Professional Documents
Culture Documents
Standard detectors
Modules, addressable
Included in delivery
Housing for surface-mounting
Technical specifications
Operating voltage 17 V - 35 V DC Connection / mounting
Current consumption: Connection cable 2-wire
Quiescent 0.5 µA Recommended cable, standard 747180
Alarm (LED on) max. 3.5 mA J-Y(ST)Y-2x2x0.8 mm
Alarm (LED off) 0.5 µA Conductor cross-section max. 2.5 mm2 (AWG 12)
Short-circuit max. 3.5 mA
Electrostatic shielding not necessary
Starting current 0.9 mA
Indication: Contact input:
Activated input LED (IP) red Voltage at contact input 9 V - 11 V DC
Fault LED (IP) yellow
Cable resistance max. 50 Ohm
Activated isolator LED (Poll/ISOL) yellow
Activated polling LEC (Poll/ISOL) green End-of-line resistor EOL 20 kOhm
Activated output LED (RLY) red Alarm resistor 1 kOhm
Output fault LED (RLY) yellow
Relay output: Note
Voltage max. 30 V DC
Current max. 1 A DC
The input is used as a binary input on the fire dtection and
suppression control panels FMZ 5000 and Clunid. It cannot
-40 °C to +70 °C be assigned to group or detector numbers.
Operating temperature
(-40 °F to 158 °F)
IP rating (EN 60529) IP 52
Material enclosure Polycarbonate UL94-V0 Connection diagram
Loop AP / XP95 1)
Technology/protocol
Discovery / CoreProtocol 2)
The contents of this publication are subject to modifications without notice. All rights reserved.
Inputs 1
Outputs 1
Addresses 1
Integrated isolator Yes
0 to 95%
Relative humidity
no condensation
Specification according to EN 54-17, EN 54-18
Weight 244 g ( 0.54 lbs) Approvals / marking
311-810_022 / AI02 / 2020-June-12 / en
1)
Protocol with FMZ 5000 / FMZ6000
2)
Not with FMZ 5000 / FMZ6000
1/1