Professional Documents
Culture Documents
By
Prof. Dr. Mousa A. Abd-Allah
Distance Relays
Its operation is dependent on the ratio V/I, which expressed in terms
of an impedance.
Distance relays
1
5/7/2022
Impedance Relay
T=K1I2 – K2V2 – K3
At balance; T = 0 = K1I2 – K2V2 – K3
K2V2 = K1I2 – K3 K2 I2
𝒁 = 𝑽𝑰 = 𝑲𝟏
𝑲𝟐
−
𝑲𝟑
𝑲𝟐 𝑰 𝟐
∴𝒁=
𝑲𝟏
𝑲𝟐
= 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝟏
𝒁 = 𝒔𝒍𝒐𝒑𝒆 𝒐𝒇 𝒄𝒉𝒂𝒓𝒂𝒄𝒕𝒆𝒓𝒊𝒔𝒕𝒊𝒄𝒔
Note:
It needs a directional element and called Directional Impedance Relay
By adding a directional element in the basic impedance relay.
This element sense the power or current flow direction and relay
can operate only if the direction of power flow is in one particular
direction w.r.t. the point where relay is installed.
2
5/7/2022
Reactance Relay
The driving torque: T = K1I2 – K2VI cos (θ - )
θ = impedance angle & = Torque angle
𝑽
𝑲𝟏 = 𝑲𝟐 𝑰 𝐜𝐨𝐬(𝜽 − 𝝉) K1 = K2.Z.cos( - 90o)
𝑲
𝒁. 𝒔𝒊𝒏𝜽 = 𝑿 = 𝑲𝟏 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝟐
3
5/7/2022
Quadrilateral Characteristic
Modern distance relays offer quadrilateral characteristic,
whose resistive and reactive reach can be set independently.
It therefore provides better resistive coverage than any mho-
type characteristic for short lines.
This is especially true for earth fault impedance
measurement, where the arc resistances and fault resistance
to earth contribute to the highest values of fault resistance.
4
5/7/2022
Ex.1: An impedance, reactance and mho relays are used to protect a line having an impedance of
3+j4 Ω. Assume that these relays are adjusted to just operate for zero impedance short circuit at
the end of the line section. If an arcing short circuit fault having an arc impedance of 1+j0 Ω
occurs anywhere on the line, find for each type of distance relays, the maximum portion of the
line that can be protected.
Solution
The line OA is the impedance vector with impedance 3+j4 Ω
OB = 3 BA = 4
Zarc=1+j0, represented by OD
Draw DF//OA and FN//EM//R-axis
% of line protected by the reactance relay is 100%
%𝒐𝒇 𝒍𝒊𝒏𝒆 𝒑𝒓𝒐𝒕𝒆𝒄𝒕𝒆𝒅 𝒃𝒚 𝒎𝒉𝒐 𝒓𝒆𝒍𝒂𝒚 = 𝑶𝑵
𝑶𝑨
𝟒
𝒙𝟏𝟎𝟎 = 𝒙𝟏𝟎𝟎 = 𝟖𝟎%
𝟓
5
5/7/2022
6
5/7/2022
Ring Mains
7
5/7/2022
Translay
It is a typical biased, electromechanical balanced voltage
system, still giving useful service on distribution systems.
Solkor Protection
Solkor unit protection is used where solid metallic pilot
wires are available.
It is a differential protection system and is available as
solkor R for pilot/earth insulation level of 5 kV and Rf
for pilot/earth insulation level of either 5 or 15 kV.
Solkor Rf gives faster clearance times for internal faults whilst its stability for through faults
is the same high value as solkor R.
Distance relays
Correct coordination is achieved by having an instantaneous directional
zone 1 protection and one or two more time delayed zones.
Zone 1: The relay has been set at about 80% of the line length and is
instantaneous in operation.
The reasons for this are:
1. to avoid overreaching into the next line section and ensure sound
selectivity.
2. To overcome the errors in the measured impedance specially for long
line (say 100km or above) which could be up to 10%.
3. Errors in the CT and PT.
Zone 2: To cover remaining 20% of the line length, but it must be time delayed to provide the necessary
coordination with the downstream relay.
Zone 3: It takes the form of an offset mho characteristic. This offset provides a closing-onto-fault
feature, The short backward reach also provides local backup for a busbar fault.
8
5/7/2022
The angular limits being governed by the power factor of the load.
It is important that when setting a distance relays, especially zone 3, which has the longest
reach, that its characteristic does not encroach on the load area, as unnecessary tripping
will undoubtedly occur.
Alternatively, it is only picked up by either zone 2 or zone 3 in which case tripping will
be unacceptably delayed.
The effect of arc resistance is most significant on short lines where the reach of the
relay setting is small. It can be a problem if the fault occurs near the end of the reach.
9
5/7/2022
10
5/7/2022
Carrier
Aided
Protection
11