reinforcement must be cut around the piles (or openings should
be left waiting for the casting of the piles) and fastened to each other beyond the interferences and
obstructions.
In case of bridge abutments, it is not possible to beat the piles or drill the piles through the
reinforcement layers. (fig 40)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 33
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
SUPPORTING PILE CUTS RINGS
Tree trenches
In case of plantation of trees at the back of the front face (at least 3 m from the facing), trenches up
to 2x2x2 m are allowed.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 34
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
5.4 INTERNAL AND EXTERNAL DRAINAGE
Good drainage is essential to the proper performance of Green Terramesh. There are two types of
drainage considerations, internal and external. Internal drainage considerations are related to control
of surface or subgrade water that may infiltrate the reinforced soil mass. The internal drainage of GTM
depends on the characteristics of the backfill used in the reinforced soil mass. External drainage
considerations deal with water that may flow externally over and/or around the facing taxing the
internal drainage and/or creating external erosion issues. The external drainage depends on the
location of the GTM with respect to local hydrogeological factors and generally deals with diverting
water flow away from the reinforced soil structure. Regardless of the source of the water, the cardinal
rule in the design of GTM is to remove water before it enters the zone of influence to prevent the
following:
build-up of hydrostatic forces that increase lateral pressures,
piping, i.e., erosion of one soil into another, which creates paths for additional water flow or
clogging of drainage aggregate, and
external soil erosion from the toe, around the edges or at the top of the GTM.
It is recommended that adequate drainage features be required unless the engineer determines that
such features are not needed for a specific project. During a determination of the need for drainage
features, the engineer must include consideration for both subsurface (e.g., ground water, perched
water, flooding and tidal action) and surface infiltration water (e.g., rain, runoff, and snow melt).
Surface drainage is an important aspect of ensuring GTM performance and must be addressed during
design. Appropriate measures to prevent surface water from infiltrating into the backfill should be
included in the design. This typically requires coordination with designers of other project elements.
When possible, finished grading at the top of the structure should provide positive drainage to prevent
or minimize infiltration of surface water into the reinforced fill.
Fig. 42 – Overleaf drainage to prevent build-up of hydrostatic forces that increase lateral pressures
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 35
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 36
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
6. CAUSE-EFFECT RELATIONS
The Green Terramesh structures must be constructed in compliance with the structural requirements
shown in the drawings, technical specification of the construction design, and in the contract
documents. The desired result is obtained through the use of high-quality materials, correct
installation procedures and careful constant supervision of the works. In case improper practices or
inacceptable deformations are observed, the necessary corrective measures must be adopted right
away to ensure that the structure is brought back to the acceptable level.
Some of the most common and probable cause-effect relations are given in the following table.
CAUSES EFFECTS
Foundation soil with insufficient bearing
capacity
Foundation soil with non-uniform bearing
capacity
Foundation soil with moisture content too high
Foundation soil not well compacted
Backfill material not well compacted
Thickness of the backfill layers greater than 30
cm
Backfill material with a moisture content higher
than the optimal value Settlements and distortions
Backfill material with too high fines content of the structure
Vegetative soil not properly distributed
Vegetative soil not well compacted
Vegetative soil with high moisture content
Vegetative soil with too high fines content
Compaction carried out not in parallel to the
front face
Vegetative soil not compacted with suitable
lightweight equipments
Excessive compaction energy
Vehicles and construction equipments kept
within 1 m from the front face
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 37
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
6.2 TOLERANCES
Care should be taken to ensure that predicted construction and design life deformations will meet
specified tolerances. For Green Terramesh structures reference can be made to Table C.11 of
standard EN 14475 “Execution of special geotechnical works” taking into account the limits specified
for reinforced soil structures having wrap around with formwork as facing elements.
The values reported in Table 2 are indicative of the construction tolerances which are commonly
achieved, or the deformations which are normally withstood without any significant structural damage
or any effect on the stability of the structure.
Deformation Tolerance
Alignment ± 100 mm
Compressibility ≥10 %
Table 2 – Deformation tolerances
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 38
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
7. MAINTENANCE
7.1 IRREGULARITIES
Water seepage
Infiltration of significant water flows which can reach the embankment from the nearby soil.
Fig. 47 – Loss of fine material retainer due to fire. The vegetative soil behind the facing remains exposed
Controls have to be performed after the completion of the work by qualified personnel (surveyors
and/or engineers, geologists).
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 39
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The staff should have a maintenance manual to record the detected problems, their extents and the
expected repair costs, each time there is a control.
The controls have to be made in order to ensure the stability of the reinforced soil structure and of the
units which compose it. Typical controls are:
Check of the Green Terramesh footing; the bottom of the reinforced soil structure has to be
intact and should not show irregularities such as settlements, distortions, deformations and
bulging of the of the front face.
Analysis of the facing; the units composing the facing have to be intact and the filling should
not have lost its content in other parts of the structure. In particular, the connection between
the surface of the last units and the ground have to be intact.
Checks have to be done every 6-12 months and the type of control is visual.
M1 - Water seepage
In case of infiltration of significant water flows within the embankment, it is essential to perform an
immediate intervention with microslotted pipe (drainage pipe) covered with a filtering geotextile sock
having the function of removing the water towards the outside of the Green Terramesh and direct it
outside of the structure. Similarly, it is required that the berms upstream of the reinforced soil structure
maintain a slope of at least 2% towards the outside to avoid water ponding.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 40
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 41
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
8. WORKING AT HEIGHT
This paragraph can be used as a basis for the editing of Risk Assessment document, whose final
contents must be adopted country by country depending on the local regulations.
In the following paragraphs, the technical details are explained and suggestions for the safety device
used as a personnel protection are given. These devices are used in the Green Terramesh installation
to assure a high installation productivity without affecting the safety of the workers (Fig.49),
Under no circumstances should anyone work from the front face of the wall. An appropriate edge
protection system shall be installed; as the wall progresses in height this edge protection system
will be lifted to ensure adequate protection.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 42
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
LEGEND:
0. Steel Post
1. Support for the protection system such as wooden plank or building site fencing
2. Anchors to fasten the device to the Terramesh element (welded panel)
3. Steel post that follow the GTM slope
4. Transversal steel post
The posts are put in place manually through anchors, without the need of an excavator or of
mechanical equipment.
The distance to each other is approx. 4 m.
This system must be installed when the reached height of the structure is ≥ 2 m and before laying
the next upper level.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 43
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 51 – Detail of the safety device inserted in the GTM element (example)
Fig. 52 – Detail of the safety device with building site fencing or wooden plank (example)
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 44
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
Fig. 53 – Working site view of the safety device with wooden plank or building site fencing
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 45
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
8.3 CONSTRUCTION IN SAFETY
- two or three workers lay and install the product (included the opening of the GTM facing).
- for the manual placement and compaction of the vegetated soil close to the facing, the worker
must be in safety.
- during the material handling or movement, the personnel must be on the safety side, also with
the protection device installed.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 46
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
9. INSTALLATION PRODUCTIVITY
The installation productivity is highly dependent on volume, geometry and access to working area.
By making reference to a typical 5 men working team (1 foreman, 4 workers) operating 8 hours a day,
the following rates can be indicatively assumed for 5 meshes Green Terramesh units (in case of long
facing with ease of access, without considering the filling and compaction works):
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 47
GREEN TERRAMESH INSTALLATION MANUAL
Rev: 6, Date 13.06.2022
The installation manual is realized in order to show how the various elements have to be assembled
in order to realize the Green Terramesh, it being understood that such installation manual is not
intended to provide to the Contractor an exhaustive summary of guidance for the organization and
control of the related operations relating to the construction of Green Terramesh.
The Company reserves the faculty to bring modifications, integrations or improvements to the Manual,
without that this can constitute reason to think inadequate the previous revision.
and more in general, MACCAFERRI will not be liable for any inaccuracies or omissions in the
execution results and will not bear the consequences of any connected liability.
This document and the information contained cannot be copied or disclosed, entirely or in part, without
the written agreement of MACCAFERRI. The acquisition of this document does not give ownership
of it and of the information included in it.
The quality of the installation depends also from the scrupulous observance of the Installation Manual,
that it must be read before carrying out the installation of Green Terramesh.
At regard, in the construction of GREEN TERRAMESH only the geometrical configurations and the
components reported in the present Manual are admitted. Eventual variations must be preliminary
agreed in writing with MACCAFERRI. In any case, the Company will not bear the consequences of
any liability regarding the execution of GREEN TERRAMESH.
Notwithstanding the above, the Manual shall not be considered as a Construction Design and, in no
case, shall replace or substitute the technical drawing or projects approved by the relevant competent
authority. Therefore, the Manual shall be considered only as a mere support to Contractor being
understood that the latter shall be the sole responsible of the execution of Green Terramesh.
The information contained in this Manual is subject to change by MACCAFERRI. without prior notice.
MACCAFERRI. gives no warranty of any kind whatsoever, either explicitly or implicitly, with respect
to the information contained herein.
MACCAFERRI. shall not be held responsible for damages of any kind, including – without limitation
– bodily harm, injury or damage to property, in connection with handling system, installation, or
compliance or non-compliance with the instructions set forth in this Manual.
The information contained in this Manual is subject to change by MACCAFERRI without prior notice Page 48