Zone
RE
F
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10%
rated
A B C N
Source
Protected zone
REF
RCT
RCT
RL
IF
IS
VS
RL
RL
RS
RT
RL
VS = IF (RCT + 2RL)
VS
RR
Metrosil Characteristic
V = CI
1MVA
(5%)
11000V
415V
1600/1
RCT =
4.9
Calculate :
1) Setting voltage (VS)
80MV
A
2) Value of stabilising
resistor required
3) Effective setting
1600/1
RCT =
4.8
RS
MCAG14
IS = 0.1
Amp
2 Core 7/0.67mm
(7.41/km)
100m Long
4) Peak voltage
developed by CTs
for internal fault
Solution (1)
Earth fault calculation :Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.
1
p.u.
1 P.U.
Total impedance = 14
1
4
I1 = 1 = 0.0714 p.u.
14
I1
= 111296 Amps
I2
IF
4
I0
Sequence Diagram
9
= 3 x 0.0714 x 111296
= 23840 Amps (primary)
= 14.9 Amps (secondary)
Solution (2)
10
Solution
(4)
11
Differential Protection
12
Differential Protection
Overall differential protection may be justified for
larger transformers (generally > 5MVA).
Provides fast operation on any winding
Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain
stability for heavy through fault current
Differential
Current
I1
BIAS
OPERATE
BIAS I
2
I1 I2
OPERATE
I1 I2
RESTRAIN
I1 +
I2
2
14
Mean Through
Current
Differential Protection
HV
PROTECTED
ZONE
LV
P1
P2
A2
A1
16
a1
a2
P2
P1
Use of Interposing CT
P1
S1
P2
A2
A1 a1
P1
S2
S1 P1
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
> Transformer Protection
P2
S2
S2
17
a2
P2
S1
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Differential Protection
150/5
P2
P1
S1
15MVA
66kV / 11kV
A2
A1 a1
a2
800/5
P2
P1
S2
S2
S1
Dy1
Differential Protection
800/5
150/5
P1
S1
P2
A2
A1 a1
a2
P2
P1
S2
S2
4.37A
4.92A
S1
S2 P1
(2.56)
S1
P2
(5)
R
R
= 62.7 kV
= 138 Amp
Secondary current
= 4.6 Amp
39
A2
a2
P1
P2
S1
P1
P2
S1
S2
REF
S2
P2
P1
S1
S2
To differential relay
40
300/5
25MV
A
11KV
1600/5
50MV
A
33KV
1000/5
4.59
5.51
10.33
2.88
2.88
Yd11(+30)
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
42
Numeric
Relay
Ratio
correction
Vectorial
correction
Virtual interposing CT
43
Differential
element
Virtual interposing CT