HOTEL AUTOMATION ROOM SYSTEM

Room controller HARS-C27

Room controller for temperature, energy and access control, and for
management of the hotel room

• For 2-pipe or 4-pipe fan-coil systems


• For VRV/VRF air condition systems (optional)
• For split/multi-split air condition systems (optional)
• For radiators and cooling/heating via 2-pipe fan-coil system
• Heating for bathroom
• Centrally programmable room temperature setpoint with
individual setpoint adjustment from the guest's room
• Control of room lighting
based on room occupancy and using keypad
• Control of blinds or courtain (optional)
• Control of room safe via transponder card (optional)
• Energy management for individual room control system
based on room occupancy
• Room access control via transponder card
• Registration and transfer of messages and alarms to the database server
• Additional inputs for various I/O functions
• Loaded standard application
• Customized application software available as an option

CM2N6262.CEEen
01.10.2009 Building Technologies
Use

The HARS-C27 room controller integrates temperature control, energy management,


access control, light control, room safe control and the management of a hotel room, at
room level.

For operation, use is made of room operating unit, card reader, card holder, light
operating unit and a connection to the bus and power supply.

Functions

The room controllers are delivered with the standard application if not defined
specifically (the basic features are described in this data sheet).

The functions are determined according to standard application functions (if not
specified otherwise).

In special cases, the standard application may be overwritten with a definitive


customized application software. A commissioning and service tool is available for this
purpose.

Temperature control The following options can be implemented with fan-coil units:
• 4-pipe heating/cooling with 3-position or PWM valves output
• 2-pipe heating/cooling with 3-position or PWM valve output with changeover
• 2-pipe system with internal electric heating, 2-position or PWM valve output
and cooling with 3-position or PWM valve output
• 4-pipe heating via external radiator
and heating/cooling with 3-position or PWM valves output
• VRV/VRF indoor unit control (cooling/heating with fan speed control*)
• Auxiliary heating in bathroom, additional radiator or underfloor heating with
2-position, 3-position or PWM valve output
*VRV/VRF fan speed control is done via software application control (optional)

Room temperature setpoints:


• Centrally programmable room comfort temperature setpoint
• Individual setpoint adjustment of room comfort temperature setpoint in guest's room
• PreComfort setpoints when guest is absent
• Economy setpoints for free rooms (i.e. from which guests have checked out)
• Remote room temperature setpoint adjustment in rooms unoccupied for long periods

Energy-saving features:
• Energy management for individual room control system and lighting
based on room occupancy:
− Room occupied, guest in room
− Room occupied, guest absent
− Room vacant, not checked in
− Room out of use, i.e. during low season
• Summer/winter strategy
(i.e. avoid heating in summer and avoid cooling in winter)
• Fan coil unit disabled if window is opened

2/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Energy management Electricity:
• Master switch function: electrical consumers enabled/disabled automatically by
putting/taking the card from card holder
• Switch-on control of courtesy light function upon entry to room
• Electrical consumers enabled and disabled by pre-programmed, guest dependent
function
• Water supply shut off in the absence of guests and hotel staff (only possible with
electromagnetic valve installed)
• Control of blinds or curtain (optional)
• Control of lights in the room
• Control of balcony/decorative light
• Control of bathroom heating

Access control • Receipt of access code from the connected transponder card reader
• Control of access to guest rooms and suites
• Receipt of access codes for guests, hotel staff and emergency access cards from
the central management station at the reception
• Management of all access codes
• Activation of door opening mechanism when access is granted
• (Optional) Access control to room safe

Management level • SOS alarm or bathroom alarm


• "Do not disturb" and "Room service call" or "Make up room"
• "Guest present" indicator for hotel staff only or for all-time
• Alarm message if door is opened in unoccupied room (door intrusion) *)
• Alarm message if window is opened in unoccupied room (window intrusion) *)
• "Room cleaned" indication for room service to mark which room is prepared for
usage
• Registration and transfer of messages and alarms to the database server
• Alarm message if water overflow in bathroom occurs **)
• Alarm message for room main power supply failure *)
• Optionally, other functions can be programmed and linked to inputs and outputs
• Door opened and window opened message
*) Messages appear on HARS-SWx system software
**) Message appears on HARS-SWx system software and
on HARS-T0x device when hotel staff card is in HARS-HTx

Building automation • Room controller parameter setting


and control • Remote adjustment of room comfort setpoint
• Alarm message if room temperature is too high
• Alarm monitoring and message display
• Room status monitoring
• Automatic registration of temperature data
• Trend graph during all usage time (with additional application)
• Interface to front office system (FOS) or property management system (PMS) via the
hotel room management station HARS-SW.xx

Communication • Online communication over RS485 building bus

Ordering

When ordering, please specify the quantity, product name and type code:

Example: 20 Room controllers HARS-C27

3/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Compatibility

Name Type Data sheet


Room operating unit HARS-T05.xx 6274.CEE
Transponder card reader HARS-RT.xx 6272.CEE
Transponder card holder HARS-HT.xx 6273.CEE
Light operating unit HARS-L05.xx 6281.CEE

Mechanical design

The HARS-C27 controller consists of a housing base, a housing cover and a printed
circuit board with connection terminals.
The controller also has a tool socket.

Device label

Terminal covers Owing to the intrinsic heat generated by the


6314z04

controller, terminal covers must not be used,


STOP Caution
as this can cause overheating.
For the same reason, adequate air circulation
must be provided in the location where the
controller is installed.

4/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Protection from To prevent accidental physical contact with relay connections carrying voltages in
physical contact excess of the SELV voltage range (Ueff > 42), the device must be fitted in a housing
(preferably a control panel). This enclosure must be accessible only by use of a key or
tool.

Alternatively, a commercially available contact guard can be used.

Connection terminals All terminals are plug-in type to ensure easier maintenance and commissioning.
To avoid incorrect wiring, terminals which can be connected to AC 230 V (supply and
relay outputs) are physically segregated from the other terminals. They are arranged so
that, under normal circumstances, all incoming and outgoing cables can be connected
without crossing.

Response in the event • If the management system or communication link fails, this will not affect local
of a fault operation
• External fuses are required for load operation power supply inputs
• The controller comes with a self-resetting thermal fuse to prevent overload damage.

Disposal

The device includes electrical and electronic components and must not be disposed of
as domestic waste.

Current local legislation must be observed.

5/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Topology

Various switch.

Light operating
Valve actuator

operating unit
Door opener

Card reader

Card holder
Hardware
Lighting

inputs/outputs
Blinds

Room
Fan

unit

Engineering notes

• 230VAC is required for the room controller power supply. This power supply should
be provided for all HARS-Cxx controllers through UPS or aggregate power supply
source
• Additional 230VAC is required for loads control power supply.
• All HARS-Cxx controllers are connected together via RS485 bus. A RS485/RS232
converter is installed on a central place between room controllers and PC. No more
than 128 controllers can be connected on the same BUS line. In practice BUS line is
divided onto logical areas (i.e. floors, dilatations, groups of rooms, etc.). Maximum
cable length for one BUS line is 1000 m.
• The room controller must be installed in a control panel or covered enclosure, which
can only be opened with a key or tool. Adequate air circulation must be ensured.
• The relevant technical, and health and safety regulations must be observed,
including local electricity company regulations applicable to connection of devices to
the electricity network.
• The management level PCs must be protected with a UPS (uninterruptible power
supply).

6/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
• A mechanical safety lock must be provided to allow the doors to be opened from the
outside in extreme emergencies.

AC 230 V The sizing and fuse protection of the power supply cables depends on the total load
supply cables and on local regulations.

Relay outputs • Relay outputs allow switching of loads up to AC 250 V, 6 A. The cable dimensions
AC 230 V depend on the connected load and the local installation regulations. The circuits
must be externally fused (≤ 6 A), as there are no internal fuses.
• The output loads control power supply input X7 should be connected to mains
voltage 230 V if not otherwise specified.

STOP • Fan coils must not be connected in parallel (use cut-off relays).
Caution

Mounting instructions

The room controller can be mounted in any orientation, as follows:

Rail mounting
The housing base is designed for
snap-mounting on DIN rails, type EN 60175
(can be released with a screwdriver).

• The HARS-C27 room controller is installed in the corridor with other installed
devices, behind the plasterboard.
• There must be a means of dissipating the heat generated during operation.
Adequate air circulation must be ensured.
• Subject to certain conditions, the HARS-C27 room controller can be installed in
suspended ceilings. Potential noise problems caused by the switching of relays
should be resolved in a sample room.
• As installation is the same for all types of room (e.g. single rooms or suites), it is
recommended that a sample room should be set up for each room type, in
cooperation with the electrical installer.
• Ensure the room controller is accessible for commissioning and service work.
• The card holder is intended for fixed installation in a dry, enclosed space.
• Commissioning must be carried out by trained personnel only

STOP • Local safety and installation regulations must be observed!


Caution Observe the technical data for the relay outputs.

7/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
RS485 BUS
(Terminal block X1)

Wiring • LiYCY twisted pair type cable with 2 twisted pair for connection of the RS232/RS485
converter to all room controllers (includes 2 spare wires)

Room peripherals The following room devices can be connected to the room controller:
cables - card reader
- card holder
- room operating unit
- light operating unit

Wiring Cables:
8 x 0,14 mm2 flat telephone cable for:
- card reader
- room operating unit
- light operating unit
6 x 0,14 mm2 flat telephone cable for:
- card holder

STOP Adequate EMC precautions must be taken when installing the equipment.
Caution The room bus and room peripherals cables must not be routed in the same
conduit as high voltage conductors.

Commissioning

• During commissioning, the room controller address has to be set by using room
operator unit connected to its socket X11.
• The controller must be connected to the supply voltage for this purpose.
• In the case of customer-specific applications, the customized application software
must be downloaded from a service tool to service socket K1.
• The room controllers are already loaded with the standard application on delivery.
It is then only necessary to adjust the parameters with the commissioning software.

8/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Technical data

Power supply Working voltage: AC 230 V, 50 / 60 Hz


Power consumption of controller Max. 50 VA
Ports/interfaces Plug-in screw terminals
Inputs 1 5 digital inputs DC 12 V / 10 mA (galvanically isolated)
Wiring Simple signal conductors
Inputs 2 1 digital input DC 5 V / 5 mA (no galvanic isolation)
Wiring Simple signal conductors
Inputs 3 2 analog inputs DC 12 V / 5 mA (galvanically isolated)
Wiring Screened twisted pair
signal conductors
Outputs 7 Triac outputs 230 V Max. AC 250 V, max. AC 0.5 A
3 Relay outputs 230 V Max. AC 250 V, max. AC 4 A
STOP Total of all outputs Max. 6 A for all outputs
Caution
1)
1 DC1) output for door opener DC 12 V, max.10W for max. 5s
(door solenoid), non-floating short-circuit proof
1)
Card reader connection DC 12V, max. 150mA
1)
Card holder connection DC 12V, max. 150mA
2)
Room operating unit connection DC 5V, max. 150mA
2)
DC +5 V for SLAVE connection to DC 5V, max. 5mA
HARS-C10 controller
1)
STOP Total of all DC 12 V currents DC 12 V, max. 1,5 A for max. 5s
Caution
2)
STOP Total of all DC 5 V currents DC 5 V, max. 0,3 A
Caution
Mounting DIN rail EN 60175
Ambient conditions Operating temperature: 0...40ºC
Storage: –30...70ºC
Electromagnetic EN 61131-2:2003
compatibility
Low voltage equipment EN 61010-1:2001
Housing To EN 60 529 IP 20
protection standard
Protection class To EN 60 730 II
conformity Meets the requirements of: EMC 2004/108/EC
Directive
Low-voltage directive 2006/95/EC
Dimensions See also dimension diagrams 159,1 x 89,8 x 59,5 mm
Dimensions Width in DIN modular spacing units 9
Weight excluding packaging 0.7 kg *)
Colour Body Light gray RAL 7035

*) depending on add installed options

9/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Connections

Interface layout:

Interfaces: X1: RS485 BUS connection


X2: Relay output and power supply max. AC 230V
X3: 2 relay outputs and power supply max. AC 230 V
X4: 1 triac and 2 relay outputs max. AC 230 V
X5: 2 triac, 3 relay outputs and power supply max. AC 230 V
X6 and X8.3: 2 triac outputs max. AC 230 V
X7: Controlled loads power supply input max. AC 230 V
X8.1 X8.2: Controller power supply input max. AC 230 V
X10: 9 digital and 2 analog input and 1 digital output
X11: Room operating unit connection
X12: Card reader connection
X13: Light operating unit connection
X14: Card holder connection
X15: 12 VDC lock output connection
K1: Service socket: 6-pin  Use special service cable!

10/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Connection diagrams

The following functions are valid for the standard application

Terminal block X7
Mains power supply Pin I Function
AC 230 V 1 L Phase 230 VAC Max. 230VA
2 N Neutral

Terminal block X8
Controller power supply Pin I/O Function
Main switch output 1 L Phase 230VAC Max. 50VA
AC 230 V 2 N Neutral
3 T1 Main switch output 230VAC Max. 10VA

Terminal block X2
Relay output Pin I/O Function
AC 230 V 1 R1 Bathroom heating
2 L Power supply 230VAC

Terminal block X3
Relay outputs Pin I/O Function
AC 230 V 1 L Power supply 230VAC
2 R1 Output relay 1
3 R2 Output relay 2

Terminal block X4
Relay outputs From X3.1 Pin I/O Function
Triac output 1 T1 Output triac
AC 230 V 2 R1 Output relay 3
3 R2 Output relay 4

Terminal block X5
Relay outputs Pin I/O Function
AC 230 V 1 L Power supply 230VAC
2 T1 Cool valve
3 T2 Heat valve
From X7.1 4 R1 Fan coil fan 3rd speed
5 R2 Fan coil fan 2nd speed
6 R3 Fan coil fan 1st speed

Terminal block X6
From X7.1
Triac output Pin I/O Function
AC 230 V 1 N.C. Don't use
2 T1 Welcome light

1)
STOP Total of all Triac and Relay outputs: Max. 230 VA for all outputs
Caution
STOP Fans connected to the relay outputs must not be operated in parallel.
Caution For parallel operation use cut-off relays or slave room controllers.

11/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Terminal block X10
Digital inputs Pin I/O Function
DC 12 V isolated 1 DI 1 Light input 1 (or other)
2 DI 2 Light input 2 (or other)
3 DI 3 Window contact
4 DI 4 Door contact
5 GND for X10:1 – X10:7
6 DI 5 SOS button
7 DI 6 Motion detector input (or other)
14 DI 7 Aux input 4
15 GND for X10:14 - X10:16
16 DI 8 Presence in from master (or other)

Analog inputs
8 A1
Water leakage sensor input
9 A2
10 T1
Bathroom temperature probe input
11 T2

Digital output
12 PRES.+ Digital output for SLAVE connection to
13 PRES.- HARS-C10

Terminal block X1
RS485 BUS Pin I/O Function
1 A+ RS485 RS485 bus (galvanically separated from controller)
2 B– RS485 RS485 bus (galvanically separated from controller)

Terminal block X15


12VDC lock output Pin I/O Function
1 +12VDC Door lock
2 GND Door lock

2)
STOP Total of all DC 12 V currents: DC 12 V, max. 1.5 A max. 5s
Caution

Service interface K1:


6-pin Pin Function
1 GND
2 +5VDC
3 DATA_IN
4 RESET
5 CLK
6 DATA_OUT
 Use special service cable!

12/13

Siemens HARS-C27 – Room Controller CM2N6262.CEEen


Building Technologies 01.10.2009
Service connector

behind the device label

Dimensions

Dimensions in mm

Without terminal covers

 2009 Siemens Building Automation CEE Subject to change 13/13