Single Zone Ventilation Calculation

For EQ. Pr -1 : Minimum IAQ Performance


Minimum ASHRAE 62.1-2007 Requirements

Fresh air Meeting


Breathing Zone PROVIDED to Minimum
Zone air
Max. Zone Zone Floor Zone Outdoor Outdoor the zone (must Standard
People Outdoor Area Outdoor distribution REQUIRED
LEVEL Served By ROOM NAME Population Area (sq.m) Air flow Air Flow meet values in Requireme
Air Rate,Rp Air Rate, Ra effectiveness AIRFLOW
Pz Az (Vbz= (Voz = drawing) nt
Ez (Vot) (l/s)
RpPz+RaAz) Vbz/Ez) (l/s)

Ground Floor
GF GAC-01 MD OFFICE 2 2.5 16 0.30 10 1 10 10 19 YES
GF GAC-02 RECEPTION 5 2.5 44 0.30 26 1 26 26 28 YES
GF GAC-03 OPEN OFFICE/CORR 6 2.5 65 0.30 35 1 35 35 35 YES
GF GAC-04 MEETING ROOM 4 2.5 15 0.30 15 1 15 15 26 YES
GF GAC-06 CABIN / FILE ROOM 8 2.5 31 0.30 29 1 29 29 29 NO
GF GAC-07 SUPERVISOR 6 2.5 6 0.30 17 1 17 17 19 YES

MF MAC-01 PRAYER ROOM/DIN 7 2.5 71 0.30 39 1 39 39 40 YES