You are on page 1of 1

Product Sheet I Detection

Standard detectors
Modules, addressable

Input / output module IOX SA 102 W-I Part no.: 925940


The analogue addressable input/output module for wall
mounting (W) monitors the status of potential-free contacts
via two inputs and reports their status to the fire alarm control
panel. The states „quiescent“, „alarm“ and „fault“ are recogni-
zed. In addition, the module has a relay output. The „Failsafe
Mode“ function can be set as an option: If there is no loop line
or protocol communication, the relay output is activated even
without instructions from the BMZ. The module is intended for
operation with fire alarm control panels via Loop AP protocol.
Addressing is done via DIP switches, the address can also be
changed after installation. The electronics have an integrated
isolator.

Included in delivery
Housing for surface-mounting
Technical specifications
Operating voltage 17 V - 35 V DC Connection / mounting
Current consumption: Connection cable 2-wire
Quiescent 0.5 µA Recommended cable, standard 747180
Alarm (LED on) max. 3.5 mA J-Y(ST)Y-2x2x0.8 mm
Alarm (LED off) 0.5 µA Conductor cross-section max. 2.5 mm2 (AWG 12)
Short-circuit max. 3.5 mA
Electrostatic shielding not necessary
Starting current 0.9 mA
Indication: Contact input:
Activated input LED (IP) red Voltage at contact input 9 V - 11 V DC
Fault LED (IP) yellow
Cable resistance max. 50 Ohm
Activated isolator LED (Poll/ISOL) yellow
Activated polling LEC (Poll/ISOL) green End-of-line resistor EOL 20 kOhm
Activated output LED (RLY) red Alarm resistor 1 kOhm
Output fault LED (RLY) yellow
Relay output: Note
Voltage max. 30 V DC
Current max. 1 A DC
The input is used as a binary input on the fire dtection and
suppression control panels FMZ 5000 and Clunid. It cannot
-40 °C to +70 °C be assigned to group or detector numbers.
Operating temperature
(-40 °F to 158 °F)
IP rating (EN 60529) IP 52
Material enclosure Polycarbonate UL94-V0 Connection diagram
Loop AP / XP95 1)
Technology/protocol
Discovery / CoreProtocol 2)
The contents of this publication are subject to modifications without notice. All rights reserved.

Inputs 1
Outputs 1
Addresses 1
Integrated isolator Yes
0 to 95%
Relative humidity
no condensation
Specification according to EN 54-17, EN 54-18
Weight 244 g ( 0.54 lbs) Approvals / marking
311-810_022 / AI02 / 2020-June-12 / en

150 x 90 x 60 mm (WxHxD) 2531-CPR-CSP11081


Dimensions G 218038 0832-CPR-F2368
5.9 x 3.5 x 2.4 inch (WxHxD)

1)
Protocol with FMZ 5000 / FMZ6000
2)
Not with FMZ 5000 / FMZ6000

1/1

Minimax GmbH | Industriestr. 10/12 | 23840 Bad Oldesloe | detection@minimax.de | www.minimax.com

You might also like