Power Breakers, Contactors and Fuses

Power Circuit Breakers


3.1
No communication No communication Has communication with trip unit
No display Has display Has display
Has ARM
Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers
3
3
3
Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 1 3
Ampere range
Interruption rating at 480 V
200–5000 A
42–200 kA
200–5000 A
42–200 kA
200–5000 A
42–200 kA
200–5000 A
42–200 kA
3
rms sensing Yes Yes Yes Yes 3
Protection and Coordination
Protection Ordering options LI, LSI, LSIG, LSIA LSI, LSIG LSI, LSIG LSI, LSIG, LSIA 3
Fixed rating plug (In) Yes Yes Yes Yes
Overtemperature trip Yes Yes Yes Yes
3
Long delay
protection
Long delay pickup 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In)
3
Long delay time I2t at 6 x Ir 2–24 sec 2–24 sec 2–24 sec 2–24 sec
(L)
Long delay time I4t No No No 1–5 sec 3
IEEE curves No No No Yes
Long delay thermal memory Yes Yes Yes Yes 3
3
High load alarm No No No 0.5–1.0 x (Ir)
Short delay Short delay pickup 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1
protection
(S) Short delay time I2t at 8 x I r 100–500 ms 100–500 ms 100–500 ms 100–500 ms
3
Short delay time flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms
Short delay time ZSI Yes Yes Yes Yes 3
Instantaneous Instantaneous pickup 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1
protection
(I)
Making current release Yes Yes Yes Yes 3
Ground fault
Off position
Ground fault alarm
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
3
3
protection
Ground fault pickup 25–100% x (In) 25–100% x (In) 25–100% x (In) 24–100% x (In)
(G) 2
Ground fault delay I2t at 0.625 x In 100–500 ms 100–500 ms 100–500 ms 100–500 ms
Disable ground fault protection No No No No 3
Neutral protection (N) Model LSI only Model LSI only Model LSI only Model LSI only
System Diagnostics
3
Cause of trip LEDs Yes Yes Yes Yes
3
Magnitude of trip information No Yes Yes Yes
Remote signal contacts No Yes Yes Yes 3
Programmable contacts No No No Yes
Electronic operations counter No No No Yes 3
Notes
1 Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance alarm or trip, reverse power trip and phase rotation alarm are included.
3
3
2 1200 A maximum ground fault setting per UL/NEC.

In = Rating plug and sensor rating.


Ir = Long delay pickup setting.
3
3
3
3
3
3
Volume 4—Circuit Protection CA08100005E—July 2017 www.eaton.com V4-T3-21
3.1 Power Breakers, Contactors and Fuses
Power Circuit Breakers

Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers, continued
3
3
3
3 Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 1

3 System Monitoring
Digital display No 4-Character LCD 4-Character LCD 24-Character LED

3 Current (%) full scale sensor No Yes +/– 2% Yes +/– 2% Yes +/– 1%
Voltage (%) L to L No No No Yes +/– 1%
3 Power and energy (%) No No No Yes +/– 2%
Apparent power kVA and demand No No No Yes
3 Reactive power kVAR No No No Yes

3 Power factor No No No Yes


Crest factor No No No Yes

3 System Communications
Type — — INCOM/PowerNet/Modbus 2/ INCOM/PowerNet/TripLink/
3 PROFIBUS 2 Modbus 2/PROFIBUS 2
Power supply in breaker N/A Optional Standard Standard
3 Additional Features
Trip log (three events) No No No Yes
3 Electronic operations counter No No No Yes

3 Testing method 3 Test set Test set Test set Integral and test set
Waveform capture No No No Yes

3 Arcflash Reduction Maintenance System Mode No No Yes Yes 4


Breaker health monitor No No No Yes
3 Programmable relay functions No No No Yes 1

3 Notes
1 Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance alarm or trip, reverse power trip and phase rotation alarm are included.

This is actually Gateway PXG900


3
2 Requires externally mounted MMINT or PMINT module.
3 Test set for secondary injection.
4 Contact Eaton for availability.

3 In = Rating plug and sensor rating.


Ir = Long delay pickup setting.

3
3
3
3
3
3
3
3
3
3
3
V4-T3-22 Volume 4—Circuit Protection CA08100005E—July 2017 www.eaton.com