14 em Accessories

st M
y
S ro S260, S270 & S280
P

Electrical Catalog List Delivery Suggested Wgt. oz.


accessories number price class order quantities (1 pc.)

Undervoltage release
For field mounting, left or right side
12 VDC S2-BM1
24 VAC/VDC S2-BM2
48 VAC/VDC S2-BM3
216 A 1 5.2
110 VAC/VDC S2-BM4
220 VAC/VDC S2-BM5
380 VAC S2-BM6
When control voltage drops below approximately 50% of rated voltage, the S2-BM opens the breaker. The breaker can not be operated unless
S2-BM1 proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory; can be left or right side mounted.

14

14.18 Low Voltage Products & Systems


AC 1600 - 3/03 ABB Inc. • 888-385-1221 • www.abb-control.com
14
Technical data Sy
s
Pr tem
Mounting and operating instructions o
M

Mounting Operation
Universal mounting position using snap-on mounting MCBs are switched on by moving the handle to the
to standard 35x7.5mm DIN rail. upper position. Stamped onto the handle switch, a “I”
is visible confirming that the breaker is closed.
Miniature circuit breakers (MCBs) can also be
mounted to front of door using a panel cut-out with The MCBs are “trip-free,” if the handle is being
breaker handle protruding through panel opening for forced to the “ON” position, the breaker will still trip
external operation. Special front mounting kit type under fault conditions.
ME is available (see page 2.12).
The “O” marking indicates that the breaker is in the
Mounting MCB Connection “OFF” position. The MCB is now open and the load is
Terminals are suitable for solid or flexible conductors disconnected from line power.
from 18 to 4 AWG (0.75 to 25mm2) with no busbar When a breaker has tripped, the MCB handle should
connected. When maximum busbar size of 36 mm2 first be set to the full “OFF” position to make certain
is used, maximum cable is 6 AWG (16 mm2). the trip mechanism has been reset. Once the fault
Maximum tightening torque of 17.5 in-lb (2 Nm) has been determined and cleared the MCB can
for line/load terminals and 4.5 in-lb (0.5Nm) for again be switched “ON”.
accessory device terminals.
Maintenance
ABB miniature circuit breakers require no special
maintenance; only normal electrical system
maintenance procedures are required.

Removing MCB

Possible mounting arrangements of MCB accessories

H11 A A
S MCB MCB BM
BM BM
S/H

Shunt trip or undervoltage release Shunt trip and/or undervoltage release


mounted with auxiliary switch

Shunt trip and undervoltage release

Remove seal Add shunt trip to MCB Attach with spring clamps

14

Low Voltage Products & Systems 14.21


ABB Inc. • 888-385-1221 • www.abb-control.com AC 1600 - 3/03
14
Approximate dimensions Sy
s
Pr tem
Accessories o
M
00.00 Inches
00.00 [Millimeters]

Accessories Left side mtd Left or right side mtd

H/S H_ A_ U_
3-pole MCB
Bell alarm Auxiliary switch Shunt trip Undervoltage trip

0.35 0.35 0.69 0.69


8.8 8.8 17.5 17.5

MB-CL
Front mounting clip
C.L.
1.77
45 D

2.26 1.77 C.L.


57.5 45

0.69
17.5
1.38
35
2.07
52.5

MB-3PD
3.25
Front mounting bracket
2.12 ( 3P )
1.43 ( 2P )

1.87
CL

C
L
BREAKER CUT OUT

0.74 ( 1P ) 14
BKT. MT. HOLES
0.25 DIA. TYP 2

RHS2-M
CL CL
Handle mechanism 0.63
16

2.07 52.5 0.83


1.38 35 21

1.77 4.36
45 110.4
3.54
90
3.26
82.5

Low Voltage Products & Systems 14.29


ABB Inc. • 888-385-1221 • www.abb-control.com AC 1600 - 3/03