Professional Documents
Culture Documents
I06 - GAE08909 r1 en SCADA INTEGRATION IN CECOER
I06 - GAE08909 r1 en SCADA INTEGRATION IN CECOER
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Change log
1. Purpose 1
2. Scope 1
3. Preliminary Considerations 1
4. Development 2
4.1. Orientation 2
4.2. Nomenclature 5
4.2.1. CECOER nomenclature 5
4.2.2. CFE Nomenclature (Mexico) 6
4.3. Criteria for signs, position status, colors and contact and relay logic 8
4.3.1. Criteria for signs on measurements 8
4.3.2. Color criteria 9
4.3.3. Operating mode 10
4.3.4. Logic for the input contacts and output relays 10
4.3.5. Switches, disconnectors and switch trolleys 11
4.3.6. Levers and Automatisms 11
4.3.7. Transformer Connections 12
4.3.8. SCADA Substations Library 13
4.3.9. Screen type 15
4.3.10. Summary table 17
4.4. Element signals and remote control functions 18
4.5. Points to be remote controlled 19
4.6. Communication protocol 34
4.7. Safe power supply 35
5. Related Documentation 35
1. Purpose
To define the criteria and requirements that must be met by those installations which request
the CECOER evacuation equipment operation/supervision service for its integration in the
SCADA.
2. Scope
All those systems which must be integrated in the SCADA for operation/supervision from
CECOER.
3. Preliminary Considerations
All the evacuation equipment which contracts the operation/supervision service from CECOER
must observe the rule defined here except for exceptional cases such as:
F04_GAE07019 r02 | en 1 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
The information does not exist in the equipment, a typical case in which certain
protections do not exist.
Installations with a particular operating feature, for example centers shared with
other companies from the sector, in which it may be necessary to collect an additional
signal.
4. Development
4.1. Orientation
For the correct location of positions and switchgear by CECOER and the Local Operator, and to
ensure that all those involved are “referring” to the same elements, it is necessary to lay down
certain general visualization criteria for the substations and be able to name the substation
switchgear and interpret the single-line diagrams and the displays used in the Remote Control
Office and in the Substation itself using identical nomenclature.
Accessing the outdoors wind farm from the control room and located perpendicularly to Bars,
we have numbered the positions and different switchgear in accordance with the following
criteria:
F04_GAE07019 r02 | en 2 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
F04_GAE07019 r02 | en 3 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Where:
2.- Line 2
3.- Transformer 1
4.- Line 4
5.- Line 5
10.- Line 10
11.- Line 11
12.- Transformer 2
13.- Line 13
For the numbering of the lines, transformers and switchgear, the following criteria are used:
Line number: Position No allocated
F04_GAE07019 r02 | en 4 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
4.2. Nomenclature
The Nomenclature to be introduced onto the screens of the evacuation equipment in the CECOER
SCADA system must comply with that described as ‘CECOER Nomenclature’. In those cases in
which the installation must comply with current legislation or requirements imposed by the
System Operator, the CECOER nomenclature and that imposed by the Operator shall both be
used when configuring the screens.
A specific name may be added to this designation for the line indicating the name of the extreme
substation at which this line is going to stop.
SWITCH (52)
Line 52-X
Transformer 52-X
Coupling 52-X
Where X is the number allocated for each position in accordance with the orientation rule.
DISCONNECTOR (89)
Line 89-X-Y
Transformer 89-X-Y
Coupling 89-X-Y
Bars 89-X-Y
Bar 1 89-X-Y
Bar 2 89-X-Y
Transfer bar 89-X-Y
By-Pass 89-X-Y
Earth 57-X-Y
Where X is the number allocated for each position in accordance with the orientation rule.
Where Y is the increasing consecutive number allocated to each element in accordance with the
orientation rule.
TRANSFORMER: TF-X
AUTOTRANSFORMER: AT-X
Where X is the number allocated for each position in accordance with the orientation rule.
F04_GAE07019 r02 | en 5 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Where X is the number allocated for each position in accordance with the orientation rule.
Where Y is the increasing consecutive number allocated to each element in accordance with the
orientation rule.
PROTECTIONS
The nomenclature to be used for the protections is based on the ANSI C.37.2 device function
standard for electrical power systems.
The equipment identification for a particular installation will have five digits. The only
exception and subject to subsequent revisions is that the distribution feeders (radial) in
34.5 KV and lower voltages y will maintain the four-digit nomenclature in the installations.
The order of the digits according to their function is from left to right.
F04_GAE07019 r02 | en 6 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
VOLTAGE IN KV NUMBER
FROM TO ALLOCATED
0.00 2.40 1
2.41 4.16 2
4.17 6.99 3
7.00 16.50 4
16.60 44.00 5
44.10 70.00 6
77.10 115.00 7
115.10 161.00 8
161.10 230.00 9
230.10 499.00 A
500.10 700.00 B
EQUIPMENT TYPE. This is defined by the second numeric character in accordance with
the following:
NO. EQUIPMENT
1 Generator - transformer (generator units)
2 Transformers or autotransformers
3 Transmission lines or feeders
4 Reactors
5 Capacitors (in series or in parallel)
6 Special equipment
7 Transfer switch or wild card diagram.
8 Switch and medium diagram
9 Bar attachment switch diagram
0 Double switch bar number 2 diagram.
NUMBER ALLOCATED TO THE EQUIPMENT. The third and fourth digits define the economic
number of the equipment in question and their combination may be in the range from 00
to Z9.
DEVICE TYPE To identify it, use the fifth numerical digit which specifies the device type
in question.
DEVICE NO
0 Switch
1 blades to bar one
2 blades to bar two
3 additional blades
4 fuse blades
5 Switch in metal-clad cabinet (extraction)
6 connection blades between feeders and/or bars
F04_GAE07019 r02 | en 7 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
7 grounding blades
8 transfer blades
9 equipment side blades (lines, transformer, generator, reactor capacitor).
B1 Voltage in KV
B2 Voltage in KV
BT Voltage in KV
For example:
B1 115 KV which means bar one of 115 KV
B2 115 KV which means bar two of 115 KV.
BT 115 KV which means transfer bar of 115 KV
In the case of a generator and transformer unit, this should be identified with the same
number; for example: If the generator is identified as U 10, the transformer is identified
as T 10. As can be seen in the above example, hyphens are not used between the letter
and the number, a space is used instead.
4.3. Criteria for signs, position status, colors and contact and relay logic
F04_GAE07019 r02 | en 8 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
+ -
G Transformer
+ + - - + Lines
G
- +
C
400kV Red
220kV Green
132kV Blue
66kV Magenta
For those installations located in Mexico and for which the CFE is the system operator,
the color code is different to that described above and the installations should be configured in
accordance with the following:
400kV Blue
230kV Yellow
F04_GAE07019 r02 | en 9 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
This color code is applied to mimic boards, single-line diagrams and computer screens.
The station identification uses the Control Area number followed by the combination of
three letters, and it is the responsibility of each Control Area to assign it, avoiding
repetitions of the identification within the Area.
To distinguish the identification between two stations with the same nomenclature from
different Control Areas, the identification number for each Area will be considered.
Local
substation Remote control
Remote
Console
Local: The manoeuvres on the substation are performed from the appliances themselves.
Remote: The manoeuvres on the substation are performed from the different devices
which control it remotely. In this state, there are two types of control:
Remote control: The manoeuvres on the substation are performed from the
control SCADA located in the control center or in the substation.
Console: The manoeuvres on the substation are performed from the substation
integrated control system.
F04_GAE07019 r02 | en 10 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
1 = Closed
0 = Open
The open state of the switches must be considered as an alarm, except in the cases
of bar coupling and capacitor battery switches.
Switches and disconnectors with double instruction. For these, the series of contacts
opposite the position of each pole is received in first position, and the series of
contacts the image of the position of each pole in second position.
In accordance with the general criteria, this means that a closed contact is received in
1st place when the element is OPEN and in second place when the element is CLOSED.
ED (signage)
00 = Invalid state
01 = Closed
10 = Open
11 = Error
On switch trolleys (EX), the alarm occurs when the trolley is in Extracted, therefore in
this case the contact is taken closed, receiving therefore:
ED (signage)
1 = Connected
0 = Extracted
1 = In Service-Automatic-Connected-Unlocked-Remote
F04_GAE07019 r02 | en 11 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
1 = Current connection
SD (controls)
SD (controls)
1st relay = Increase
F04_GAE07019 r02 | en 12 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
F04_GAE07019 r02 | en 13 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
IMPORTANT: In all the elements with associated orders, the color of the button must
correspond with the state to which it is transiting (examples: order on switches; button
open: green (color of the open state of the switch) and button close: red (color pf the closed
state of the switch).
F04_GAE07019 r02 | en 14 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Static elements
Drawn in gray so that the operator has a record of their existence, but does not have
information about or control over the same.
Bars
If the operator has information about these, the voltage level should be displayed in the
right section and the true value in the left section.
F04_GAE07019 r02 | en 15 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Dashed gray line which, in shared substations, delimits the different properties. On the left
of the line, the name of the different owner companies is given.
Dynamic elements
In the upper right section insert the name of the element and on the right, below the
name of the element, the status of the element command, status of the recloser…
Transformer
- On the left, enter the allocated transformer number, the voltage levels and the power.
- On the right insert relay 86 (in this case it does not exist) and then the transformer
regulator.
Measurements
-General measurements: These are the total measurements of active, reactive power and
current, before and after being transformed. They should be inserted on the lower and
upper left of the transformer.
-Measurements of the feeder compartments: These are the active and reactive powers and
current of each service feeder. They should be placed to the left of the switch cabinet. (*)
If this is impossible due to lack of space, only the current is inserted in the lower part of
each switch cabinet (after the output name and number of turbines).
The arrows indicating the direction of these measurements must be inserted to the left of
the value.
Service feeders
-The name (Service feeder 1, Service feeder 2…) should be inserted in the lower part of
each service feeder and the wind turbines which evacuate through it identified.
-In addition, if several wind farms evacuate to the same ST, the service feeders which
belong to each wind farm should be identified with a key.
F04_GAE07019 r02 | en 16 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
0 1
PC-Remote PC-Remote
control control
Switch Open Green Closed Red
F04_GAE07019 r02 | en 17 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
The transfer of information from the UCS to the Control Centers and vice-versa is based on four
types of elementary signals:
ED (digital inputs)
EA (analog inputs)
EC (meter inputs)
SD (digital outputs or commands)
This information must be sent from the UCS to the Control, that is, in the event of the activation
of an alarm/trip this must be sent immediately without waiting for the UCS to be interrogated.
In accordance with the characteristics of the different elements in the installations, certain
logical-functional groups of these signals have been defined, called remote control functions.
These are described in the following table:
Breakdown into
Function Description: most frequent use
element signals
ED EA EC SD
I1 Simple instruction 1
I2 Double instruction 2
M Analog Measurement 1
F04_GAE07019 r02 | en 18 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Breakdown into
Function Description: most frequent use
element signals
C2. Double order (open/close) with double instruction (00, 01, 10, 2 2
11). Typical single core wire operation switch function
F04_GAE07019 r02 | en 19 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
Supply failure of each equipment For each of the Integrated Control positions
A
(SIPCO)
Communication failure for each For each of the Integrated Control positions
A
position (SIPCO)
A Fire alarm
F04_GAE07019 r02 | en 20 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
AUXILIARY SERVICES
A Synchronism failure
F04_GAE07019 r02 | en 21 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
F04_GAE07019 r02 | en 22 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
(1) In the ST where the AC auxiliary services supply of the line VT is taken
(2) For metal-clad SF6 switch cabinets
A SF6 low pressure alarm (2nd level) Locking or trip (Extinction by SF6)
M Active power
M Reactive power
M Voltage
M Frequency
F04_GAE07019 r02 | en 23 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
C1/C2 Switch
132 kV LINES
M Active power
M Reactive power
M Voltage
M Frequency
C1/C2 Switch
F04_GAE07019 r02 | en 24 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
M Active power
M Reactive power
M Frequency
C1/C2 Switch
F04_GAE07019 r02 | en 25 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
M Active power
M Reactive power
M Voltage
M Current
C1. Switch
I1 Switch extracted
I1 Bar Disconnector
F04_GAE07019 r02 | en 26 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
I1 Ground disconnector
M Active power
M Reactive power
M Voltage
M Current
C1/C2 Switch
F04_GAE07019 r02 | en 27 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
M Current
M Voltage
C1/C2 Switch
F04_GAE07019 r02 | en 28 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
M Voltage
R2 Regulator connection
F04_GAE07019 r02 | en 29 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
A Buchholz alarm
A Regulator locked
C0/A Trip due to tank The restoration order for these protections is
unique and in local via relay 86
C0/A Buchholz Trigger
F04_GAE07019 r02 | en 30 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
BARS
Anomaly in differential protection Includes alarm, minis trip, and diff prot. of
A unique bar without permission to change
bars
C1. Connec./Disc. Bar resistant ground Only in MV; and if the protections are
digital with detection of grounds, only ATRS
A Bar resistant ground trip is taken per Bar
A Trip to MV lines by 27
A Trip to MV lines by 59
BAR CONNECTION
M Current
C1/C2 Switch
F04_GAE07019 r02 | en 31 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
C1. Permission to change bars This cancels bar connection protections and
installs the bar differential protection on
single bar.
C1. Reclosure in Service / Out of Service This exists according to the service needs.
GENERATOR
F04_GAE07019 r02 | en 32 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
CAPACITOR BATTERY
M Reactive power
C1/C2 Switch
C2/C1 Circuit-breaker
I1 Ground disconnector
C0/A Battery protection trip This groups all the trips which
produce locking of closure. If it
does not have restoration it is
taken as A
A Opening by automatism
A Closing by automatism
F04_GAE07019 r02 | en 33 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
GROUNDING REACTANCES
I1 Ground disconnector
A Bucholz Trigger
C0/A Trip due to relay (86) This groups all the trips which
produce locking of closure.
F04_GAE07019 r02 | en 34 | 35
I06_GAE08909 r01
| en | P
INSTRUCTION
REQUIREMENTS AND CRITERIA FOR INTEGRATING
EVACUATION EQUIPMENT IN THE SCADA
Any printed or electronic copy of this document that is not residing in the company's Intranet shall be considered as uncontrolled
(except for copies that are clearly stamped "Controlled copy")
5. Related Documentation
Code Title
Requirements and Verification for Operation/control of evacuation equipment and management and
I05_GAE08909
implementation of HV work
NOTE: On the intranet, consult the applicable documentation associated with each technology.
F04_GAE07019 r02 | en 35 | 35