The document specifies construction details for galvanized steel rectangular ductwork for a project in Makkah, Saudi Arabia. Ductwork dimensions range from 0-4500mm and are constructed from 16 to 24 gauge steel using Pittsburgh lock seams. Reinforcement requirements include companion angles and tie rods, with spacing and sizes specified based on duct size. Construction meets a 6" W.G. standard and ASTM A653 galvanization specification.
The document specifies construction details for galvanized steel rectangular ductwork for a project in Makkah, Saudi Arabia. Ductwork dimensions range from 0-4500mm and are constructed from 16 to 24 gauge steel using Pittsburgh lock seams. Reinforcement requirements include companion angles and tie rods, with spacing and sizes specified based on duct size. Construction meets a 6" W.G. standard and ASTM A653 galvanization specification.
The document specifies construction details for galvanized steel rectangular ductwork for a project in Makkah, Saudi Arabia. Ductwork dimensions range from 0-4500mm and are constructed from 16 to 24 gauge steel using Pittsburgh lock seams. Reinforcement requirements include companion angles and tie rods, with spacing and sizes specified based on duct size. Construction meets a 6" W.G. standard and ASTM A653 galvanization specification.
Steel Rectangular Duct Work & Fittings (Single Wall)
Client : M/S. SAUDI BINLADEN GROUP Project : King Abdullah Bin Abdulaziz Project Third Saudi Expansion of : Holy Haram Makkah & Surrounding Areas Central Utility : Complex & Service Tunnel Shamiyah (Haramain Division) : Makkah Mukarramah Project.
GALV. STEEL RECTANGULAR DUCT WORK (SINGLE WALL)
6" W.G. CONSTRUCTION SCHEDULE (01 Gauge Higher Than SMACNA) As per Project Specification Galv. Steel Conform to ASTM A653, (G-115) Lock Forming Quality.
MAX. DUCT U.S. LONGITUDINAL INTERMEDIATE TRANSVERSE
DIMENSIONS GAUGE CONNECTIONS REINFORCEMENT CONNECTIONS PITTSBURGH SLIDE ON FLANGE 0-203 24 NOT REQUIRED LOCK SEAM AFC-35 PITTSBURGH SLIDE ON FLANGE 204-559 22 NOT REQUIRED LOCK SEAM AFC-35 PITTSBURGH SLIDE ON FLANGE 560-762 20 NOT REQUIRED LOCK SEAM AFC-35 PITTSBURGH SLIDE ON FLANGE 763-914 18 NOT REQUIRED LOCK SEAM AFC-35 PITTSBURGH COMPANION ANGLE 915-1219 16 NOT REQUIRED LOCK SEAM 50x50x5 mm PITTSBURGH ANGLE 50X50X5mm COMPANION ANGLE 1220-1524 16 LOCK SEAM @600mm Max Spacing 50x50x5 mm ANGLE 50X50X5mm COMPANION ANGLE PITTSBURGH 1525-2743 16 @600mm Max Spacing 50x50x5 mm + LOCK SEAM + 1 Tie Rod (12 mm Ø) 1 Tie Rod (12 mm Ø)
ANGLE 60X60X6mm COMPANION ANGLE
PITTSBURGH 2744-3000 16 @600mm Max Spacing 60x60x6 mm + LOCK SEAM + 1 Tie Rod (12 mm Ø) 1 Tie Rod (12 mm Ø)
ANGLE 70X70X6mm COMPANION ANGLE
PITTSBURGH 3001-4500 16 @600mm Max Spacing 70x70x6 mm + LOCK SEAM + 2 Tie Rod ( 12 mm Ø) 2 Tie Rod (12 mm Ø)