Safety Switches
General Duty Short-Circuit Ratings (kA) Using Class “R”, “J” or “T” Fusing where Applicable
Ampere
Rating NEMA 1 NEMA 3R
30 100 at 240V 100 at 240V
60 100 at 240V 100 at 240V
100 100 at 240V 100 at 240V
200 100 at 240V 100 at 240V
400 100 at 240V 100 at 240V
600 100 at 240V 100 at 240V
Heavy Duty Short-Circuit Ratings (kA) Using Class “R”, “J”, “L” or “T” Fusing where Applicable
Ampere
Rating NEMA 1 NEMA 3R NEMA 12 NEMA 4 & 4X
30 200 at 600V 200 at 600V 200 at 600V 200 at 600V
60 200 at 600V 200 at 600V 200 at 600V 200 at 600V
100 200 at 480V 200 at 480V 200 at 600V 200 at 600V
100 at 600V 100 at 600V
200 200 at 600V 200 at 600V 200 at 600V 200 at 600V
400 200 at 480V 200 at 480V 200 at 480V 200 at 480V
100 at 600V 100 at 600V 100 at 600V 100 at 600V
600 200 at 480V 200 at 480V 200 at 480V 200 at 480V
100 at 600V 100 at 600V 100 at 600V 100 at 600V
800① 200 at 480V 200 at 480V 200 at 480V 200 at 480V
100 at 600V 100 at 600V 100 at 600V 100 at 600V
1200① 200 at 600V 200 at 600V 200 at 600V 200 at 600V
①
Class “L” fuse connectors supplied as standard for 800A and 1200A.
Note:
Class “H” fuse clips supplied as standard for 30-600A.
Rated at 10,000 rms when using class “H” fuses.
Double-Throw Short-Circuit Ratings (kA) Using Class “R”, “J” or “T” Fusing where Applicable
Ampere
Rating NEMA 1 NEMA 3R NEMA 12 NEMA 4 & 4X
30 100 at 600V 100 at 600V 100 at 600V 100 at 600V
60 100 at 600V 100 at 600V 100 at 600V 100 at 600V
100 100 at 600V 100 at 600V 100 at 600V 100 at 600V
200 100 at 600V 100 at 600V 100 at 600V 100 at 600V
400 100 at 600V 100 at 600V 100 at 600V 100 at 600V
600 100 at 600V 100 at 600V 100 at 600V 100 at 600V
800 100 at 600V 100 at 600V — —
Note:
Class “H” fuse clips supplied as standard for 30-600A except Class “T” for 400A at 600V and 600A at 240V.
Rated at 10,000A rms when using Class “H” fuses.
Safety switch short-circuit ratings are applicable to AC only. For 600 Vdc, 10 kA short-circuit applies.
Safety switch I2t and Ip values are identical to UL maximum acceptable I2t and Ip values for the corresponding class fuse.