o Type A: Transformer switchgear

o Type B: Line switchgear


o Type C: Auxiliary services transformer switchgear
o Type D: Capacitors bank/ reactors switchgear
o Type E: Voltage transformers
o Type F: Current transformers
o Type G: Bus-raiser with disconnector

FRAMEWORK AGREEMENT
SWITCHGEAR (IEC 20kV-30/33kV-34,5kV)
TECHNICAL FEATURES
DESCRIPTION SPECIFICATION PROPOSED
GENERAL DATA
Assembly Indoor
Insulation SF6
Type Metal Clad
Service Voltage (kV) 20kV-30/33kV-34,5kV
Rated Voltage (kV) 24kV-36kV-38kV
Power frequency withstand voltage
50kV-70kV-80kV
(kV rms value)
Lightning impulse withstand voltage
125kV-170kV-150kV
(kV peak value)
Maximum installation height above sea level without
By Manufacturer
variation in the insulation levels
Bus current capability (A) 1600-2000-2500A
Rated short time withstand current (kA rms) 31,5kA-40kA
Model By Manufacturer
Type By Manufacturer
Catalogue Code By Manufacturer
Documents By Manufacturer

F02_I70_GAE08018 r01 | es 1|5


Weigth (kg) By Manufacturer
Poles 3
Nominal Frequency (Hz) 50/60Hz
Neutral Earthed
DIMENSIONS
Width By Manufacturer
Depth By Manufacturer
Heigth By Manufacturer
Applicable standards By Manufacturer
BUSBAR
Bus and connections material Copper
Bus and Connections Insulation sheath YES
CONNECTIONS
Cable entry Lower part
Connection box YES
Cable entry number Switchgear Type:
(consider up to 630 mm2 cables) A and G:4, B:3, C:1 and D:2
Connection terminal By Manufacturer
VOLTAGE PRESENCE INDICATOR
Voltage Presence detector Capacitive
Type of indicator Lighted signal
SF6
SF6 level indicator YES
DISCONNECTOR
Type Three positions(open-close-earth)
EARTHING BUSBAR
Earthing busbar YES
Material Cooper
Size Equivalent 95 mm2/AWG 4/0
CURRENT TRANSFORMER
Type Inductive

F02_I70_GAE08018 r01 | es 2|5


Switchgear Type:
A: TBD/5-5-5-5A
B: 600-1200/5-5A
Ratio C(circuit breaker): 600/5A
C(fuse): N/A
D: 300-600/5-5
F: TBD/5-5
Switchgear Type:
A: 15VA cl0,2s F≤5; 15VA cl0,2s F≤5;
20VA 5P20; 20VA 5P20.
Type B and D: 15VA cl0,5 F≤5; 20VA 5P20
C(circuit breaker): 20VA 5P20
C(fuse): N/A
F: 15VA cl0,2s F≤5; 15VA cl0,2s F≤5
Connections Front part
Insulation Bushing
BREAKER
Type SF6 or vaccum
Operation Device Motor charged spring stored energy
mechanism, with available manual crank
charging mechanism
Manufacturer By Manufacturer
Model, type and catalogue data By Manufacturer
Switchgear Type:
A:1600-2000-2500A
Rated normal current (A) B:1250A
C: 630A
D:630A
Rated short circuit withstand current 31,5kA-40kA
Assembly By Manufacturer
Switchgear Type:
Coils A: 2 open coil+1 close coil
B, C and D: 1 open coil+1 close coil

F02_I70_GAE08018 r01 | es 3|5


Control Voltage 125 Vcc
Position Indicator YES
Availabe auxiliary contacts 6 NA/ 6 NC
Mechanical operational counter Front pannel
FUSE (in case of using them in switchgear type C)
Model, type and catalogue data By Manufacturer
Rated normal current (A) 10A
Rating - Curve By Manufacturer
VOLTAGE TRANSFORMER
Quantity 3 per busbar
Type To use inside switchgear
Connection Line-Ground
Ratio Vn/V3:110/V3:110/V3:110/3
Accuraccy 30 VA CI 0,2-50 VA CI 0.5-3P, 30 VA 3P
INTERLOCKS AND SAFETY DEVICES
Prevention of the removal of circuit breakers that are not
YES
in the open position.
Prevention of the insertion of circuit breakers into
YES
switchgears with parts energized.

Prevent access to MV parts that are not de-energized and


earthed. Energization indicators are required and
interlocking devices that prevent access to energized parts.
YES
To access to any part it will be required to follow a
sequence of operations of the interlocking systems to
guarantee the safety.

Electromechanical interlock to avoid the close of the circuit


YES
breaker.
Circuit breakers will not automatically close when springs
YES
are charged with the crank.
When the disconnector is in ground position a key will be
YES
released blocking the disconnector.

F02_I70_GAE08018 r01 | es 4|5


Switchgears type D (capacitors bank/ reactors switchgear)
must have a time interlock so when the circuit breaker
YES
opens there must pass 10 minutes before be able to earth
the disconnector releasing its associated key.

The circuit breakers and disconnectors must be


YES
bidirectionally interlocked between them.
Visual indicators of voltage presence in each section
YES
separated by disconnectors or breakers.
The front panel will have a visual diagram of the MV circuit,
associating the indication and operation of elements to the
YES
SLD in order to allow verification during the operation of
elements.

Each cabinet will contain light and its switch. YES


Each cabinet will include devices in order to prevent
YES
condensation, such as a heater and thermostat.
Internal Arc IAC AFLR

F02_I70_GAE08018 r01 | es 5|5