You are on page 1of 5

TEST REPORT

* Airborne Particle Count Test *


Customer Name M/s Chandrakanth Nethralaya Certificate No PCT /2023-24 /1137
& Address Calicut Kerala Date of Testing 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the actual particle count level "At Rest" Occupancy state of the clean Area/Clean zone.
Details of Instruments Used for testing
Instrument Used TSI PARTICLE COUNTER Instrument Sr. Number 95002207055
Make TSI Calibrated on 23.08.2022
Model 9500-01 Calibration Due on 23.08.2023
Sampling Flow Rate 100 LPM Sampling Time 1 Minutes
Details of Specification and Area
Area Classification Class "7" Occupancy State " At Rest "
Considered PC Sizes 0.5µm & 5.0µm Test Reference ISO-14644(Part1):2015
Area Name Operation Theatres Room Name Lasik OT
Ø Obtained Test Results Ø
No. of Particles >0. 5 µm/m³ No. of Particles > 5 µm/m³
Location Pass/fail
R R
Location 1 161600 161600 730 730
Location 2 96140 96140 1420 1420
Location 3 69560 69560 3410 3410
Location 4 46640 46640 730 730 Pass
Location 5 51960 51960 230 230
Location 6 35200 35200 130 130
Average 76850 Average 1108

Conclusion:
The Above Particle Count Test results confirms to ISO "7"standards with respect to partical count cleanliness class limit
(Maximum Permitted number of particles/m³ equal to or above as per ISO 14644(part1):2015
At Rest In Operation
Class
>0.5µm particles/m³ >5µm particles/m³ >0.5µm particles/m³ >5µm particles/m³
ISO-5 3500 29 3500 29
ISO-6 35200 293 352000 2930
ISO-7 352000 2930 3520000 29300
ISO-8 3520000 29300 Not Defined Not Defined
Test Conducted By Checked & Approved By Test Witnessed By

( for SRM Clean Room Associates ) ( for SRM Clean Room Associates ) ( for Chandrakanth Nethralaya )
TEST REPORT
* Airborne Particle Count Test *
Customer Name M/s Chandrakanth Nethralaya Certificate No PCT /2023-24 /1138
& Address Calicut Kerala Date of Testing 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the actual particle count level "At Rest" Occupancy state of the clean Area/Clean zone.
Details of Instruments Used for testing
Instrument Used TSI PARTICLE COUNTER Instrument Sr. Number 95002207055
Make TSI Calibrated on 23.08.2022
Model 9500-01 Calibration Due on 23.08.2023
Sampling Flow Rate 100 LPM Sampling Time 1 Minutes
Details of Specification and Area
Area Classification Class "7" Occupancy State " At Rest "
Considered PC Sizes 0.5µm & 5.0µm Test Reference ISO-14644(Part1):2015
Area Name Operation Theatres Room Name Retina & Cornea OT
Ø Obtained Test Results Ø
No. of Particles >0. 5 µm/m³ No. of Particles > 5 µm/m³
Location Pass/fail
R R
Location 1 245320 245320 1060 1060
Location 2 205200 205200 1300 1300
Location 3 148960 148960 740 740
Location 4 99050 99050 420 420 Pass
Location 5 89230 89230 140 140
Location 6 112300 112300 1260 1260
Average 150010 Average 820

Conclusion:
The Above Particle Count Test results confirms to ISO "7"standards with respect to partical count cleanliness class limit
(Maximum Permitted number of particles/m³ equal to or above as per ISO 14644(part1):2015
At Rest In Operation
Class >0.5µm particles/m³ >5µm particles/m³ >0.5µm particles/m³ >5µm particles/m³
ISO-5 3500 29 3500 29
ISO-6 35200 293 352000 2930
ISO-7 352000 2930 3520000 29300
ISO-8 3520000 29300 Not Defined Not Defined
Test Conducted By Checked & Approved By Test Witnessed By

( for SRM Clean Room Associates ) ( for SRM Clean Room Associates ) ( for Chandrakanth Nethralaya )
TEST REPORT
* Airborne Particle Count Test *
Customer Name M/s Chandrakanth Nethralaya Certificate No PCT /2023-24 /1139
& Address Calicut Kerala Date of Testing 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the actual particle count level "At Rest" Occupancy state of the clean Area/Clean zone.
Details of Instruments Used for testing
Instrument Used TSI PARTICLE COUNTER Instrument Sr. Number 95002207055
Make TSI Calibrated on 23.08.2022
Model 9500-01 Calibration Due on 23.08.2023
Sampling Flow Rate 100 LPM Sampling Time 1 Minutes
Details of Specification and Area
Area Classification Class "7" Occupancy State " At Rest "
Considered PC Sizes 0.5µm & 5.0µm Test Reference ISO-14644(Part1):2015
Area Name Operation Theatres Room Name Cataract OT -I
Ø Obtained Test Results Ø
No. of Particles >0. 5 µm/m³ No. of Particles > 5 µm/m³
Location Pass/fail
R R
Location 1 213350 213350 1320 1320
Location 2 189850 189850 330 330
Location 3 191370 191370 370 370
Location 4 306520 306520 1050 1050 Pass
Location 5 187560 187560 1470 1470
Location 6 201880 201880 1340 1340
Average 215088 Average 980

Conclusion:
The Above Particle Count Test results confirms to ISO "7"standards with respect to partical count cleanliness class limit
(Maximum Permitted number of particles/m³ equal to or above as per ISO 14644(part1):2015
At Rest In Operation
Class
>0.5µm particles/m³ >5µm particles/m³ >0.5µm particles/m³ >5µm particles/m³
ISO-5 3500 29 3500 29
ISO-6 35200 293 352000 2930
ISO-7 352000 2930 3520000 29300
ISO-8 3520000 29300 Not Defined Not Defined
Test Conducted By Checked & Approved By Test Witnessed By

( for SRM Clean Room Associates ) ( for SRM Clean Room Associates ) ( for Chandrakanth Nethralaya )
TEST REPORT
* Airborne Particle Count Test *
Customer Name M/s Chandrakanth Nethralaya Certificate No PCT /2023-24 /1139
& Address Calicut Kerala Date of Testing 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the actual particle count level "At Rest" Occupancy state of the clean Area/Clean zone.
Details of Instruments Used for testing
Instrument Used TSI PARTICLE COUNTER Instrument Sr. Number 95002207055
Make TSI Calibrated on 23.08.2022
Model 9500-01 Calibration Due on 23.08.2023
Sampling Flow Rate 100 LPM Sampling Time 1 Minutes
Details of Specification and Area
Area Classification Class "7" Occupancy State " At Rest "
Considered PC Sizes 0.5µm & 5.0µm Test Reference ISO-14644(Part1):2015
Area Name Operation Theatres Room Name Cataract OT -II
Ø Obtained Test Results Ø
No. of Particles >0. 5 µm/m³ No. of Particles > 5 µm/m³
Location Pass/fail
R R
Location 1 296020 296020 2140 2140
Location 2 294320 294320 2830 2830
Location 3 282610 282610 1630 1630
Location 4 301130 301130 1620 1620 Pass
Location 5 310670 310670 2020 2020
Location 6 293740 293740 1050 1050
Average 296415 Average 1882

Conclusion:
The Above Particle Count Test results confirms to ISO "7"standards with respect to partical count cleanliness class limit
(Maximum Permitted number of particles/m³ equal to or above as per ISO 14644(part1):2015
At Rest In Operation
Class >0.5µm particles/m³ >5µm particles/m³ >0.5µm particles/m³ >5µm particles/m³
ISO-5 3500 29 3500 29
ISO-6 35200 293 352000 2930
ISO-7 352000 2930 3520000 29300
ISO-8 3520000 29300 Not Defined Not Defined
Test Conducted By Checked & Approved By Test Witnessed By

( for SRM Clean Room Associates ) ( for SRM Clean Room Associates ) ( for Chandrakanth Nethralaya )
TEST REPORT
* Airborne Particle Count Test *
Customer Name M/s Chandrakanth Nethralaya Certificate No PCT /2023-24 /1140
& Address Calicut Kerala Date of Testing 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the actual particle count level "At Rest" Occupancy state of the clean Area/Clean zone.
Details of Instruments Used for testing
Instrument Used TSI PARTICLE COUNTER Instrument Sr. Number 95002207055
Make TSI Calibrated on 23.08.2022
Model 9500-01 Calibration Due on 23.08.2023
Sampling Flow Rate 100 LPM Sampling Time 1 Minutes
Details of Specification and Area
Area Classification Class "7" Occupancy State " At Rest "
Considered PC Sizes 0.5µm & 5.0µm Test Reference ISO-14644(Part1):2015
Area Name Operation Theatres Room Name Septic OT
Ø Obtained Test Results Ø
No. of Particles >0. 5 µm/m³ No. of Particles > 5 µm/m³
Location Pass/fail
R R
Location 1 28680 28680 1450 1450
Location 2 12710 12710 1350 1350
Location 3 9060 9060 970 970
Location 4 9300 9300 1070 1070 Pass
Location 5 7360 7360 980 980
Location 6 13530 13530 1130 1130
Average 13440 Average 1158

Conclusion:
The Above Particle Count Test results confirms to ISO "7"standards with respect to partical count cleanliness class limit
(Maximum Permitted number of particles/m³ equal to or above as per ISO 14644(part1):2015
At Rest In Operation
Class >0.5µm particles/m³ >5µm particles/m³ >0.5µm particles/m³ >5µm particles/m³
ISO-5 3500 29 3500 29
ISO-6 35200 293 352000 2930
ISO-7 352000 2930 3520000 29300
ISO-8 3520000 29300 Not Defined Not Defined
Test Conducted By Checked & Approved By Test Witnessed By

( for SRM Clean Room Associates ) ( for SRM Clean Room Associates ) ( for Chandrakanth Nethralaya )