ECOFIT
Catalogue 2021
™
Medium & Low Voltage Distribution
Modernization of Switchboards
se.com/digmod
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021
www.se.com www.se.com
General Contents
ECOFIT™
Modernization Solutions..................................................................................................... page 2
Medium Voltage
B
Low Voltage
C
Asset Connect
E
Protection Relays
F
Sustainability Offers
I
Complementary Services
J
1 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 1
www.se.com www.se.com
Upgrade or replace?
J Let our tool help you determine
J
https://www.se.com/ww/en/work/services/field-services/
electrical-distribution/renew/upgrade-or-replace.jsp
K K
2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 3
www.se.com www.se.com
B
Full switchgear replacement ECOFIT™ solution
C
Site work costs
3 to 4 times lower*
D
Material costs
20 % to 50 % less*
30 to 70 % E
savings*
Downtime costs
2 to 6 days
F
50 to 150 times less* 1 to 4 hours
4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 5
www.se.com www.se.com
Peace of Mind G
Pre-tested solutions from established
manufacturers provide a high degree of
confidence in a retrofit solution. Established Less environmental impact
players like Schneider Electric have managed
thousands of switchgear retrofit projects and
Since a retrofit solution replaces only a portion
of the existing electrical equipment, fewer waste H
have an extensive library of lessons learned. materials need to be processed compared to a
Qualified personnel and up-to-date tools reduce complete replacement.
the risk of accidents and delays. Accompanying At the same time, we propose a state-of-the-art
safety improvements and updated warranties end-of-life disposal solution for the obsolete SF6
equipment and other raw material.
I
also contribute to overall power network peace
of mind.
6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 7
www.se.com www.se.com
E
Humidity, (ex DGPT2)
SMD Nearby Oil sensors
Display
Powertag sensors
Final Distribution
Arc flash
Protection
F
Simply add
Panel Server Panel Server Panel Server
seamless
Wireless sensors
(Thermal, PFC,
G
Humidity…) (Non SE Circuit breaker) AHC panels…
To PME
(STEP 2)
Simply connect (or retrofit) Feeder Simply connect (or retrofit) Simply add Major feeders
and Transformer protection relay Incomer Masterpact Circuit Breaker. monitoring with seamless
and get CB health status monitoring Add Power Quality Meters Wireless sensors
H
Enable (must have) / Enable+ (could have)
J
presentation
Asset Advisor Predictive: • Maintenance plan optimization
• Remote Services
• Asset Schneider Electric Expert
• Power Quality or Energy Management
• Predictive maintenance
mitigation implementation…
• Historian
• Trends & Dashboards Asset Advisor Preventive:
• Reporting
K
• Technical support level 1
• Alarms
• Remote monitoring
• Alarms priorization
8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 9
www.se.com www.se.com
Maintenance costs
G
Modernization
Product life
H
Installation End of End of spare End of
& commissioning commercialization parts supply
commitment
spare parts
I
10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 11
www.se.com www.se.com
Modernization
• Extend obsolete assets lifetime. E
Through the contract duration, we will replace • Digitize your installation by replacing obsolete
your obsolete assets by new ranges with up to assets with new connected ranges.
date Digital technology to enable you the use of
advanced tools and the access to cloud advisor
• Spread your modernization investment over
several years. F
services. The plan is customized at the start of
• Have better control of your budget with an
the contract, with substitution of obsolete assets
all inclusive service plan and predictable
by new ranges connected to manufacturer digital
expenses.
platform (labor & devices), at the end of the
contract period. • Feel reassured with access to our remote G
support services whenever you need them.
12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 13
www.se.com www.se.com
6 200 D
customers. You benefit from the experience and
know-how in electric distribution, automation and
power & control of a recognized global leader.
services people in more than
A long history of innovation for
88
countries
a global offer
As world leader, Schneider Electric has
developed a large and comprehensive range
E
of innovative devices.
You take benefit of a global leader experience
and know-how in electric distribution, automation
and power & control.
F
All the devices included in this overview have
5%
of sales devoted to R&D
been designed and manufactured to incorporate
the benefits of this extensive experience.
Manufactured as original
G
For services purpose, the life of the following
equipment is extended by rebuilding them
according to their original design.
H
More than
Schneider Electric, a brand you can trust!
115 000
ECOFIT™ in services/delivered
I
in various business segments
14 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 15
www.se.com www.se.com
16 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 A1
www.se.com www.se.com
Standard & Customized solutions index Standard & Customized solutions index
Medium voltage ECOFIT™ standard solutions Medium voltage ECOFIT™ standard solutions
How to find an ECOFIT™ solution?
1 2 3
1 Select the " generic family ". 2 Select the " Panel type ". 3 Select the " Original device type ".
Original Brand MV CB or MV Panel MV Panel type Original device type New device type Flyer N° Page
Contactor or Cradle
Disconnector to Cradle
1 2 3 Federal Pioneer 3 Metalclad switchgear DST 2 & 5 DST 2V & 5V SERED111067EN B26
Original Brand MV CB or MV Panel MV Panel type Original device type New device type Flyer N° Page Merlin Gerin 3 Motorstart P50D C - CD CTV1 - R400 - R400D SERED111005EN B27
Contactor or Cradle
Disconnector to Cradle Merlin Gerin 3 Motorstart P500D C1 - CD1 CTV1 - R400 - R400D SERED111006EN B28
Square D 5-15 kV MC switchgear VAD2-3 Magnum CB SERED111036EN B2 Delle 3 Normabloc N13xx HL HVX - FPX SERED111033EN B29
3
A A
Siemens 8BD1 3AC - H515 EasyPact EXE SERED111200EN B3 GEC-Alsthom 3 Normaclad PX12 - 24 FPX FPX SERED111124EN B49
3
AEG, Alsthom, AHA ECA HVX-O2 SERED111168EN B4 Alstom, AREVA, 3 PIX SF6 FPX FPX SERED111137EN B50
3
Alstom Schneider Electric
Merlin Gerin Belledonne B200-B400 DSE22 to DSE78 Evolis - LF2 - LF3 - SF1 SERED111009EN B5 AEG, Alstom 3 R VA - VAA VA - VAA SERED111188EN B51
3
Merlin Gerin Belledonne B200G DSE22K - DSE23K Evolis - LF1 SERED111010EN B6 AEG, Alstom 3 R M - MC - IMC - E - AL - ALF VA - VAA - Contactor SERED111042EN B30
3
- BAL - FAL - IFAL - TG
Merlin Gerin 3 Belledonne B650 DIS Evolis - LF1 - R400 - R400D SERED111007EN B7
B B
GOST standard 3 RSW RSW Evolis - LF SERED111163EN B31
Merlin Gerin 3 Belledonne B900 DIS SF1 SERED111008EN B8
Ansaldo 3 Siclad MAG II LF1 - LF2 SERED111050EN B32
AEI, GEC, GEC- 3 BVP 17 BVP 17 VMX SERED111060EN B9
Square D 3 Solenarc DSE Metal-Clad DSE Magnum CB SERED111037EN B33
Alsthom, Alstom,
switchgear
AREVA
Nuova Magrini 3 Venus GI-GL LF1 - LF3 SERED111051EN B34
CEM 3 Cemabloc CB CB FP - HVX SERED111026EN B10
Galileo
CEM, Delle 3 Cemafluor C26.0 and CS and FPR SERED111028EN B11
C C
GEC-Alsthom, 3 VISAX BLV BLV SERED111140EN B52
Alsthom, Cemafluor C26.1 CX Alstom, AREVA,
GEC-Alsthom Schneider Electric
CEM, Delle 3 Cemafluor C26.2 FPR FPR SERED111185EN B43 Merlin Gerin VM6 DM12 FB4 SF1 SERED111018EN B35
3
Alsthom,
GEC-Alsthom GEC-Alsthom, 3 VMX VMX VMX SERED111154EN B53
Alstom, AREVA
CEM, Delle 3 DNF4-2E FP - GFA HVX - LF2 - CVX SERED111187EN B12
Alsthom, AEG, Alstom, 3 WBA VA - VAA VA - VAA SERED111189EN B54
D GEC-Alsthom
CEM, Delle
Alsthom,
3 DNF4 MI&FI FP HVX SERED111196EN B13
AREVA
AEG, Alstom,
AREVA
3 WBA ECA - BAL - AL VA - VAA - Contactor SERED111082EN B36 D
GEC-Alsthom AEG, Alstom, 3 WBB VA - VAA VA - VAA SERED111198EN B55
CEM, Delle 3 DNF5 - DNF5-2B FP HVX SERED111191EN B14 AREVA
Alsthom, AEG, Alstom, 3 WBB ECA - BAL - AL VA - VAA - Contactor SERED111084EN B37
GEC-Alsthom AREVA
E CEM, Delle
Alsthom,
GEC-Alsthom
3 DNF6 FP HVX SERED111192EN B15 AEG, Alstom,
AREVA,
Schneider Electric
3 WBD VA - VAA VA - VAA SERED111195EN B56
E
CEM, Delle 3 DNF7 FP HVX-O2 SERED111190EN B16 AEG, Alstom, 3 WBD HVX-C VA - VAA SERED111129EN B38
Alsthom, GEC- AREVA,
Alsthom, Alstom, Schneider Electric
AREVA,
F F
Schneider Electric AEG, Alstom, 3 WK (A/B/C/D/E/F) VA - VAA VA - VAA SERED111199EN B57
AREVA
Nuova Magrini 3 Epoclad DHF & F LF1 - LF2 - LF3 - SF1 SERED111049EN B17
Galileo AEG 3 WK (A/B/C/D/E/F) MC - AL - BAL - TG VA - VAA - Contactor - LTRI SERED111086EN B39
Merlin Gerin 3 Fluair F100 - F200 FG1 - FG2 Easypact EXE - Evolis - SERED111012EN B18 Yorkshire 3 YSF6 YSF6 YSF6 Evolis SERED111066EN B40
LF2 - LF3 Switchgear
Merlin Gerin 3 Fluair F100C R400 - R400D R400 - R400D SERED111013EN B44 AEG, Alstom, 3 AHA AHA panel AHA panel SERED111167EN B58
AREVA
G G
Merlin Gerin 3 Fluair F300 FG3 HVX-O2 or SF1 - SF2 SERED111101EN B19
CEM, Delle 3 DNF7 DNF7 panel DNF7 panel SERED111100EN B59
Merlin Gerin 3 Fluair F400C FC4 SF2 SERED111014EN B20 Alsthom,
Merlin Gerin 3 Fluair F400G FG4 SF1 - SF2 SERED111015EN B21 GEC-Alsthom
GEC, GEC- HMC400 - HMC 400 - HMC 400 - SERED111061EN B45 Merlin Gerin 3 Fluair F100 - F200 panel F100 - F200 panel F100 - F200 panel SERED111071EN B60
3
Alsthom, Alstom, HMC410 HMC 410 HMC 410 GEC-Alsthom 3 Normaclad PX 12-24 PX 12-24 panel PX 12-24 panel SERED111091EN B61
AREVA
Alstom, AREVA, 3 PIX PIX - SF6 panel PIX - SF6 panel SERED111157EN B62
H H
GEC, GEC- 3 HMC1072 HMC1072 HMC1072 SERED111062EN B46 Schneider Electric
Alsthom, Alstom,
AREVA GEC-Alsthom, 3 VISAX VISAX panel VISAX panel SERED111123EN B63
Alstom, AREVA,
GEC, GEC- 3 HMC1172 HMC1172 HMC1172 SERED111063EN B47 Schneider Electric
Alsthom, Alstom,
AREVA GEC-Alsthom, 3 VMX VMX panel VMX panel SERED111097EN B64
Alstom, AREVA
Concordia Sprecher, 3 HP HP - W - TW - TM HVX - VA SERED111078EN B22
AEG, Alstom, 3 WBA WBA panel WBA panel SERED111081EN B65
I I
Sprecher & Schuh,
GEC-Alsthom, AREVA
Alstom, AREVA AEG, Alstom, 3 WBB WBB panel WBB panel SERED111083EN B66
Schneider HWX HWX HWX SERED111166EN B48 AREVA
3
Electric, GEC, AEG, Alstom, 3 WBD WBD panel WBD panel SERED111128EN B67
GEC-Alsthom, AREVA,
Alstom, AREVA Schneider Electric
GOST standard K104 K104 Evolis - LF SERED111164EN B23 AEG, Alstom, WK WK panel WK panel SERED111085EN B68
J J
3 3
AREVA
GEC, GEC- 3 KAD KAD VMX-540 SERED111162EN B24
Alsthom, Alstom All brands 3 Cradle to Cradle All breaker types Evolis MC Cassette SERED111105EN B41
GOST standard 3 KRU KRU 2-10 EasyPact EXE - Evolis - LF1 SERED111165EN B25 All brands 3 Cradle to Cradle All breaker types F400 Cassette SERED111106EN B42
K K
Discover the ECOFIT™ web selector Discover the ECOFIT™ web selector
se.com/ecofitselector se.com/ecofitselector
A2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 A3
www.se.com www.se.com
Standard & Customized solutions index Standard & Customized solutions index
Low voltage ECOFIT™ standard solutions Protection relays ECOFIT™ standard solutions
How to find an ECOFIT™ solution? How to find an ECOFIT™ solution?
1 Select the " generic family ". 2 Select the " Panel type ". 3 Select the " Original device type ". 1 Select the " generic family ". 2 Select the " Panel type ". 3 Select the " Original device type ".
1 2 3 1 2 3
Original Brand LV CB or LV Drawer Automatic Panel Original device type New device type Flyer N° Page Original Brand Protection relay Panel type Original device type New device type Flyer SERED N° Page
Contactor compensation type Alstom All CDG Easergy P1 / P3 / P5 or SERED111147EN F3
3
General Electric 3 NA AK-(1-2-3-4-5) -15/25 MasterPact MTZ1 SERED111232EN C2 MiCOM P40
Series Westinghouse 3 All CO MiCOM P111/115 SERED111131EN F4
General Electric NA AK-(1A-2A-3A-4A-5A) - MasterPact MTZ1 SERED111249EN C3 ABB All DPU 445 MiCOM P123 SERED111134EN
A A
3 3 F5
15/25 Series ABB 3 All HCB / HCB1 MiCOM P521 SERED111133EN F6
General Electric 3 NA AK-(1-2-3-4-5) - 50 Series MasterPact MTZ2 SERED111250EN C4 General Electric, Basler 3 All IAC, IFC, DIAC and BE1-50/51 B ECOFIT 50/51 SERED111132EN F7
General Electric 3 NA AKR-30 Series MasterPact MTZ1 SERED111247EN C5 Alstom 3 All / draw out MCAG 34 MiCOM P126 SERED111201EN F8
General Electric 3 NA AKR-50 Series MasterPact MTZ2 SERED111248EN C6 AREVA 3 All / draw out M range - MCGG 11, 21 & 22 MiCOM P120H SERED111104EN F9
General Electric 3 NA AKRT-50 Series MasterPact MTZ2 SERED111246EN C7 AREVA 3 All / draw out M range - MCTI 39-40 MiCOM P821MF SERED111103EN F10
B B
Nuova Magrini Galileo 3 NA B Control MasterPact MTZ1 - MTZ2 SERED111053EN C8 ALSTOM, AREVA 3 All MCGG 62 MiCOM P126 SERED111135EN F11
Merlin Gerin 3 NA ComPact C801-C1251 ComPact NS800 - NS1250 SERED111022EN C9 Alstom 3 All MVTR 51 MiCOM P123 SERED111203EN F12
Merlin Gerin 3 NA DA MasterPact MTZ2 - MTZ3 SERED111019EN C10 Merlin Gerin, Schneider Electric 3 All Sepam series 20 Easergy P3 SERED20036EN F13
Cutler-Hammer, 3 NA DS-206, DS-206H, MasterPact MTZ2 SERED111235EN C11 Merlin Gerin, Schneider Electric 3 All Sepam series 40 Easergy P3 SERED20037EN F14
Westinghouse DS-206E Series Alstom, AREVA, Schneider Electric 3 All MiCOM Px20 (20TE) Easergy P5 SERED111202EN F15
Square D 3 NA DS-206, DS-206H, MasterPact MTZ2 SERED111240EN C12 Alstom, AREVA, Schneider Electric 3 All MiCOM Px20 (30TE) Easergy P5 SERED111286EN F16
DS-206E Series
C C
Merlin Gerin, Schneider Electric 3 All Sepam series 20 Easergy P5 SERED111204EN F17
Cutler-Hammer, 3 NA DS-416, DS-416S, MasterPact MTZ2 SERED111234EN C13 Merlin Gerin, Schneider Electric 3 All Sepam series 40 Easergy P5 SERED111285EN F18
Westinghouse DS-416H Series Merlin Gerin All Sepam 2000 Sepam series 60 or series 80 SERED111087EN F19
3
Square D 3 NA DS-416, DS-416S, MasterPact MTZ2 SERED111241EN C14
DS-416H Series
Cutler-Hammer, 3 NA DS-420 Series MasterPact MTZ2 SERED111233EN C15 How to find an ECOFIT™ solution?
Westinghouse
D Square D
Federal Pioneer
3
3
NA
NA
DS-420 Series
H series
MasterPact MTZ2
MasterPact MTZ
SERED111238EN
SERED111068EN
C16
C17
1 Select the " generic family ". 2 Select the " Original device type ".
D
Substation automation ECOFIT™ standard solutions
ITE, ABB, BBC 3 NA K-225, K-600, K-800 Series MasterPact MTZ1 SERED111245EN C18
ITE, ABB, BBC 3 NA K-1600 Series MasterPact MTZ2 SERED111244EN C19
ITE, ABB, BBC 3 NA KDON-600, KDON-800, MasterPact MTZ1 SERED111243EN C20
KDON-1600 Series
1 2
F F
Schneider Electric 3 ADVC Lite ADVC 3 SERED111221EN G9
Square D, Westinghouse 3 NA SE MasterPact MTZ2 SERED111039EN C26
Alstom, AREVA 3 Bay Controller BM9x00 MiCOM C264 SERED111144EN G10
Merlin Gerin 3 NA SelPact MasterPact MTZ2 - MTZ3 SERED111020EN C27
Alstom, AREVA 3 DCX MiCOM C264 SERED111217EN G11
Schneider Electric 3 NA MasterPact NT-NW MasterPact MTZ C28 General Electric GE FANUC Quantum or M580 PLC & EcoSUI EWS SERED111169EN G12
3
Merlin Gerin 3 NA LV Circuit Breaker - C30 AREVA 3 PACIS OI V3.X up to V4.6 PACiS EcoSUI NRJED113543EN G13
Associated offers
AREVA 3 PSCN3020 HMI EcoStruxure Substation Operation user interface NRJED113562EN G14
Merlin Gerin T140 T140 drawers T140 drawers SERED111094EN C31
G G
3
Schneider Electric 3 PTCC ADVC 3 SERED111222EN G15
Merlin Gerin 3 MB400 MB400 drawers MB400 drawers SERED111095EN C32
Schneider Electric 3 Seefox HMI EcoStruxure Substation Operation user interface SERED111143EN G16
Merlin Gerin 3 NA LV Drawers - C33
Associated offers
I 1 Select the " generic family ". 2 Select the " Panel type ". 3 Select the " Original device type ".
Merlin Gerin, Schneider Electric
Merlin Gerin, Schneider Electric
Schneider Electric, Square D
3
3
3
Varset
Varlogic
PM, ME, iME, EN basic meters
VarSet and VarSet Fast
VarPlus Logic
New range
SERED111287EN
SERED111348EN
SERED111349EN
H4
H5
H6
I
Schneider Electric, Square D 3 CM, DM, ION & PM meters PMxxxx range & ION9000 SERED111350EN H7
ION-E 3 ION-E, SPM & PME software PME 2020 SERED111351EN H8
1 Schneider Electric Power Manager software Energy Expert software SERED111352EN H9
3
Original Brand Dry Oil Original device type New device type Flyer N° Page
J J
Schneider Electric, Square D 3 PLS & PSO software PSO 2020 SERED111353EN H10
All brands 3 All Trihal SERED111218EN D2 Merlin Gerin, Schneider Electric 3 XM, XL, XD, XLI, XTU IMDIFL SERED111354EN H11
All brands 3 All Minera SERED111219EN D3 AREVA, then Schneider Electric 3 MRxxx and MZxxx series IMD-IM20 or IMD-IM400 SERED20040EN H12
MRxxx System
Schneider Electric, Square D 3 Gateway PowerTag Link xxx, Com'X SERED111355EN H13
range or Panel Server
K K
Discover the ECOFIT™ web selector Discover the ECOFIT™ web selector
se.com/ecofitselector se.com/ecofitselector
A4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 A5
www.se.com www.se.com
Standard & Customized solutions index Standard & Customized solutions index
Medium voltage ECOFIT™ customized solutions Medium voltage ECOFIT™ customized solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request. Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric can help you to identify the right solution to modernise your installation with a site visit if required. Schneider Electric can help you to identify the right solution to modernise your installation with a site visit if required.
Original Brand Panel type Original device type Un (kV) In (A) Isc (kA) New device type Original Brand Panel type Original device type Un (kV) In (A) Isc (kA) New device type
ABB AIS E7512 / 10 10 1250 40 HWX EIB, AEG, Alstom, AREVA AIS DEC x-xx/x F (CRR1000) (frontal) up to 40,5 up to 2500 up to 31,5 ISF2
ABB AIS EKU5012 / 10 10 1250 50 HWX at 24kV; up
ABB AIS EKU5016 / 10 10 1600 50 HWX to 25kA at
ABB AIS EKU5025 / 10 10 2500 50 HWX 36/40,5kV
ABB AIS GR256 12 630 13,1 HWX Federal Pacific AIS DST - DST2 4,16 1200, 2000,3000 29-41 Magnum
ABB AIS HB12-12-40 24 1600 25 Evolis Federal Pacific AIS DST - DST2 13,8 1200, 2000 18-28 Magnum
ABB VHE800 HKK12 / 1226 12 1250 26,3 HWX FUJI HF HF5150 - 10M 12 1250 40 Evolis
A ABB
ABB
ABB
VHE800
VHE950
AIS
HKK12 / 1240
HKK12 / 3140
JVE301
12
12
12
1250
2500
400
40
40
40
HWX
HWX
HWX
FUJI
FUJI
FUJI HF
AIS
HF55
HF5150 - 10M
HF515
OCB
12
13,8
7.2
2000
3000
600
40
26,2
25
HVX IEC
3AH3
Evolis
A
ABB AIS MS 2 12 1250 40 HWX GEC BVX KAD 12 400 to 1250 up to 20 VMX
ABB AIS MS 3 12 1600 40 HWX GEC Alstom Fluokit M36 FP 36 630 29 CBX
ABB AIS MT1 12 1250 26,3 HWX General Electric AIS AM 4,16 400 Fused Magnum
ABB AIS MT2 12 1250 26,3 HWX General Electric AIS AM 4,16 1200, 2000,3000 40 Magnum
B B
ABB AIS OD1M 12 400 26,3 HWX General Electric AIS AM 7,2 1200, 2000, 3000 33 Magnum
ABB AIS S F ASG 12-16 1250 to 2500 26-40 HWX General Electric AIS AM 13,8 1200, 2000 18 up to 37 Magnum
ABB Caloremag OD3/OD4 7.2 1250 31,5 LF2 General Electric AIS AM - 7.2 7,2 1200, 2000, 3000 33 Magnum
ABB VHA-12S VRC 7,2 400 25 LF General Electric AIS AM - 13.8 Tall-Boy 13,8 3000 37 Magnum
ABB HA3zc GCB 12 630 to 2500 40 LF General Electric AIS AM - 4.16 4,16 600, 1200 20 Magnum
AEG FKCM4 / 24-2 VA / VAA / LTRI / AL 24 up to 1250 up to 25 VA/VAA General Electric AIS AMH 4,76 1200, 2000 29 Magnum
AEG FKCM5 / 12-2 VA / VAA / LTRI / AL 12 up to 1250 up to 25 VA/VAA General Electric AIS AMH - 4.76 4,76 1200, 2000 29 Magnum
Hitachi MV cubicle CVG - 15F - 25 7,2 630 25 Evolis
C C
AEG FKEM4 / 24 - 2 / 721 VA / VAA / LTRI / AL 24 up to 1250 up to 25 VA/VAA
AEG FKEM4 / 24 - 2 / 723 VA / VAA / LTRI / AL 24 up to 1250 up to 25 VA/VAA Hitachi HW MGH 10L - 25 13,8 630 25 VA 8012/17 P210 or 3AH5
AEG, Alstom, AREVA AHA ECA 12 1200, 2500, 4000 31.5 / 50 HVX-O2 Hitachi HB MGH 10L - 25 13,8 1250 25 VA 8012/17 P210 or 3AH5
ALIND AIS HL430 12 1250 40 HWX Hitachi HB MGH 10T - 25 13,8 1600 25 VA 8020/17 P210 or 3AH5
Allis-Chalmers & Siemens-Allis AIS FA 4,16 3000 41 Magnum Hitachi HW MGH 10V - 25 13,8 2000 25 VA 8020/17 P210 or 3AH5
Allis-Chalmers & Siemens-Allis AIS MA 4,16 1200, 2000 40 & 50 Magnum Inoue AIS HVX 12 630 - 1600 31,5 HVX
Allis-Chalmers & Siemens-Allis AIS FB 7,2 &13,8 1200, 2000 18 Magnum ITE AIS 5-HV 4,16 1200, 2000 29 to 40 Magnum
Allis-Chalmers & Siemens-Allis AIS FC, MC 13,8 1200, 2000, 3000 18 - 28 Magnum
D D
ITE / ABB AIS 5-HK 4,16 1200, 2000, 3000 40 to 50 Magnum
Allis-Chalmers & Siemens-Allis AIS FC 13,8 1200, 2000 37 Magnum ITE / ABB AIS 7.5-HK 7,2 1200, 2000 33 Magnum
ALSTHOM FP HVX 24 630 25 HVX ITE / ABB AIS 15-HK 13,8 1200, 2000, 3000 18 to 37 Magnum
Alsthom NORMABLOC-DNL4 HL 12 2500 40 FPX JYOTI AIS MT2-1208-20 12 1250 25 Evolis
Alsthom WBS VB6 24 1250A 25KA HVX-O2 LG AIS GVB 7.2 630 31.5 Evolis
Alstom GMA Version 1 GMA 12 2000 25 GMA Version 2 McGraw AIS PSD 13,8 1200, 2000 18 Magnum
Alstom NORMAFLUOR-DNF4 FP 17.5 2500 25 HVX McGraw AIS WSA 13,8 1200, 2000 18 Magnum
Alstom AHA ECA up to 17.5 1250 31.5 HVX-O2 Merlin Gerin V23-60 DIS23-D3 24kV 630A 25 SF
E Alstom
Alstom / AREVA / Schneider Electric
Sachsenwerk
Fluokit-M9
CB
VB x-xx/x L G3 (CRR1-2) (lateral)
12
up to 24
630
up to 1250
16
up to 25
SF1
Evolis (vacuum lateral) - SF1
(lateral)
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Flurin
Lorin
Flurin
FG1
FG1, FG2
FG2
17.5
17.5
17.5
1250
1250
1250
25
25
25
LF
LF
LF
E
Alstom / AREVA / Schneider Electric Fluokit-M9 DPI x-xx/x L G3 (CRR1-2) (lateral) up to 24 up to 1250 up to 25 SFset (SF6 - lateral) Merlin Gerin / Lorenzetti Inebrasa CCM III VC TOYO 7.2 400 50 Rollarc
Alstom / AREVA / Schneider Electric Fluokit-M9 VBL 12-17.5 630-1250 up to 25 Evolis or SF1 Merlin Gerin / Lorenzetti Inebrasa CCM II C1 7,2 400 50 Rollarc
Alstom / AREVA / Schneider Electric Fluokit-M9 DPIL 12-17.5 630-1250 up to 25 SFset Mitsubishi AIS VF / FM 12 1250 31.5 Evolis
Alstom / AREVA / Schneider Electric GIS CBR 27.5 1250-2000 25 CBR Mitsubishi AIS 6 DHE 32 M 4.76 1200 to 2000 29 LF
F F
Alstom / AREVA / Schneider Electric GIS SDR 17-27.5 1250-1600 12.5 SDR NGEF AIS E7512 12 1600 25 Evolis
ARTECHE AIS HAF6142 - 4 24 1250 25 Evolis NGEF AIS E7525 12 1250 40 Evolis
ASEA VHE-800 HKK 12 1600 40 Evolis NGEF AIS EKU 5012 12 2500 40 Evolis
ASEA VHE HCA 24 / 1225 24 1250 25 VAA 6312/24 P275 or 3AH5 NGEF AIS EKU 5016 12 2500 40 Evolis
ASEA VHE HCA 24 / 2540 24 2500 25 VA 6325/24 P2753AH5 or 3A NGEF AIS EKU 5025 7,2 2500 40 Evolis
ASEA VHE, VHD HKK 12 up to 3150 up to 40 EVOLIS, LF1, LF2, HVX, VA NGEF AIS EKU 5025 12 1250 40 Evolis
ASEA VHE, VHD HKK 24 up to 2500 up to 25 HVX NGEF AIS EKU 5025 / 10 10 2500 50 Evolis
G G
BBC, EIB AIS DB (frontal) 17 up to 1250 up to 25 HVX17 / SF1 NGEF AIS EKU - GR256 12 1250 31.5 Evolis
CGL AIS SFG-40S 7,2 1250 31.5 Rollarc NGEF AIS EKU 5012 / 10 6.6 1250 30.6 Evolis
Calor Emag AIS OD3 12 630 to 1250 31.5 Evolis NGEF AIS GR256 12 1250 31.5 Evolis
Calor Emag AIS OD4 12 630 to 1250 31.5 Evolis NISSIN AIS VSR 7.2 400A 4 CTV
CONCORDIA SPRECHER PIC-106 HP 12-24 up to 1600 up to 25 HVX NMG AIS 10 MG 500 7.2 630A 25 LF
CONCORDIA SPRECHER PID 104 / 105 / 106 HP 12-24 up to 1600 up to 25 HVX SACE AIS D6 17.5 1250 25 LF
CONCORDIA SPRECHER SC - SD 204 / 206 HVTW(z) 12-24 up to 1600 up to 25 HVX SACE DIARC DR 17.5-50 17.5 800, 1250, 3150 20 HVX
SHINKO MV cubicle HL6-9 24 630 25 SF1
H H
CONCORDIA SPRECHER SCC 204 / 206 HPCTW 12-24 up to 1600 up to 25 HVX
CONCORDIA SPRECHER SCD 204 HPDTW 12-24 up to 1600 up to 25 HVX SIEMENS 8AA20 3AH1 12 800 20 VA 5012/12 P210 or 3AH1
DELLE ALSTHOM MV cubicle HP75-125 / 35KV 36 320 31,5 SF2-F400 SIEMENS 8BC 3AB - 10N / 4000 7,2 4000 73 3AH3
DELLE NORMABLOC - DN6S HG 24 2500 25 FP SIEMENS 8BC 3AB - 10N / 2500 7,2 2500 40 3AH3
DELLE NORMABLOC - DN6S HL 24 1250 25 FP SIEMENS 8BD1 3AC 7.2 630 to 2000 25 Evolis
DELLE NORMABLOC - DNL4 HK & HL 12 2500 40 HVX SIEMENS 8BD1 CB 7.2 630 to 2000 40 Evolis
DELLE NORMABLOC - DNTL HL 12 1250 40 FPX SIEMENS 8BD1 3AC 7,2 630 40 Evolis
DELLE NORMABLOC - DNTC CHT 7,2 200 25 GFA SIEMENS 8BD1 3AC 12 1250 to 2500 40 HWX
I DELLE
DELLE
DELLE
NORMABLOC - DNTG
NORMABLOC - N142
NORMABLOC - N143
HL
RA
HK
7,2
17.5
17.5
3200
400
630
40
25
16
FP
GFA or FP
FP
SIEMENS
SIEMENS 8BK20
AIS
3AH 1115 - 2
H512 / H515
12
12
1250
1250
31,5
31.5
VA 8025/12 P210 or 3AH5
Evolis I
SIEMENS AIS 3TL / 1BF 7.2 450 6 CVX
DELLE NORMABLOC - N340 FJ 23 400 12.5 FP SIEMENS GWS H515 24 630 16 HVX 24-16-06F210 or VD4
DELLE NORMABLOC - N342 RA 23 200 12.5 FP 2406-16
DELLE NORMABLOC - N1147 HL 12 1250 40 FPX SIEMENS GWHS 3AH1 12 630 25 HVX 12-25-06F150 or VM1
DELLE NORMABLOC - ND3 HG or HK or HL 7,2 1250 12.5 FP 12.06.25
J DELLE
DELLE
DELLE
NORMABLOC - ND5
NORMASEPT - N740
NORMASEPT - N1742
HG
HL
RA
17.5
24
24
1250
400
200
12.5
14.5
16
FP
FP
FP
SILIN
Square D
Square D
MV cubicle
AIS
AIS
B4SE0796011
DSE
DSE23
36
4,16
4,16
1250
1200
2000
25
29
29
HVX-O2 ( EP)
Magnum
Magnum
J
DELLE FLUOMATIC - N962 SFC 7,2 400 12.5 GFA Square D AIS DSE25 4,16 3000 41 Magnum
Delta H2000 LF1, LF2, LF3, EVOLIS 12 - 24 1250 25 - 40 LF1, LF2, LF3, EVOLIS Square D AIS DSE-65 13,8 1200 up to 28 Magnum
Delta MSX HVX, VA 12 - 24 2500 - 3150 25 - 40 HVX, VA Square D AIS DSE-68 13,8 3000 37 Magnum
EGEMAC 8BK 3AF6542-4 24 1250 25 VAA 6312/24 P275 or 3AH3
K EIB
EIB
A6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 A7
www.se.com www.se.com
Standard & Customized solutions index Standard & Customized solutions index
Medium voltage ECOFIT™ customized solutions Low voltage ECOFIT™ customized solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request. Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric can help you to identify the right solution to modernise your installation with a site visit if required. Schneider Electric can help you to identify the right solution to modernise your installation with a site visit if required.
Original Brand Panel type Original device type Un (kV) In (A) Isc (kA) New device type Original Brand Panel type / Range Original device type Type In (A) New device type
Square D AIS VAD2 4,16 1200 up to 41 Magnum Federal Pacific FP FP - 50 - H3, 21" Frame (ANSI) 800 MasterPact NT/NW/MTZ
Square D AIS VAD2 13,8 1200, 3000 37 Magnum Federal Pacific FP FP - 50 - H3, 21" Frame (IEC & ANSI) 2000 MasterPact NT/NW/MTZ
Square D AIS VAD3 4,16 1200, 2000 up to 41 Magnum Federal Pacific FP FP-75 3200 MasterPact NT/NW/MTZ
Square D AIS VAD3 13,8 1200, 2000 up to 28 Magnum Federal Pioneer HL 25HL-2 800 MasterPact NT/NW/MTZ
Toshiba AIS HVX 7,2 1250 40 HVX Federal Pioneer HL 25HL-2 600 MasterPact NT/NW/MTZ
VOIGHT HAEFFENER MV cubicle 10 / 100 LAD - 6 10 1000 31,5 LF2 MCset Federal Pioneer HL 35HL-2 800 MasterPact NT/NW/MTZ
VOLTAS AIS BMTT 12 1250 26,3 HWX Federal Pioneer HL 50HL-2 1600 MasterPact NT/NW/MTZ
A VOLTAS
VOLTAS
VOLTAS
AIS
AIS
AIS
BE
BEC
BMTT
12
12
12
1250
1250
1250
40
40
40
HWX
HWX
HWX
Federal Pioneer
Federal Pioneer
General Electric
HL
HL
AE-1B (M.O.)
65HL-2
75HL-2
AE - 1B (M.O.)
2000
3000
800
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ
A
VOLTAS AIS FB4 24 2000 25 Evolis General Electric AK AK - (2A/3A/4A/5A)-50 1600 MasterPact NT/NW/MTZ
VOLTAS AIS FB4 36 1250 25 SF General Electric AKR AKR/AKRT - 30 (AKD-8 swgr) 800 MasterPact NT/NW/MTZ
VOLTAS AIS FB4 Kiosk 22 630 25 Evolis General Electric AKR AKR with Contactor 540 MasterPact NT/NW/MTZ
VOLTAS AIS FG2 12 1250 40 Evolis or LF General Electric AKR AKRU - 30 (1 Position) 800 MasterPact NT/NW/MTZ
B VOLTAS
VOLTAS
VOLTAS
AIS
AIS
AIS
FG2
FG2
FG2
7,2
7,2
12
2000,2500,3150
1250
1250
40
31.5/ 40
40
Evolis or LF
Evolis or LF
Evolis or LF
General Electric
General Electric
General Electric
AKR
AKR
AL
AKRU - 50 (1 Position)
AKR - 75 (3 Pos./Ver. Bus)
AL - 2-50 (M.O.)
1600
3200
1600
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ
B
VOLTAS AIS FG2 12 1250 40 HWX General Electric Any M-Pact 800 - 4000 MasterPact NW/ MTZ
VOLTAS AIS FP 12 1250 40 HWX General Electric Any Power Break 800 - 3000 MasterPact NT/NW/MTZ
VOLTAS AIS GHM 12 1250 40 Evolis General Electric Any Power Break 2 800 - 2000 MasterPact NT/NW/MTZ
VOLTAS AIS HF 12 1250 40 Evolis Any Record 800 - 1600 MasterPact NT/MTZ
General Electric
C C
VOLTAS AIS HKK 12 1250 40 HWX
Hundt & Weber Any HN / HE 800 - 3150 MasterPact NT/NW/MTZ
VOLTAS AIS HKO 12 1250 40 HWX
VOLTAS AIS HL 12 1250 40 Evolis Hundt & Weber Any LH 800 - 3150 MasterPact NT/NW/MTZ
Westinghouse AIS 50 - DH 4,16 1200, 2000 29 / 41 Magnum Hundt & Weber Any LS 800 - 1000 MasterPact NT/MTZ
Westinghouse AIS 75 - DH 7,2 1200, 2000 33 Magnum Holec Any Torsimat 72G/H/K/M/P 1250 - 4000 MasterPact NT/NW/MTZ
Westinghouse AIS 150 - DH 13,8 1200, 2000 18 / 28 Magnum Hyundai Any HAT 600 - 2500 MasterPact NT/NW/MTZ
Westinghouse AIS 150 - DH 13,8 1200, 2000, 3000 37 Magnum ITE / ABB / BBC K-Line K-600 / K-800 with MOC/TOC 800 MasterPact NT/NW/MTZ
Westinghouse AIS 50 - DH 4,16 1200, 2000 29 / 41 Magnum ITE / ABB / BBC K-Line K-2000 / K-2000S with TOC 2000 MasterPact NT/NW/MTZ
D Westinghouse
Westinghouse
Westinghouse
AIS
AIS
AIS
50 - DHP
75 - DHP
75 - DHP
4,16
7,2
7,2
1200, 2000, 3000
1200, 2000, 3000
320
41
33
Fused
Magnum
Magnum
Magnum
ITE / ABB / BBC
ITE / ABB / BBC
K-Line
K-Line
KB
KC
600
1600
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ D
ITE / ABB / BBC MB MB-8 / MBE-8 800 MasterPact NT/NW/MTZ
Westinghouse AIS 150 - DHP 13,8 1200, 2000 18 / 28 Magnum ITE / ABB / BBC MB MB-16 / MBE-16 1600 MasterPact NT/NW/MTZ
Westinghouse AIS 150 - DHP 13,8 3000 33 Magnum ITE / ABB / BBC K-Line LKE-8 800 MasterPact NT/NW/MTZ
Westinghouse AIS 5WYB 4,16 1200, 2000, 3000 41 Magnum KAFAK KAFAK SFBY 250 ComPact NSX
Westinghouse AIS 8WYB 7,2 1200, 2000, 3000 33 Magnum KAFAK KAFAK SFBY 630 ComPact NSX
E Westinghouse
Westinghouse
Westinghouse
AIS
AIS
DHP
15WYB
15WYB
Air Circuit Breaker
13,8
13,8
5
1200, 2000
3000
1200
18 / 28
33
31.5
Magnum
Magnum
EVOLIS
Merlin Gerin
Merlin Gerin
Merlin Gerin
ComPact CM
ComPact CM
InterPact
CM 1250 3P Fixed Front
CM 1600 4P HH Fixed
IN IN2500A 3P Fixed
1250
1600
2500
ComPact NS
MasterPact NT/NW/MTZ
InterPact INS
E
Mitsubishi Any AE 630 - 5000 MasterPact NT/NW/MTZ
Any SS 1000 - 1600 MasterPact NT/MTZ
F Original Brand
ABB
Panel type / Range
Novomax
Original device type
NovomaxG2
Type In (A)
1250 - 2000
New device type
MasterPact NT/NW/MTZ
Siemens
Siemens
Any
Any
3WE
3WL
1000 - 4000
1000 - 5000
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ F
Siemens Any 3WN1 630 - 3200 MasterPact NT/NW/MTZ
ABB Novomax NovomaxG3 1600 - 2000 MasterPact NT/NW/MTZ
Siemens Any 3WN6 630 - 3200 MasterPact NT/NW/MTZ
ABB Novomax NovomaxG5 4500 MasterPact NT/NW/MTZ
Any Emax E1 800 - 1600 MasterPact NT/MTZ Siemens Any SBS 1200 - 2000 MasterPact NW/MTZ
ABB
Any Emax E2 800 - 2000 MasterPact NT/NW/MTZ Square D Any MP-08 / MP-16 800 - 1600 MasterPact NT/NW/MTZ
ABB
G G
Square D Any MP-20 2000 MasterPact NT/NW/MTZ
ABB Any Emax E3 800 - 3200 MasterPact NW/MTZ
Square D Any MP-25 / MP-30 2500 - 3000 MasterPact NT/NW/MTZ
ABB Any Emax E4 3200 - 4000 MasterPact NW/MTZ Square D Any SED 800 - 3000 MasterPact NT/NW/MTZ
ABB Any Emax E6 3200 - 6300 MasterPact NW/MTZ Square D Any SEM (SED-M) 800 - 2000 MasterPact NT/NW/MTZ
ABB Any Megamax E1 1250 - 2000 MasterPact NT/NW/MTZ Square D DSII DSII-308 800 MasterPact NT/NW/MTZ
ABB Any Megamax E2 2000 - 2500 MasterPact NW/MTZ Square D DSII DSII-508 800 MasterPact NT/NW/MTZ
ABB Any Megamax E3 2000 - 3000 MasterPact NW/MTZ Square D DSII DSII-608 800 MasterPact NT/NW/MTZ
Square D DSII DSII-516 1600 MasterPact NT/NW/MTZ
H H
ABB Any Megamax E4 3200 MasterPact NW/MTZ
Any Megamax E5 3200 MasterPact NW/MTZ Square D DSII DSII-616 1600 MasterPact NT/NW/MTZ
ABB
Square D DSII DSII-620 2000 MasterPact NT/NW/MTZ
ABB Any Megamax E6 6300 MasterPact NW/MTZ
Terasaki Any AH 1000 - 3000 MasterPact NT/NW/MTZ
ABB Any Novomax G2 1250 - 3000 MasterPact NT/NW/MTZ
Terasaki Any AT 630 - 3200 MasterPact NT/NW/MTZ
ABB Any Novomax G3 1600 - 2500 MasterPact NW/MTZ
Unelec Any CN2-CN3 800 - 4000 MasterPact NT/NW/MTZ
ABB Any Novomax G30 800 - 1000 MasterPact NT/MTZ
Unelec Any CNP 1000 - 2500 MasterPact NT/NW/MTZ
ABB Any Novomax G4 3200 MasterPact NW/MTZ
I I
Unelec Any SP 1000 - 2500 MasterPact NT/NW/MTZ
ABB Any Novomax G5 4000 - 5000 MasterPact NW/MTZ
Westinghouse / Cutler Hammer / Eaton DB DB - 15 Three Position (in DB-25 cell) 225 MasterPact NT/NW/MTZ
ABB Any Otomax 2000 MasterPact NW/ MTZ Westinghouse / Cutler Hammer / Eaton DB DB - 25 Three Position 800 MasterPact NT/NW/MTZ
ABB Any Otomax P1 800 - 3000 MasterPact NT/NW/MTZ Westinghouse / Cutler Hammer / Eaton DB DB - 25 Single Position 800 MasterPact NT/NW/MTZ
ABB Any Otomax P2C 1000 - 4000 MasterPact NT/NW/MTZ Westinghouse / Cutler Hammer / Eaton DB DBL - 25 Three Position 800 MasterPact NT/NW/MTZ
ABB Any Otomax VTM 1250 MasterPact NT/MTZ Westinghouse / Cutler Hammer / Eaton DB DB - 50 Single Position 1600 MasterPact NT/NW/MTZ
AEG Any ALG 2000 MasterPact NW/MTZ Westinghouse / Cutler Hammer / Eaton DB DB - 50 Three Position 1600 MasterPact NT/NW/MTZ
Westinghouse / Cutler Hammer / Eaton DSII DSII - 308 800 MasterPact NT/NW/MTZ
J J
AEG Any M 1000 - 3000 MasterPact NT/NW/MTZ
Any ME 400 - 6300 MasterPact NT/NW/MTZ Westinghouse / Cutler Hammer / Eaton DSII DSII - 508 800 MasterPact NT/NW/MTZ
AEG
Westinghouse / Cutler Hammer / Eaton DSII DSII - 608 800 MasterPact NT/NW/MTZ
ASEA Any ALG 1250 - 3200 MasterPact NW/MTZ
Westinghouse / Cutler Hammer / Eaton DSII DSII - 516 1600 MasterPact NT/NW/MTZ
ASEA/ABB VMG VMG 800 MasterPact NT/NW/MTZ Westinghouse / Cutler Hammer / Eaton DSII DSII - 616 1600 MasterPact NT/NW/MTZ
ASEA/ABB VMG VMG 1250 MasterPact NT/NW/MTZ Westinghouse / Cutler Hammer / Eaton DSII DSII - 620 2000 MasterPact NT/NW/MTZ
ASEA/ABB VMG VMG 1600 MasterPact NT/NW/MTZ
ASEA/ABB VMG VMG 2000 MasterPact NT/NW/MTZ
K K
ASEA/ABB VMG VMG 2500 MasterPact NT/NW/MTZ
ASEA/ABB VMG VMG 3200 MasterPact NT/NW/MTZ
Federal Pacific FM FM - 600 Fused 600 MasterPact NT/NW/MTZ
Federal Pacific
Federal Pacific
FM
FP
FM - 1600 Fused
FP - 25 / FPS - 25
1600
800
MasterPact NT/NW/MTZ
MasterPact NT/NW/MTZ
Discover the ECOFIT™ web selector
Federal Pacific FP FPS - 30 800 MasterPact NT/NW/MTZ
Federal Pacific FP FP - 50 1600 MasterPact NT/NW/MTZ se.com/ecofitselector
Federal Pacific FP FP - 50 - H3, 14" Frame (IEC) 800 MasterPact NT/NW/MTZ
A8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 A9
Medium Voltage distribution
www.se.com www.se.com
A10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2020 B1
www.se.com www.se.com
PE91038
PE90542
PE90544
End of full
End of spare parts
Commercialization commercialization availability
End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D VAD2 VAD3 VAD2 VAD3 3AC - H515 D
Rated current (Ir) 1200 - 3000 A Rated current (Ir) 630 - 1250 - 2500 A
Short circuit current (Isc) 29 kA 41 kA 18-28 kA 37 kA Short circuit current (Isc) 25 - 31.5 kA
E E
Rated voltage Un (50/60 Hz) 5 kV 15 kV Rated voltage Un (50/60 Hz) 12 kV
Magnum 5SSB Magnum 15SSB Magnum 5SSB Magnum 15SSB EasyPact EXE EasyPact EXE
Technology Vacuum Vacuum Rated current Ir (A) 1200 - 3000 1200 - 3000 Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 5 15 Short circuit current Isc (kA) 29-41 18-28 Rated voltage Ur (kV) 12 O-0.3 s-CO-15 s-CO
O-3 min-CO-3 min-CO
F Surge withstand voltage Up (kV) 60
Nominal frequency (Hz) 60
95
60
Switching sequence
Opening time (ms)
O-0.3 s-CO-15 s-CO
60 60
Surge withstand voltage Up (kV) 75 Closing time (ms) 50 F
Nominal frequency (Hz) 50 - 60 Opening time (ms)
Rated current Ir (A) Up to 2300 Number of switching 10 000
Magnum CB main characteristics
operations
Built with totally new components and tested to ANSI standards, (Less down time for installation + Enhanced equipment reliability). Short circuit current Isc (kA) 31.5
G Magnum circuit breakers correctly interface with the existing breaker
compartment components and maintain safety interlocks inherent in
• Manufactured with new components.
• Undergoes complete factory testing.
Short circuit duration Tk (s) 3 Service temperature (°C) - 25 / + 40 G
the original equipment design. • Backed by our standard equipment warranty.
• New circuit breakers are installed in existing switchgear. • New, easy-to-maintain operating mechanism.
• Original footprint is left intact, saving time and money. • No bulky arc chutes to handle and maintain.
• Installation expense is a fraction of new equipment costs. • Reduced need for difficult to obtain spare parts.
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
T°, Humidity, CB health status Vacuum solutions may require Vacuum solutions may require
See page E1 overvoltage protections overvoltage protections
B2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B3
www.se.com www.se.com
ECA
1972 1986 1988 2001 A
PE91041
DSE22 to DSE78
HVX-O2
PE90400
PE90401
Evolis - LF2 - LF3 - SF1
ECOFIT™ solution
B B
PE91042
PE91040
ECOFIT™
End of com- solution
Commercialization mercialization End of full spare parts availability
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV
HVX-O² HVX-O² LF2/LF3 LF2/LF3 SF1 Evolis LF2/LF3 LF2/LF3 SF1 Evolis
Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO Technology SF6 SF6 SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 12 Rated voltage Ur (kV) 7.2 - 12 17.5 24 7.2 - 12 - 17.5 O-0.3 s-CO-15 s-CO
F Surge withstand voltage Up (kV) 95 Closing time (ms) 35 Surge withstand voltage Up (kV) 60 - 75 95 125 60 - 75 - 95 Closing time (ms) < 72 < 65 < 65 F
Nominal frequency (Hz) 50 Opening time (ms) 53 Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 654 < 50 < 50
Rated current Ir (A) Up to 4000 Number of switching 10 000 Rated current Ir (A) 630 - 3150 630 - 3150 630 - 1250 630 - 2500 Number of switching 10 000 10 000 10 000 10 000*
operations operations
G G
Short circuit current Isc (kA) 29 - 50 29 - 40 10 - 25 40
Short circuit current Isc (kA) Up to 40 Short circuit duration Tk (s) 3 3 3 4 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
Short circuit duration Tk (s) 3 Service temperature (°C) -5/+40 * class MI: 2000 operations for Isc = 40 kA
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require with LF circuit breaker Vacuum solutions may require
overvoltage protections T°, Humidity, CB health status overvoltage protections
See page E1
B4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B5
www.se.com www.se.com
PE90396
DSE22K - DSE23K DIS
PE90403
PE90404
PE90397
PE90398
B
ECOFIT™ solution
B
ECOFIT™
solution
End of full spare
Commercialization End of commercialization parts availability End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D DSE22K - DSE23K DIS D
Rated current (Ir) 630 - 1250 A Rated current (Ir) 400 - 1250 A
Short circuit current (Isc) 25 - 31.5 kA Short circuit current (Isc) 25 - 31.5 kA
E E
Rated voltage Un (50/60 Hz) 7.2 kV Rated voltage Un (50/60 Hz) 7.2 kV
LF1 Evolis LF1 Evolis LF1 R400 R400D Evolis LF1 R400 R400D Evolis
Technology SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO Technology SF6 SF6 SF6 Vacuum Switching sequence O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 7.2 Rated voltage Ur (kV) 7.2 7.2 7.2 7.2
F F
O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 60 Closing time (ms) < 72 < 65 Surge withstand voltage Up (kV) 60 60 60 60 Closing time (ms) < 72 75 - 155 75 - 155 < 65
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 54 < 50 Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 54 20 - 50 20 - 50 < 50
Rated current Ir (A) 630 - 1250 630 - 1250 Number of switching 10 000 2000* - 10 000 Rated current Ir (A) 630 - 1250 400 400 630 - 2500 Number of switching 10 000 30 0000 10 0000 10 000
operations operations
G Short circuit current Isc (kA)
Short circuit duration Tk (s)
25 - 31.5
3
25 - 31.5
3 Service temperature (°C) - 25 / + 40 - 25 / + 40
Short circuit current Isc (kA)
Short circuit duration Tk (s)
31.5
3
10*
3
10*
3
25 - 31.5
3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
G
* class MI: 2000 operations for Isc = 40 kA * With fuses
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air
J
with LF circuit breaker Vacuum solutions may require with LF circuit breaker Vacuum solutions may require
T°, Humidity, CB health status overvoltage protections T°, Humidity, CB health status overvoltage protections
See page E1 See page E1
B6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B7
www.se.com www.se.com
PE90604
PE90396
DIS BVP 17
SF1 VMX
PE90397
PE90399
PE90605
PE90606
ECOFIT™ solution
B
ECOFIT™
End of
solution B
Commercialization commercialization End of full spare parts availability End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D DIS BVP 17 D
Rated current (Ir) 400 - 1250 A Rated current (Ir) 400 - 1250 A
Short circuit current (Isc) 12.5 kA Short circuit current (Isc) 25 kA
E E
Rated voltage Un (50/60 Hz) 23 kV Rated voltage Un (50/60 Hz) 11 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B9
www.se.com www.se.com
PE90466
PE90762
PE90763
PE90461
CB CS - CX
HVX FPR
PE90462
PE90463
ECOFIT™ solution
B
ECOFIT™
solution B
PE90467
PE90468
End of
Commercialization commercialization End of full spare parts availability End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D CB CS-CX D
Rated current (Ir) 400 - 1250 - 2500 A Rated current (Ir) 400 - 1250 A
Short circuit current (Isc) 12.5 - 16/25 - 40 kA Short circuit current (Isc) 14.5 kA
E E
Rated voltage Un (50/60 Hz) Up to 23 kV Rated voltage Un (50/60 Hz) 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Oil, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B11
www.se.com www.se.com
PE90671
FP-GFA FP
PE90667
PE90672
PE90673
End of End of
Commercialization commercialization End of full spare parts availability Commercialization commercialization End of full spare parts availability
PE90668
PE90669
C C
Main technical characteristics Main technical characteristics
D FP-GFA FP D
Rated current (Ir) 400 - 2000 A Rated current (Ir) 400 - 2000 A
Short circuit current (Isc) 40 kA Short circuit current (Isc) 40 kA
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 12 kV
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B13
www.se.com www.se.com
PE90679
PE90678
FP FP
HVX HVX
B
ECOFIT™ solution ECOFIT™ solution
B
PE90672
PE90673
PE90680
PE90673
End of End of
Commercialization commercialization End of full spare parts availability Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D FP FP D
Rated current (Ir) 630 - 2000 A Rated current (Ir) 400 - 2000 A
Short circuit current (Isc) 40 kA Short circuit current (Isc) 31.5 kA
E E
Rated voltage Un (50/60 Hz) 17.5 kV Rated voltage Un (50/60 Hz) 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B14 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B15
www.se.com www.se.com
PE90577
PE90579
FP DHF & F
HVX-O² LF1 - LF2 - LF3 - SF1
B
ECOFIT™ solution ECOFIT™
B
PE90675
PE90676
solution
End of full spare
Commercialization End of commercialization parts availability End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D FP DHF & F DHF & F DHF & F DHF & F DHF & F DHF & F DHF & F DHF & F D
6DHF 7F/N 10DHF 7F 15DHF 12F 24DHF 20DHF
Rated current (Ir) 400 - 2000 A 6DHF/N 250-350 250-750 350-750 350-850 12F/N 350-500 350-750
Short circuit current (Isc) 31.5 kA 250-500 350-750 24F
500-750
E E
Rated voltage Un (50/60 Hz) 36 kV Rated current (Ir) 630 - 3150 A 630 - 3150 A 630 - 3150 A 630 - 3150 A 630 - 1250 A 630 - 3150 A 630 - 3150 A 630 - 1250 A
20 - 48 kA 29 - 34 kA 12 - 43 kA 18 - 48 kA 13.5 - 32.5 kA 12.5 - 48 kA 9.2 - 14.5 kA 8 - 18 kA /20DHF
HVX-O² HVX-O² Short circuit current (Isc)
12.5 - 18 kA /24F
Technology Vacuum Switching sequence O-0.3 s-CO-3 min-CO Rated voltage Un (50/60 Hz) 6 kV 7.2 kV 10 kV 12 kV 15 kV 17 kV 20 kV 24 kV
O-3 min-CO-3 min-CO
Rated voltage Ur (kV) 40.5
F F
O-0.3 s-CO-15s-CO
CO-15 s-CO LF1 LF2 LF3* SF1 LF1 LF2 LF3* SF1
Surge withstand voltage Up (kV) 185 Closing time (ms) 45 - 53 Technology SF6 SF6 SF6 SF6 Switching sequence O-3 min-CO-3 min-CO
Rated voltage Ur (kV) 7.2 7.2 - 12 17.5 24 O-0.3 s-CO-3 min-CO
Nominal frequency (Hz) 50 - 60 Opening time (ms) 45 - 63 O-0.3 s-CO-15 s-CO
Rated current Ir (A) Up to 2500 Number of switching 10 000 Surge withstand voltage Up (kV) 60 60 - 75 95 125 Closing time (ms) < 72 < 72 < 72 < 65
G Short circuit current Isc (kA) 31.5
operations Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 50 - 60 Opening time (ms) < 54 < 54 < 54 < 50 G
Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40 Rated current Ir (A) 630 - 1250 2000 / up 630 - 3150 630 - 1250 Number of switching 10 000 10 000 10 000 10 000
to 2000 operations
Short circuit current Isc (kA) 31.5 40 - 50 40 25
H H
Short circuit duration Tk (s) 3 3 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 - 25 / + 40
* Ur: 7.2 / 12 kV, A: 3150, kA: 50
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B16 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B17
www.se.com www.se.com
PE90742
PE90744
PE90409
PE90411
FG1-FG2 FG3
Easypact EXE - Evolis - LF2 - LF3 SF1-SF2 or HVX-O²
B
ECOFIT™ ECOFIT™
solution solution B
End of full spare End of full spare
Commercialization End of commercialization parts availability Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D FG1 - FG2 FG3 D
Rated current (Ir) 630 - 3150 A 630 - 3150 A 630 - 3150 A Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 25 - 50 kA 25 - 50 kA 25 - 31.5 kA Short circuit current (Isc) 25 - 31.5k A
E E
Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV Rated voltage Un (50/60 Hz) 24 kV
Evolis & LF2 LF3 Evolis & LF2 LF3 SF1 SF2 HVX-O² SF1 SF2 HVX-O²
Easypact EXE Easypact EXE
Technology SF6 SF6 Vacuum Switching sequence O-0.3 s-CO-3 min-CO
Technology Vacuum SF6 SF6 Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO Rated voltage Ur (kV) 24 24 24
F F
O-0.3 s-CO-15s-CO
Rated voltage Ur (kV) Up to 17.5 7.2 - 12 17.5 O-0.3 s-CO-15 s-CO CO-15 s-CO
Surge withstand voltage Up (kV) Up to 95 60 - 75 95 Closing time (ms) < 65 < 72 < 72 Surge withstand voltage Up (kV) 125 125 125 Closing time (ms) < 65 < 65 45 - 63
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) < 50 < 54 < 54 Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) < 50 < 50 25 - 53
Rated current Ir (A) 630 - 2500 630 - 2000 630 - 3150 Number of switching 2000 10 000 10 000 Rated current Ir (A) 630 - 1250 1250 - 2500 Up to 1250 Number of switching 10 000 10 000 10 000
G Short circuit current Isc (kA) 40 (Evolis)
31.5
25 - 50 31.5-40
operations (Isc = 40 kA /
M1 class) - Short circuit current Isc (kA) 25 25 - 31.5 Up to 25
operations electrical
G
10 000 Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 5 / + 40
(Easypact EXE)
Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
with LF circuit breaker Vacuum solutions may require Vacuum solutions may require
T°, Humidity, CB health status overvoltage protections overvoltage protections
See page E1
B18 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B19
www.se.com www.se.com
PE90416
PE90417
PE90450
FC4 FG4
SF2 SF1 - SF2
B B
ECOFIT™ ECOFIT™
solution solution
C C
Main technical characteristics Main technical characteristics
D FC4 FG4 D
Rated current (Ir) 1250 - 2500 A Rated current (Ir) 1250 - 2500 A 1250 - 2500 A
Short circuit current (Isc) 31.5 - 40 kA Short circuit current (Isc) 40 kA 25 - 40 kA
E E
Rated voltage Un (50/60 Hz) 36 kV Rated voltage Un (50/60 Hz) 24 kV 36 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J J
K K
B20 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B21
www.se.com www.se.com
PE90652
PE91043
PE91006
HP - W - TW - TM K104
HVX - VA Evolis / LF
ECOFIT™ solution
B
ECOFIT™
solution
End of commercialization
B
End of full spare Commercialization End of full spare parts availability
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D HP - W - TW - TM K104 D
Rated current (Ir) 600 - 800 - 1250 - 2500 - 3150 A Rated current (Ir) 630 - 1000 - 1600 A
Short circuit current (Isc) 8.4 - 12.5 - 21.7 - 31.5 - 40 kA Short circuit current (Isc) 25 -31.5 kA
E E
Rated voltage Un (50/60 Hz) 7.2 - 12 - 24 kV Rated voltage Un (50/60 Hz) 6 - 10 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Oil, raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B22 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B23
www.se.com www.se.com
PE91007
PE91008
PE91028
PE91028
C C
Main technical characteristics Main technical characteristics
D KAD KRU 2-10 D
Rated current (Ir) 800 A Rated current (Ir) 630 - 1000 - 1600 A
Short circuit current (Isc) 25 kA Short circuit current (Isc) 25 -31.5 kA
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 6 - 10 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B24 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B25
www.se.com www.se.com
PE90390
DST2 & 5 - DST2 C - CD
DST2V & 5V CTV1 - R400 - R400D
ECOFIT™
B
ECOFIT™
B
PE90618
PE90619
solution solution
PE90391
PE90392
End of full spare End of full spare
Commercialization End of commercialization parts availability Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D DST2 & 5 DST2 C-CD D
Rated current (Ir) 1200 - 3000 A 1200 - 3000 A Rated current (Ir) 80 - 200 A
Short circuit current (Isc) 250 - 350 MVA 500 - 750 MVA Short circuit current (Isc) 50 kA (with fuses)
E E
Rated voltage Un (50/60 Hz) 5 kV 15 kV Rated voltage Un (50/60 Hz) 7.2 kV
DST2V DST5V DST2V DST5V CTV1 R400 R400D CTV1 R400 R400D
Technology Vacuum Vacuum Rated current Ir (A) 1200 - 3000 1200 - 3000 Technology Vacuum SF6 SF6 Switching sequence
Rated voltage Ur (kV) 5 15 3-phase rating (MVA) 350 500 - 750 Rated voltage Ur (kV) 7.2 7.2 7.2
F Surge withstand voltage Up (kV) 60 95 Surge withstand voltage Up (kV) 60 60 60 Closing time (ms) 60 - 80 75 - 155 75 - 155 F
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 20 - 30 20 - 50 20 - 50
Rated current Ir (A) 80 - 250 80 - 250 80 - 250 Number of switching 200 000 300 000 100 000
operations
Make the most of your equipment with available add-ons Short circuit current Isc (kA) 50 50 50
G (with fuses) (with fuses) (with fuses) G
Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Short circuit duration Tk (s) 3 3 3 Service temperature (°C) -2 5 / + 40 - 25 / + 40 - 25 / + 40
Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1
See page F1
H H
TECHNOLOGY Vacuum vs SF6, Oil, Air
Vacuum solutions may require
overvoltage protections
Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Additional offer Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1
Magnum circuit breakers correctly interface with the Optional capabilities
PE90619
See page F1
existing breaker compartment components and maintain • Increased fault current interruption rating.
B26 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B27
www.se.com www.se.com
PE90481
C1 - CD1 HL
PE90393
PE90395
PE90482
PE90483
B
ECOFIT™
B
ECOFIT™ solution
solution
C C
Main technical characteristics Main technical characteristics
D C1-CD1 HL D
Rated current (Ir) 80 - 250 A Rated current (Ir) 630 - 1250 A
Short circuit current (Isc) 50 kA (with fuses) Short circuit current (Isc) 25 & 40 kA
E E
Rated voltage Un (50/60 Hz) 7.2 kV Rated voltage Un (50/60 Hz) 17.5 kV
CTV1 R400 R400D CTV1 R400 R400D HVX FPX HVX FPX
Technology Vacuum SF6 SF6 Switching sequence Technology Vacuum SF6 Switching sequence O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 7.2 7.2 7.2 Rated voltage Ur (kV) 17.5 17.5 O-15 s-CO O-0.3 s-CO-15 s-CO
F Surge withstand voltage Up (kV) 60 60 60 Closing time (ms) 60 - 80 75 - 155 75 - 155
Surge withstand voltage Up (kV) 95 95 Closing time (ms)
O-0.3 s-CO-15 s-CO
35 - 53 50
F
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 20 - 30 20 - 50 20 - 50
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) 45 - 63 50
Rated current Ir (A) 80 - 250 80 - 250 80 - 250 Number of switching 200 000 300 000 100 000
operations Rated current Ir (A) 630 - 1250 630 - 1250 Number of switching 10 000 10 000
Short circuit current Isc (kA) 50 50 50
G (with fuses) (with fuses) (with fuses) Short circuit current Isc (kA) 16 - 40 12.5 - 40
operations
G
Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40 Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B28 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B29
www.se.com www.se.com
PE91009
PE91010
M - MC - IMC - E RSW
PE90554
FAL - IFAL Evolis - LF
ECOFIT™ solution
B B
BAL - ALF - AL
PE90555
PE90556
TG End of commercialization
End of com- VA - VAA-Contactor Commercialization End of full spare parts availability
mercialization
IMC -MC ECOFIT™ solution
C Commercialization
End of
commercialization
End of full spare parts
availability
C
Main technical characteristics Main technical characteristics
D M - MC - IMC - E - AL - ALF - BAL - FAL - IFAL - TG RSW D
Rated current (Ir) 1250 - 4000 A Rated current (Ir) 630 - 1250 A
Short circuit current (Isc) 16 - 50 kA Short circuit current (Isc) 25 -31.5 kA
E E
Rated voltage Un (50/60 Hz) 12 - 36 kV Rated voltage Un (50/60 Hz) 6 - 10 kV
Rated current Ir (A) 630 - 3550 Number of switching 10 000 Rated current Ir (A) 630 - 1250 630 - 1250 Number of switching 20 000 10 000
operations operations
Short circuit current Isc (kA) 25 - 31.5 25 - 31.5
G G
Short circuit current Isc (kA) 16 - 50
Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40 Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
Remote racking See page F1
See page F1
J TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
Vacuum solutions may require Vacuum solutions may require
overvoltage protections overvoltage protections
K K
B30 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B31
www.se.com www.se.com
PE90582
PE90539
MAG II DSE
LF1 - LF2 MAGNUM CB
B
ECOFIT™ solution
B
ECOFIT™
PE90540
PE90541
solution
PE90581
C C
Main technical characteristics Main technical characteristics
D MAG II - 6 - 250/400 MAG II - 10 - 500 MAG II - 15 - 6 - 300/350 DSE D
Rated current (Ir) 630 - 1250 - 2000 A 630 - 1250 - 2000 A 630 - 1250 - 2000 A Rated current (Ir) 1200 - 3000 A 1200 - 3000 A
Short circuit current (Isc) 20 - 48 kA 20 - 28 kA 12 - 30 kA Short circuit current (Isc) 250 MVA 250 - 1000 MVA
E E
Rated voltage Un (50/60 Hz) 6 kV 10 kV 15 kV Rated voltage Un (50/60 Hz) 5 kV 15 kV
Nominal frequency (Hz) 50 - 60 50 - 60 Opening time (ms) < 54 < 54
Rated current Ir (A) 630 - 1250 2000 Number of switching 10 000 10 000
operations
G Short circuit current Isc (kA)
Short circuit duration Tk (s)
31.5
3
40
3 Service temperature (°C) - 25 / + 40 - 25 / + 40
G
* For Siclad panels 630 mm & 850 mm wide
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B32 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B33
www.se.com www.se.com
PE90421
GI-GL FB4
LF1-LF3 SF1
PE90422
PE90423
PE90583
PE90585
ECOFIT™ solution
B
ECOFIT™
solution B
End of full spare
Commercialization End of commercialization parts availability End of
Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D GI GL FB4 D
Rated current (Ir) 630 - 1250 A 630 - 1250 A 1600 - 3150 A 1600 - 3150 A 1600 - 3150 A 1600 - 3150 A Rated current (Ir) 400 - 1250 A 400 - 1250 A 400 - 1250 A 400 - 1250 A
Short circuit current (Isc) 12.5 - 31.5 kA 12 - 25 kA 50 kA 20 - 40 kA 20 - 40 kA 20 - 31.5 kA Short circuit current (Isc) 12.5 - 31.5 kA 12.5 - 25 kA 12.5 - 20 kA 12.5 - 20 kA
E E
Rated voltage Un (50/60 Hz) 7 - 12 kV 17 - 24 - 36 kV 7 kV 12 kV 24 kV 36 kV Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Oil, raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
B34 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B35
www.se.com www.se.com
PE90659
ECA - BAL - AL BAL - AL
VA - VAA - Contactor ECA
VA - VAA - Contactor
PE90664
PE90663
B B
ECOFIT™ solution
PE90665
PE90666
ECOFIT™
End of full spare solution
Commercialization parts availability
End of
Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D BAL - AL ECA BAL - AL ECA D
Rated current (Ir) 250 A 630 - 2500 A Rated current (Ir) 250 - 630 A 630 - 2500 A
Short circuit current (Isc) 20 kA 20 - 50 kA Short circuit current (Isc) 20 kA 20 - 50 kA
E E
Rated voltage Un (50/60 Hz) 3.6 - 12 kV 12 - 24 kV Rated voltage Un (50/60 Hz) 3.6 - 12 kV 12 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Oil, raw material recovery Easergy Px, Sepam, MiCom, Oil, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
Remote racking Remote racking
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air
J
with LF circuit breaker Vacuum solutions may require with LF circuit breaker Vacuum solutions may require
T°, Humidity, CB health status overvoltage protections T°, Humidity, CB health status overvoltage protections
See page E1 See page E1
B36 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B37
www.se.com www.se.com
PE90661
HVX-C
MC
VA - VAA
AL - BAL - TG
ECOFIT™ solution
PE90661
PE90650
B B
TG
End of full spare VA - VAA - Contactor - LTRI
PE90663
PE90821
C C
Main technical characteristics Main technical characteristics
D HVX-C MC - AL - BAL - TG D
Rated current (Ir) 630 - 2500 A Rated current (Ir) 630 - 3150 A
Short circuit current (Isc) 25 - 31.5 kA Short circuit current (Isc) 31.5 - 50 kA
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) Up to 36 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
Remote racking Remote racking
See page F1 See page F1
B38 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B39
www.se.com www.se.com
Insulated
YSF6 Switchgear legacy - It is particularly adapted for non Schneider Installed Base.
and no legacy
PE57994
YSF6 Evolis cubicles - ECOFIT™ solution with shutters and mechanical interlocks embedded.
with minimum inside
B
ECOFIT™
solution panel width - Only the fixed connections (between the cradle and existing busbar) B
PE90608
PE90609
≥ 560 mm
are customized.
End of full spare
Commercialization End of commercialization parts availability
- No age condition of the existing equipment.
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 7.2 - 12 kV 7.2 - 12 - 17.5 kV
YSF6 Evolis YSF6 Evolis MC1 MC2 MC3 MC1 MC2 MC3
Technology Vacuum Switching sequence O-3 min-CO-3 min-CO Technology Vacuum Vacuum Vacuum Switching sequence O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Rated voltage Ur (kV) 11 Rated voltage Ur (kV) 7.2 - 12 7.2 - 12 - 17.5 7.2 - 12 - 17.5
F F
O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75 - (95 for Australia) Closing time (ms) < 50 Surge withstand voltage Up (kV) 60 - 75 60 - 75 - 95 60 - 75 - 95 Closing time (ms) < 65 < 65 < 65
Nominal frequency (Hz) 50 - 60 Opening time (ms) < 65 Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) < 50 < 50 < 50
Rated current Ir (A) 630 - 1250 Number of switching 10 000 Rated current Ir (A) 630 - 1250 630 - 1250 630 - 2500 Number of switching 2.000 (for Isc= 40 kA class M1) - 10 000
operations operations
G Short circuit current Isc (kA)
Short circuit duration Tk (s)
25
3 Service temperature (°C) - 25 / + 40
Short circuit current Isc (kA)
Short circuit duration Tk (s)
Up to 31.5
3
Up to 40
3
Up to 40
1 Service temperature (°C) - 25 / + 40 - 25 / + 40 - 25 / + 40
G
240 240 550
DE57194EN
Cassette MC1 MC2 MC3
285
Phase to phase (mm) E 145 185 240
H H
Dimensions (mm) W 556 686 886 H
370
805 H 980 980 980
D 1223 1223 1223
Make the most of your equipment with available add-ons 300
I I
Weight (kg) 222 255 326
321 611 100
W D
Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1
See page F1
Make the most of your equipment with available add-ons
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
J
with LF circuit breaker Vacuum solutions may require Easergy Px, Sepam, MiCom, SF6, raw material recovery
T°, Humidity, CB health status overvoltage protections Arc Flash See page I1
See page E1 See page F1
B40 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B41
www.se.com www.se.com
PE90466
PE90762
PE90763
Switchgear legacy - It is particularly adapted for non Schneider Installed Base.
DE57396
FPR
and no legacy
cubicles FPR
- ECOFIT™ solution with shutters and mechanical interlocks embedded.
with minimum inside
B
ECOFIT™ solution
panel width -O
nly the fixed connections (between the cradle and existing busbar) B
PE90467
PE90468
≥ 1105 mm End of full spare
are customized.
Commercialization End of commercialization parts availability
- No age condition of the existing equipment.
E E
F400-SF F400 cassette MC1 MC2 Rated voltage Un (50/60 Hz) 24 kV
Technology SF6 SF6 Switching sequence O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO FPR FPR
Rated voltage Ur (kV) 24 - 36 40.5 O-0.3 s-CO-15 s-CO
Technology SF6 Switching sequence O-3 min-CO-3 min-CO
Surge withstand voltage Up (kV) 125 - 170 185 Closing time (ms) < 65 < 65 O-0.3 s-CO-15 s-CO
Rated voltage Ur (kV) 24
F Nominal frequency (Hz)
Rated current Ir (A)
50 - 60
1250 - 2500
50 - 60
630 - 1250
Opening time (ms)
Number of switching
< 50
10 000
< 50
10 000
Surge withstand voltage Up (kV) 125 Closing time (ms) 50 F
operations Nominal frequency (Hz) 50 - 60 Opening time (ms) 80
Short circuit current Isc (kA) 25 - 40 31.5
Rated current Ir (A) 400 - 1250 Number of switching 10 000
Short circuit duration Tk (s) 3 3 Service temperature (°C) - 25 / + 40 - 25 / + 40 operations
G G
Short circuit current Isc (kA) 12.5
PE57431
Cassette 1250 A 2500 A - 3000 A Short circuit duration Tk (s) 1 Service temperature (°C) - 25 / + 40
H Weight (kg)
C 2030
750
2030
850
H
Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1
See page F1
Make the most of your equipment with available add-ons
J Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
J
Easergy Px, Sepam, MiCom SF6, raw material recovery
Arc Flash See page I1
See page F1
K K
TECHNOLOGY Vacuum vs SF6, Oil, Air
Vacuum solutions may require
overvoltage protections
B42 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B43
www.se.com www.se.com
PE90413
PE90597
R400 - R400D HMC400 - HMC410
R400 - R400D HMC400 - HMC410
B
ECOFIT™ solution ECOFIT™
B
PE90595
PE90594
solution
Commercialization End of full spare parts availability
End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics
D HMC400 - HMC410 D
Rated current (Ir) 400 A 400 A
Short circuit current (Isc) 43.8 kA 26.3 kA
E E
Rated voltage Un (50/60 Hz) 3.3 kV 6.6 kV
Refurbishment
In-house refurbishment, including vacuum contactors and control scheme, using Gemstart unit, on-site maintenance.
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B44 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B45
www.se.com www.se.com
PE90600
HMC1072 HMC1172
HMC1072 HMC1172
B
ECOFIT™ ECOFIT™
solution solution B
End of full spare End of full spare
Commercialization End of commercialization parts availability Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D HMC1072 HMC1172 D
Rated current (Ir) 400 A Rated current (Ir) 400 A
Short circuit current (Isc) 63 kA rms / 1 s - 50 kA rms / 3 s Short circuit current (Isc) 63 kA rms / 1 s - 50 kA rms / 3 s
E E
Rated voltage Un (50/60 Hz) 7.2 kV Rated voltage Un (50/60 Hz) 7.2 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air
J
T°, Humidity, CB health status Vacuum solutions may require T°, Humidity, CB health status Vacuum solutions may require
See page E1 overvoltage protections See page E1 overvoltage protections
B46 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B47
www.se.com www.se.com
PE91027
PE90765
HWX FPX
HWX FPX
ECOFIT™
B
ECOFIT™ solution
PE90857
PE90766
End of full spare
Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D HWX FPX D
Rated current (Ir) 3150 A Rated current (Ir) Up to 3150 A Up to 2500 A
Short circuit current (Isc) 50 kA Short circuit current (Isc) 40 kA 31.5 kA/3s
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 12 kV 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
B48 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B49
www.se.com www.se.com
PE90554
FPX VA - VAA
FPX VA - VAA
PE90857
PE90857
PE90555
ECOFIT™ solution
PE90556
B
ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D FPX VA - VAA D
Rated current (Ir) Up to 3150 A Up to 2500 A Up to 2500 A Rated current (Ir) 1250 - 4000 A
Short circuit current (Isc) 40 kA 31.5 kA 31.5 kA Short circuit current (Isc) 16 - 50 kA
E E
Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV Rated voltage Un (50/60 Hz) 12 - 36 kV
Nominal frequency (Hz) 50 - 60 50 - 60 50 - 60 Opening time (ms) 50 Nominal frequency (Hz) 50 - 60 Opening time (ms) 20 - 50
Rated current Ir (A) Up to 3150 Up to 2500 Up to 2500 Number of switching 10 000 Rated current Ir (A) 630 - 3550 Number of switching 10 000
operations operations
G G
Short circuit current Isc (kA) Up to 40 Up to 31.5 Up to 31.5 Short circuit current Isc (kA) 16 - 50
Short circuit duration Tk (s) 3 3 3 Service temperature (°C) - 5 / + 40 Short circuit duration Tk (s) 3 Service temperature (°C) - 5 / + 40
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B50 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B51
www.se.com www.se.com
PE90692
BLV VMX
PE90219
BLV VMX
ECOFIT™ solution ECOFIT™ solution
B B
PE90865
PE90865
PE90764
PE90764
Commercialization End of commercialization parts availability Commercialization End of commercialization parts availability
C C
Main technical characteristics Main technical characteristics
D BLV VMX D
Rated current (Ir) 400 - 1250 A 400 - 1250 A 400 - 1250 A 400 - 1250 A Rated current (Ir) 630 - 2000 A
Short circuit current (Isc) 16 - 40 kA 16 - 40 kA 16 - 40 kA 16 - 31.5 kA Short circuit current (Isc) Up to 25 kA / 3 s
E E
Rated voltage Un (50/60 Hz) 7.2 kV 12 kV 17.5 kV 24 kV Rated voltage Un (50/60 Hz) 11 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J J
K K
B52 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B53
www.se.com www.se.com
PE90659
PE90657
VA - VAA VA - VAA
VA - VAA VA - VAA
PE90664
PE90663
B
ECOFIT™ solution ECOFIT™ solution
B
PE90665
PE90666
C C
Main technical characteristics Main technical characteristics
D VA VAA VA VAA D
Rated current (Ir) 630 - 2500 A 630 - 1250 A Rated current (Ir) 630 - 2500 A 630 - 1250 A
Short circuit current (Isc) 20 - 50 kA 16 - 25 kA Short circuit current (Isc) 20 - 50 kA 16 - 25 kA
E E
Rated voltage Un (50/60 Hz) 12 - 24 kV 12 - 24 kV Rated voltage Un (50/60 Hz) 12 kV 12 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J J
K K
B54 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B55
www.se.com www.se.com
PE90661
VA - VAA VA - VAA
VA - VAA VA - VAA
PE90661
PE90650
B
ECOFIT™ solution ECOFIT™ solution
PE90821
C C
Main technical characteristics Main technical characteristics
D VA - VAA VA - VAA D
Rated current (Ir) 630 - 2500 A Rated current (Ir) 630 - 2500 A
Short circuit current (Isc) 25 - 31.5 kA Short circuit current (Isc) 31.5 - 50 kA
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) Up to 36 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J J
K K
B56 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B57
www.se.com www.se.com
ECOFIT™ proposal for panel extension or replacement ECOFIT™ proposal for panel extension or replacement
AHA With ECOFIT™, a true extended life time DNF7 With ECOFIT™, a true extended life time
PE90748
AHA DNF7
AHA DNF7
B
ECOFIT™ solution ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D AHA DNF7 D
Rated current (Ir) Up to 4000 A Rated current (Ir) 400 - 2000 A
Short circuit current (Isc) Up to 40 kA Short circuit current (Isc) 31.5 kA
E E
Rated voltage Un (50/60 Hz) 12 kV Rated voltage Un (50/60 Hz) 36 kV
Overall dimensions (w x h x d) 700 x 2330 x 1450 Ingress Protection degree (IP) Enclosure IP42 - Compartment IP2X Overall dimensions (w x h x d) 1300 x 2250* x 2300** Ingress Protection degree (IP) Enclosure IP3X
(mm) 900 x 2330 x 1450 (mm)
G * 2900 mm with busbar compartment - ** 2500 mm with internal arc withstand, 2750 mm with cables voltage compartment - *** With forced cooling (on request) G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash, Remote racking See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B58 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B59
www.se.com www.se.com
ECOFIT™ proposal for panel extension or replacement ECOFIT™ proposal for panel extension or replacement
F100 - 200 With ECOFIT™, a true extended life time PX12-24 With ECOFIT™, a true extended life time
PE90677
PE90409
F100 - 200 PX12-24
F100 - 200 PX12-24
B B
ECOFIT™ solution ECOFIT™ solution
Commercialization End of commercialization Commercialization End of commercialization
C C
Main technical characteristics Main technical characteristics
D F100 F200 PX12 PX24 D
Rated current (Ir) 630 - 3150 A 630 - 3150 A Rated current (Ir) 400 - 3150 A 400 - 2500 A
Short circuit current (Isc) 25 - 50 kA 25 - 50 kA Short circuit current (Isc) 25 - 40 kA 16 - 25 - 31.5 kA
E E
Rated voltage Un (50/60 Hz) 7.2 kV 12 - 17.5 kV Rated voltage Un (50/60 Hz) 12 kV 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, Raw material recovery Easergy Px, Sepam, MiCom, SF6, raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
with LF circuit breaker Vacuum solutions may require Vacuum solutions may require
T°, Humidity, CB health status overvoltage protections overvoltage protections
See page E1
B60 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B61
www.se.com www.se.com
PE90219
PE90217
PIX - SF6 VISAX
PIX - SF6 VISAX
B
ECOFIT™ solution ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D PIX - SF6 VISAX D
Rated current (Ir) Up to 3150 A Up to 2500 A Up to 2500 A Rated current (Ir) Up to 2500 A Up to 2500 A Up to 2500 A
Short circuit current (Isc) 40 kA / 3 s 31.5 kA / 3 s 31.5 kA / 3 s Short circuit current (Isc) 25 kA / 3 s 25 kA / 3 s 25 kA / 3 s
E E
Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV Rated voltage Un (50/60 Hz) 12 kV 17.5 kV 24 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash See page I1
See page F1 See page F1
K K
B62 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B63
www.se.com www.se.com
ECOFIT™ proposal for panel extension or replacement ECOFIT™ proposal for panel extension or replacement
VMX With ECOFIT™, a true extended life time WBA With ECOFIT™, a true extended life time
PE90657
PE90692
VMX WBA
VMX WBA
B
ECOFIT™ solution
B
ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D VMX WBA D
Rated current (Ir) 630 - 2000 A Rated current (Ir) 630 - 2500 A 630 - 2500 A
Short circuit current (Isc) Up to 25 kA / 3 s Short circuit current (Isc) 16 - 25 kA & 20 - 50 kA 20 - 50 kA
E E
Rated voltage Un (50/60 Hz) 11 kV Rated voltage Un (50/60 Hz) 12 - 24 kV 12 - 38 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, SF6, raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash See page I1 Arc Flash, Remote racking See page I1
See page F1 See page F1
B64 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B65
www.se.com www.se.com
ECOFIT™ proposal for panel extension or replacement ECOFIT™ proposal for panel extension or replacement
WBB With ECOFIT™, a true extended life time WBD With ECOFIT™, a true extended life time
PE90820
WBB WBD
WBB WBD
ECOFIT™ solution
B B
ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D WBB WBD D
Rated current (Ir) 630 - 2500 A Rated current (Ir) 630 - 3150 A
Short circuit current (Isc) 20 - 50 kA Short circuit current (Isc) 80 kA
E E
Rated voltage Un (50/60 Hz) 12 - 24 kV Rated voltage Un (50/60 Hz) 12 kV
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash, Remote racking See page I1 Arc Flash, Remote racking See page I1
See page F1 See page F1
J Asset Connect MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air TECHNOLOGY Vacuum vs SF6, Oil, Air
J
T°, Humidity, CB health status Vacuum solutions may require Vacuum solutions may require
See page E1 overvoltage protections overvoltage protections
B66 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B67
www.se.com www.se.com
WK
WK
B B
ECOFIT™ solution
C C
Main technical characteristics
D WK D
Rated current (Ir) 630 - 3150 A
Short circuit current (Isc) 20 - 50 kA / 3 s
E E
Rated voltage Un (50/60 Hz) 12 - 24 - 38 kV
WK WK
Rated insulation level (kV) 12 - 36 Rated current of busbar (A) 630 - 4000
Rated power frequency 28 - 38 Rated short time withstand 63 - 80
F withstand voltage/1 mn (kVrms)
Lightning impulse withstand 110
current (4 s) (kA)
Internal Arc Classification (1 s) PEHLA 31.5 kA
F
voltage (peak value) (kVp) (AFLR)
Overall dimensions (w x h x d) 600/1060 x 2330 x 1700/2100 Ingress Protection degree (IP) Standard IP2X
(mm) On request IP3X, IP4X
G G
H H
Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY SF6 Recovery Services
I
Easergy Px, Sepam, MiCom, Raw material recovery
Arc Flash, Remote racking See page I1
See page F1
J Asset Connect (only WKC) MONITORING TECHNOLOGY Vacuum vs SF6, Oil, Air
J
T°, Humidity, CB health status Vacuum solutions may require
See page E1 overvoltage protections
B68 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B69
www.se.com www.se.com
Brand Type
D: (arm length) E: F:
B Range Type of new CB
B
Rated Current (A) Rated Voltage (kV)
E E
Phase to phase distance for MCset Diagram Number (optional)
YES v
V Downtime in RC&S granted by our customer
(in days)
G Mechanical Interlocking G
NO v
V On-site downtime granted by our customer
(in days)
Comments / Message
Asset Connect
H
Temperature v
I To request for a quote, please use the ECOFIT™ web selector: se.com/ecofitselector
Humidity v I
Arc Flash v
Circuit breaker health status (requires digital protection relay) v
J Protection J
Relay modernization v
Remote racking v
K Sustainability
K
SF6 recover v
B70 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 B71
Low Voltage distribution
www.se.com www.se.com
C
DS-206, DS-206H, DS-206E Series............... C11
DS-416, DS-416S, DS-416H Series................ C13
DS-420 Series................................................ C15
H Series......................................................... C17
K-225, K-600, K-800 Series........................... C18
K-1600 Series................................................ C19
KDON-600, KDON-800, KDON-1600 Series.... C20
KDON-1600 Series........................................ C21
LA-600, LA-800 Series................................... C22
LA-1600 Series.............................................. C23
LAF-600, LAF-800 Series............................... C24
MasterPact M08 - M63................................... C25
SE.................................................................. C26
Selpact.......................................................... C27
MasterPact NT-NW......................................... C28
LV Circuit Breaker:
Source-changeover systems......................... C30
LV Circuit Breaker:
Measurements - Diagnostics & Maintenance -
Protections - Communication......................... C30
LV Circuit Breaker: Smartpanel integration,
architecture and systems............................... C30
LV Drawer
T140............................................................... C31
MB400........................................................... C32
LV Drawers - Associated offers...................... C33
Order forms
ComPact Plug and Play................................. C34
ComPactkit.................................................... C35
Masterpact M Plug and Play.......................... C36
Masterkit........................................................ C37
B72 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C1
www.se.com www.se.com
US17012
US17013
US17014
MasterPact MTZ1 MasterPact MTZ1
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D AK - (1 - 2 - 3 - 4 - 5) - 15/25 Series MasterPact MTZ1 AK - (1A - 2A - 3A - 4A - 5A) - 15/25 Series MasterPact MTZ1 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 800 A 800 A Rated current (A) In 40°C 800 A 800 A
Ultimate breaking capacity 42 - 30 - 22 kA 42 kA Ultimate breaking capacity 42 - 30 - 22 kA 42 kA
E (kA rms, 220/415 V AC 50/60 Hz) Icu (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu
E
AK Series direct replacement solution AK Series direct replacement solution
US17012
US17014
F The direct replacement AK Series solutions draw-out types enable to benefit from all the enhanced The direct replacement AK Series solutions draw-out types enable to benefit from all the enhanced F
features of MasterPact MTZ circuit breakers and accessories. features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C3
www.se.com www.se.com
US17016
US17017-3
US17018
MasterPact MTZ2 MasterPact MTZ1
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D AK - (1 - 2 - 3 - 4 - 5) - 50 Series MasterPact MTZ2 AKR-30 Series MasterPact MTZ1 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 1 600 A 1 600 A Rated current (A) In 40°C 800 A 800 A
Ultimate breaking capacity 65 - 50 - 42 kA 65 kA Ultimate breaking capacity 42 - 30 - 30 kA 42 kA
E (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu
E
AK Series direct replacement solution AKR Series direct replacement solution
US17016
US17018
F The direct replacement AK Series solutions draw-out types enable to benefit from all the enhanced The direct replacement AKR Series solutions draw-out types enable to benefit from all the enhanced F
features of MasterPact MTZ circuit breakers and accessories. features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C5
www.se.com www.se.com
US17018
US17021
US17018
MasterPact MTZ2 MasterPact MTZ2
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D AKR-50 Series MasterPact MTZ2 AKRT-50 Series MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 1 600 A 1 600 A Rated current (A) In 40° C 2 000 A 2 000 A
Ultimate breaking capacity 65 - 50 - 42 kA 65 kA Ultimate breaking capacity 65 - 65 - 50 kA 65 kA
E (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu
E
AKR Series direct replacement solution AKRT Series direct replacement solution
US17018
US17018
F The direct replacement AKR Series solutions draw-out types enable to benefit from all the enhanced The direct replacement AKRT Series solutions draw-out types enable to benefit from all the enhanced F
features of MasterPact MTZ circuit breakers and accessories. features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C7
www.se.com www.se.com
PE90430
PE90572
PE90431
PE90573
PE90426
B3-90 / B4-100)
ComPact NS800 - NS1250
MasterPact MTZ1 - MTZ2
B ECOFIT™ solution
ECOFIT™ solution
B
End of
Commercialization commercialization End of full spare parts availability End of
Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics
D B Control (B1-35 / B1-50 / B3-50 / B3-75 /
B3-90 / B4-100)
MasterPact MTZ1 - MTZ2
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40°C
690 V
800 - 1250 A
690 V
800 - 1250 A
D
Ultimate breaking capacity 50 - 150 kA 50 - 150 kA
Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V (kA rms, 220/415 V AC 50/60 Hz) Icu
Rated current (A) In 40°C 800 - 4000 A 800 - 4000 A
DE90252
The ECOFIT™ComPact Plug & Play solution lets you The ECOFIT™ ComPactkit solution enables to benefit
retrofit the latest generation of ComPact NS from all the enhanced features of ComPact NS circuit
B Control ECOFIT™ solution
PE90426
circuit breakers in the existing ComPact C chassis with breakers and accessories. It requires total
F The ECOFIT™ B Control solutions fixed or draw-out types enable to benefit from all the enhanced very short onsite servicing times. shutdown of the installation to access the busbars. F
features of MasterPact MTZ1 or MTZ2 circuit breakers and accessories.
Solution available for withdrawable type only, 3P & 4P, Solution available for fixed type, 3P & 4P,
800 A to 1250 A. 800 A to 1250 A.
1 Removal 2 Replacement
G G
PE90256
PE90257
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C9
www.se.com www.se.com
US17025
PE90424
PE90427
US17024
MasterPact MTZ MasterPact MTZ2
B ECOFIT™
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization End of commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D DA MasterPact MTZ2 - MTZ3 DS Series (DS-206, DS-206H, DS-206E) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 630 - 6300 A 800 - 6300 A Rated current (A) In 40°C 800 A 800 A
Ultimate breaking capacity 42 - 100 kA 42 - 150 kA Ultimate breaking capacity 50 - 42 - 42 kA 65 kA
E (kA rms, 220/415V AC 50/60 Hz) Icu (kA rms, 600 V AC 50/60 Hz) Icu
E
DA ECOFIT™ solution DS Series direct replacement solution
PE90427
US17025
F The ECOFIT™ DA solution enables to benefit from all the enhanced features of MasterPact MTZ The direct replacement DS Series solutions draw-out types enable to benefit from all F
circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
It requires total shutdown of the installation to access the busbars. The kit solution (including
circuit breaker) is available for fixed and withdrawable types, 3P & 4P, 630 to 6300 A.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C11
www.se.com www.se.com
US17025
US17027
US17025
MasterPact MTZ2 MasterPact MTZ2
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D DS Series (DS-206, DS-206H, DS-206E) MasterPact MTZ2 DS Series (DS-416, DS-416S, DS-416H ) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 800 A 800 A Rated current (A) In 40°C 1 600 A 1 600 A
Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 50 - 42 - 42 kA 65 kA Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 65 - 65 - 50 kA 65 kA
E E
DS Series direct replacement solution DS Series direct replacement solution
US17025
US17025
F The direct replacement DS Series solutions draw-out types enable to benefit from all The direct replacement DS Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C13
www.se.com www.se.com
US17025
US17027-2
US17025
MasterPact MTZ2 MasterPact MTZ2
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D DS Series (DS-416, DS-416S, DS-416H) MasterPact MTZ2 DS Series (DS-420) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 1 600 A 1 600 A Rated current (A) In 40°C 2 000 A 2 000 A
Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 65 - 65 - 50 kA 65 kA Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 65 - 65 - 50 kA 65 kA
E E
DS Series direct replacement solution DS Series direct replacement solution
US17025
US17025
F The direct replacement DS Series solutions draw-out types enable to benefit from all The direct replacement DS Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C14 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C15
www.se.com www.se.com
US17025
PE90615
PE90616
MasterPact MTZ2 MasterPact MTZ
B End of commercialization
Direct replacement
solution
ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D DS Series (DS-420) MasterPact MTZ2 H Series MasterPact MTZ1-MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 600 V 600 V
Rated current (A) In 40°C 2 000 A 2 000 A Rated current (A) In 40°C 600 - 4000 A 800 - 6000 A
Ultimate breaking capacity 65 - 65 - 50 kA 65 kA Ultimate breaking capacity 30 - 200* kA 30 - 200* kA
E (kA rms, 240 - 480 - 600 V AC 50/60 Hz) Icu (kA rms, 220/415 V AC 50/60 Hz) Icu
* with fuse
E
DS Series direct replacement solution H Series direct replacement solution
US17025
PE90616
F The direct replacement DS Series solutions draw-out types enable to benefit from all The direct replacement H Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C16 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C17
www.se.com www.se.com
US17008
US17022
US17008
MasterPact MTZ1 MasterPact MTZ2
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D K Series (K-225, K-600, K-800) MasterPact MTZ1 K Series (K-1600) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 V 254 - 508 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 225, 600 - 800 A 225, 600 - 800 A Rated current (A) In 40°C 1 600 A 1 600 A
Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 25 - 42 kA 42 kA Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 65 - 50 - 42 kA 65 kA
E E
K Series direct replacement solution K Series direct replacement solution
US17008
US17008
F The direct replacement K Series solutions draw-out types enable to benefit from all The direct replacement K Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C18 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C19
www.se.com www.se.com
US17010
US17009
US17010
(KDON-600, KDON-800, KDON-1600)
MasterPact MTZ2
MasterPact MTZ1
B Direct replacement
solution End of commercialization
Direct replacement
solution B
End of commercialization End of full spare parts
End of full spare parts Commercialization availability
Commercialization availability
C C
Main technical characteristics Main technical characteristics
D KDON Series
(KDON-600, KDON-800, KDON-1600)
MasterPact MTZ1 KDON Series (KDON-1600) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated current (A) In 40° C 600 - 800, 1 600 A 600 - 800, 1 600 A
Rated current (A) In 40°C 600 - 800, 1 600 A 600 - 800, 1 600 A Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 200 kA* 200 kA*
US17010
F The direct replacement KDON Series solutions draw-out types enable to benefit from all The direct replacement KDON Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C20 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C21
www.se.com www.se.com
US17002
US17005
US17006
MasterPact MTZ1 MasterPact MTZ2
B End of commercialization
Direct replacement
solution
End of commercialization
Direct replacement
solution B
End of full spare parts End of full spare parts
Commercialization availability Commercialization availability
C C
Main technical characteristics Main technical characteristics
D LA Series (LA-600, LA-800) MasterPact MTZ1 LA Series (LA-1600) MasterPact MTZ2 D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V
Rated current (A) In 40°C 600 - 800 A 600 - 800 A Rated current (A) In 40°C 1 600 A 1 600 A
Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 25 - 42 kA 42 kA Ultimate breaking capacity (kA rms, 600 V AC 50/60 Hz) Icu 65 kA 65 kA
E E
LA Series direct replacement solution LA Series direct replacement solution
US17002
US17006
F The direct replacement LA Series solutions draw-out types enable to benefit from all The direct replacement LA Series solutions draw-out types enable to benefit from all F
the enhanced features of MasterPact MTZ circuit breakers and accessories. the enhanced features of MasterPact MTZ circuit breakers and accessories.
G G
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C22 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C23
www.se.com www.se.com
US17002
035928
MasterPact MTZ1 MasterPact MTZ
B End of commercialization
Direct replacement
solution
End of
ECOFIT™ solution
B
End of full spare parts Commercialization commercialization End of full spare parts availability
Commercialization availability
C C
Main technical characteristics Main technical characteristics
D LAF Series (LAF-600, LAF-800) MasterPact MTZ1 MasterPact M08 - M63 MasterPact MTZ D
Rated operational voltage (V AC 50/60 Hz) Ue 254 - 508 - 635 V 254 - 508 - 635 V Rated operational voltage (V AC 50/60 Hz) Ue 690 V 690 V
Rated current (A) In 40° C 600 - 800 A 600 - 800 A Rated current (A) In 40°C 800 - 6300 A 800 - 6300 A
Ultimate breaking capacity 200 kA* 200 kA* Ultimate breaking capacity 40 - 150 kA 42 - 150 kA
F F
PE90452
The direct replacement LAF Series solutions draw-out types enable to benefit from all Plug & Play
the enhanced features of MasterPact MTZ circuit breakers and accessories. The ECOFIT™ MasterPact Plug & Play solution allows you to retrofit the latest
generation of MasterPact MTZ circuit breakers in the existing MasterPact M chassis.
Solution available for withdrawable type only, 3P & 4P, 800 A to 3200 A.
PE90453
PE90454
of MasterPact MTZ circuit breakers and accessories without modifying the busbars.
It requires total shutdown of the installation to access the busbars.
H H
Solution available for fixed and withdrawable types, 3P & 4P, 800 A to 6300 A.
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C24 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C25
www.se.com www.se.com
PE90435
PE90428
PE90426
MasterPact MTZ2 MasterPact MTZ
C C
Main technical characteristics Main technical characteristics
D SE MasterPact MTZ2 Selpact MasterPact MTZ D
Rated operational voltage (V AC 50/60 Hz) Ue 600 V 600 V Rated operational voltage (V AC 50/60 Hz) Ue 660 V 690 V
Rated current (A) In 40°C 1250 - 3000 A 1250 - 3000 A Rated current (A) In 40°C 630 - 3200 A 800 - 3200 A
Ultimate breaking capacity 100 kA 85 kA Ultimate breaking capacity
42 - 100 kA 42 - 150 kA
E (kA rms, 220/415 V AC 50/60 Hz) Icu (kA rms, 220/415 V AC 50/60 Hz) Icu
E
SE direct replacement solution Selpact ECOFIT™ solution
PE90435
PE90426
F The direct replacement SE solutions draw-out types enable to benefit from all The ECOFIT™ Selpact solutions enable to benefit from all the enhanced features of MasterPact MTZ F
the enhanced features of MasterPact MTZ circuit breakers and accessories. circuit breakers and accessories.
G The Plug&Play solution is available for withdrawable type only, 3P & 4P, 630 to 1600 A.
Kit G
The kit solution (including circuit breaker) is available for fixed and withdrawable types, 3P & 4P, 630 to 3200 A.
H H
Make the most of your equipment with available add-ons Make the most of your equipment with available add-ons
I Protection relays PROTECTION SUSTAINABILITY Resources, circular and Protection relays PROTECTION SUSTAINABILITY Resources, circular and
I
Micrologic, Arc flash well-being performances Micrologic, Arc flash well-being performances
See page F1 See page I1 See page F1 See page I1
C26 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C27
www.se.com www.se.com
DB419903
MasterPact NT/NW MasterPact MTZ Fixed and drawout version
Circuit Breaker Circuit Breaker
A + 13
mm
+3
mm
The size of MasterPact MTZ1 is 13 mm deeper than MasterPact NT due to
the bigger size of the new front cover.
A
[1] For MasterPact MTZ2/3 the difference is only 3 mm.
F F Integration of MasterPact MTZ in Prisma, Blokset or Okken cubicles does
MasterPact MTZ1 MasterPact MTZ2 / MTZ3 not require design or parts modifications.
B [1] the size of MasterPact MTZ1 is 13 mm, including spring
charging handle deeper than MasterPact NT due to the bigger
B
size of the new front cover. For MasterPact MTZ2/3
the difference is only 3 mm.
Chassis terminal blocks wiring modification on the chassis terminal blocks. Auxiliary circuits
UC2 /Res
UC1
COM
Ui 1250V
Ue 1150V
Ue
Icw
Icm
ct
Uimp
12kV
690/1000V
50kA/1s
105kA
50/60Hz
peak
wiring on the chassis terminals blocks has to be modified according
to MasterPact MTZ drawout instruction sheet (ref. NVE35470-00) or
CT1 AS
C T2 914 60947-2CEI UNE
924 912 IEC
CT3 4 922 1 911 BS
93 VDE 55°C
OF1 932 1 92 UTE
OF2 14 93 Ie
Ith 4000A
12
OF3 24 11 Ue
22 (A)
D D
OF24 4 23 1 221
24 2 23
24 1
24
H
MC
PF B2
254 2 B3
XF 25 B1
MX1 A2 251
C2 A3
MN/MX2 C3 A1
D2/C12 3 C1
/C1 1
D1/C1
CE1
CE2 314
3 324 2 312 1
CE 4 32 1 31
33 32
SDE184 332
MC2 4 82 331
C3 48 4 81
4 U -V 47 1 et
R es
Test
UC 3 N- 47
E2/Res V 2
- V V1
SD
184/K2
UC2M3/T1 18 2/
(ref. DOCA0101EN-00).
84 33
3 MC2 82 331
UC -VN 484
474 81
C4
es U V3 471
E 2/R -
- V2V1
SD
184/K2
UC2M3/T1 18 2/ /K1
Dimensions and mounting Specific attention of the MasterPact NT/NW chassis condition is required
E =
E
DB419798
=
XF
MN/ MX1
rpact
Maste
DB431651
t
R ese
Test t
R ese
Te st
VPS
F F
Power
Aux
Aux
Power VPS
MTZ1 Kit for retrofitting an NW chassis for MTZ1 moving part: réf. LV850066SP.
OF 1
+ 13
OF2 4 14
12 1
mm
XF 254 B 1 41
MX1 2 A 2 3 2 52 B
=
1 C 3 A 1 251 MN /MX2
SD E84 D2/C-12
/C 13
C A
U C4
U C3 82 11 C1
D1/C
SD E 2/R
es M2C/
2 484
/V3 VN 81
UC 2M3/TT15 184/ K - 474/ V 1 V2
[1]
AF2
Z3 A F1
Z1 Z2
F1 -
F2 +
NT chassis retrofit
= SDE1
MN MX1 XF
MX2
PF MCH
• same fixing points.
G G
MC2
SDE2 UC4
UC3
UC2 /Res
UC1
COM
DB431701
DB419124
DB419122
DB419123
= Masterpac
NW40
t
HA10
Uimp
12kV
Ui 1250V
Ue 1150V 690/1000V
Ue 50kA/1s
peak
Icw 105kA
Icm 50/60Hz
AS NEMA
60947-2CEI UNE
IEC BS
VDE
UTE 55°C
Ie
Ith 4000A Ue
(A)
(V)
4000
1000
AC23A 50/60Hz
60947-3CEI UNE
IEC BS
VDE
UTE
Aux
Power
Tes t
R e s et
VPS
CE1 4
Kit for retrofitting an NW chassis for MTZ2/3 moving part: réf. LV850065SP.
CE2 4 31 2
A
In 1000
31 1
CE3 4 32 2
32 1 31
E1 33 2 32
2 SD 84 33 1
33
MC 4 82
UC3- 48 4
47 1 81
UC4 VN 47
2/Re
s
2
V3 -
SDE
4/K V2
UC2M3/TT51 18 182/ - 1 V1
UC1 M1 M2 AF3
T2
AF2
181/K
COM - T6Z3 Z4 AF1
- - Z2
- Z1
F1-
MTZ2 / MTZ3
F2+
H H
+3
NW
mm NW chassis retrofit For more information refer to the MasterPact MTZ Substitution and
technical guide reference LVPED516027EN.
=
Drawout version
DB419799
= Two identical frame sizes using the same mounting system as the Make the most of your equipment with available add-ons
CT1
CE1
CD1
CD2
I I
CE2
CE3
F1
F2
F3
=
a ct
Masterp
Aux
Aux
Power
Power VPS
VPS
AA
1000
InIn1000
J =
mm
[1]
• same connection points
• same fixing points.
Asset Connect MONITORING
J
PF MCH
T°, Humidity,
DB419126
DB419127
MN MX1 XF
See page E1
MX2
SDE1
MC2
SDE2 UC4
UC3
UC2 /Res
UC1
COM
=
Masterpact
HA10 12kV
NW40 Uimp
Ui 1250V
Ue 1150V 690/1000V
Ue 50kA/1s
peak
Icw 105kA
Icm 50/60Hz
AS NEMA
K K
60947-2 UNE
IEC CEI
BS
VDE 55°C
UTE
Ie
Ith 4000A Ue
(A)
(V)
4000
1000
AC23A 50/60Hz
60947-3 UNE
IEC BS CEI
VDE
UTE
R es et
Tes t
A
In 1000
EcoStruxure™ Asset
& Power Advisor
+3 MTZ2 / MTZ3 Power Monitoring Expert
mm See page 9 and page E1
NW
C28 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C29
www.se.com www.se.com
PE90688
PE90685
T140 drawers
PB116185
PB116185
PB116185
Commercialization commercialization parts availability
C C
Micrologic 2.0X 5.0X 6.0X 7.0X
Functions Long time Long time Long time Long time
+ instantaneous + short time + short time + short time Main technical characteristics
D + instantaneous + instantaneous
+ earth fault
+ instantaneous
+ earth leakage up to 3200 A T140 drawers T140 drawers D
Measurement: Energy management is the challenge of present & future generations. Rated operational voltage (V AC 50/60 Hz) Ue 440 V 440 V
To meet this requirement Micrologic X incorporates all the measuring functions of a power meter including Energy Class 1 accuracy 3rd party certified.
Rated current (A) In 40°C 125 - 625 A 125 - 625 A
Diagnostics & Maintenance: Optimal continuity of services as well as extended life of equipment is one of customers main concerns.
For that purpose Micrologic X integrates new extended diagnosis and assistance to maintenance. Ultimate breaking capacity 1 to 6 1 to 6
E Protection: Improvement of the reliability of Micrologic X, dual settings and additional facilities increase the performance and the flexibility of low voltage
systems of protection.
(kA rms, 220/415 V AC 50/60 Hz) Icu
E
Communication: It is now usual to make available most of the information processed by a Protection Control Unit, locally for network operation and
maintenance, and remotely for higher functions of control, monitoring, energy efficiency and assets management.
To comply with this requirement Micrologic X, incorporates several channels of communication, including Ethernet and wireless communication facilities.
T140 drawers ECOFIT™ solution
PE90685
F Smartpanel integration, architecture and systems
Available for ECOFIT™ solutions using MasterPact MTZ
The ECOFIT™ T140 drawer solution enables to benefit from all the enhanced features of latest F
technology devices.
A
TZ cture The drawer solutions are suitable for manual or electrical operations.
act Mn archite
terp
Internet
Mas unicatio
G G
facility hero
EcoStruxure
m facility insight
POWER
Com
100-230V
POWER
Asset Advisor
POWER
200
Com’X
EcoStruxure
Facility Advisor
T140 drawers ECOFIT™ solution - Drawer components
PB103354
example of digitized switchboard On site control
and monitoring system
• Electrical distribution - Functional units (NSX range with Micrologic)
H architecture
H
I
H
E
• Motor control command and protections - Functional units.
102870
102870
102873
24VDC
ETH2
ETH2
ETH1
ETH1
B
set)
Z (factory
IFE-XX.YY.Z
IFE
I6
C
I5
I4
C
I3
I2
C
I1
+
I I
24VDC
Ethernet
A1
O1
I1
O2
I2
O3
I3
APP
I4
C
I5
I6
LV434063
IO
T2
O3 T1
34
Modbus SL
O2 33
24
LC1D12
O1 23
14
13
106167
Compact NSX
111601
107395
0V
D1 D0
COM
LK/10-100/ACT
NETWORK R
COM STATUS ETHERNET
PF MCH
MN MX1 XF
STATUS
Q 24V +24V0V
I2
6 I1
F
SDE1
0V
MC2 5
I2
Q 24V
8
UC3
I1
0V
SDE2 UC4 I2
Q 24V
7
4 I1
UC2 /Res
0V
UC1 3
I2
Q 24V
6
COM
I1
0V
Q 24V
2 I1
I2 5
0V
Q 24V
1 I1
I2 4
0V
Q 24V
I1
I2 3
0V
2
1
ct
Masterpa
HA10 12kV
NW40 Uimp
Ui 1250V
Ue 1150V 690/1000V
Ue 50kA/1s
peak
Icw 105kA
PF MCH Icm 50/60Hz NEMA
MN MX1 XF
AS
60947-2CEI UNE
IEC BS
VDE 55°C
MX2 UTE
Ie
Ith 4000A Ue
(A)
(V)
MC2 SDE1
4000
1000
SDE2 UC4
UC3
AC23A 50/60Hz
UC2 /Res IEC
60947-3CEI UNE
UC1 VDE
BS
COM UTE
B FDM128 H IFM G
K K
Aux
Power VPS
Masterpact
HA10 12kV
NW40 Uimp
Ui 1250V A +24VDC
In 1000
CMD
SDOF0V
Ue 1150V 690/1000V
Ue 50kA/1s
peak
C EIFE
Icw 105kA
I Switch
Icm 50/60Hz
AS NEMA
60947-2CEI UNE
IEC BS
VDE 55°C
UTE
Ie
Ith 4000A Ue
(A)
(V)
4000
1000
AC23A 50/60Hz
60947-3CEI UNE
IEC BS
VDE
UTE
Masterpact fixed
Aux
Power VPS
circuit breaker
D IFE J ULP port
A
In 1000
Masterpact drawout
E I/O K ULP cord circuit breaker
C30 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C31
www.se.com www.se.com
PE90685
MB400 drawers
B ECOFIT™ solution
E E
1 component motor feeder 2 components motor feeder 3 components motor feeder
F The ECOFIT™ MB400 drawer solution enables to benefit from all the enhanced features of latest F
technology devices.
G G
MB400 drawers ECOFIT™ solution - Drawer components Circuit breaker - Thermomagnetic circuit breaker + Contactor Thermomagnetic circuit breaker or
PB103354
102870
102873
• Control command auxiliaries for all types of drawers. Protection auxiliary circuit
106167
J J
054047
111601
107395
K K
Specific spare parts: for any spare parts request for the fixe part, please contact your local correspondant.
C32 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C33
www.se.com www.se.com
Order N° Plug & Play solution Order N° C801 / 1251 ComPactkit solution (references not adapted, supplied as loose components)
Kit Plug & Play C801/1251 Qty Front connection 3P ref. EF593816 Qty 4P ref. EF593819 Qty
Delivery address Delivery address (Top & Bottom)
A A
Options Rear horizontal connection 3P ref. EF593817 Qty 4P ref. EF593820 Qty
Door option kit for electric mechanism or direct manual mechanism (Top & Bottom)
(include transparent cover ref 33859) Qty Rear vertical connection 3P ref. EF593818 Qty 4P ref. EF593821 Qty
Door option kit for prolongated manual mechanism Qty (Top & Bottom)
Customer's name Customer's name
Indication contacts Indication contacts
B B
NS800 to SD trip indication (maximum 1) (only for manually operated devices) NS800 to SD trip indication (maximum 1) (only for manually operated devices)
NS1250 6 A-240 V AC Qty Low level Qty NS1250 6 A - 240 V AC Qty Low level Qty
To indicate your choices, check the applicable square boxes To indicate your choices, check the applicable square boxes
SDE "fault-trip" indication (maximum 1) SDE "fault-trip" indication (maximum 1) (SDE integrated in electrically operated devices)
and enter the appropriate information in the rectangles and enter the appropriate information in the rectangles
(SDE integrated in electrically operated devices) 6 A - 240 V AC Qty Low level Qty
Circuit breaker or switch-disconnector 6 A-240 V AC Qty Low level Qty Circuit breaker or switch-disconnector
OF ON/OFF indication contacts (maximum 3)
NS800 to NS1250 OF ON/OFF indication contacts (maximum 3) NS800 to NS1250 6 A - 240 V AC Qty Low level Qty
C C
Rating A 6 A-240 V AC Qty Low level Qty Rating A
Circuit breaker N, H Circuit breaker N, H Remote operation
Switch-disconnector NA Remote operation Switch-disconnector NA Electrical Standard
Number of poles 3 or 4 Electrical Standard Number of poles 3 or 4 operation Power supply AC DC V
Device Fixed X operation Power supply AC DC V Device Fixed X Voltage MX AC DC V
Voltage MX AC DC V releases MN AC DC V
Micrologic control unit Micrologic control unit
D D
releases MN AC DC V MN delay unit Adjustable Non-adjustable
Basic protection 2.0 5.0 6.0* MN delay unit Adjustable Non-adjustable Basic protection 2.0 5.0 6.0*
A - Ammeter 2.0 5.0 6.0* 7.0* A - Ammeter 2.0 5.0 6.0* 7.0* Rotary handles for NS800 / 1250 fixed device
E - Energy 2.0 5.0 6.0* Rotary handles for NS800 / 1250 fixed device E - Energy 2.0 5.0 6.0* Direct Black Red on yellow front
P - Power 5.0 6.0* 7.0* Direct Black Red on yellow front P - Power 5.0 6.0* 7.0*
CNOMO conversion access
Locking
* For residual or source ground return earth fault protection * For residual or source ground return earth fault protection Toggle (1 to 3 padlocks) Removable system Fixed system
E E
with Micrologic 6 and earth leakage protection with Extended Black Red on yellow front with Micrologic 6 and earth leakage protection with
Rotary OFF position
Micrologic 7, please contact your Country Account Manager Micrologic 7, please contact your Country Account Manager
Locking (compulsory information) handle using Ronis 1351B.500 Profalux KS5 B24 D4Z
AD - External power-supply module V
Locking delivered and mounting on ECOFIT: 2 identical locks + 1 key for tripping withdrawal
AD - External power-supply module V a keylock Keylock kit (without keylock)
LR - Long-time rating plug Standard 0.4 to 1 Ir - specify Ronis or Profalux LR - Long-time rating plug Standard 0.4 to 1 Ir
For VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
Low setting 0.4 to 0.8 Ir Low setting 0.4 to 0.8 Ir electrically OFF position locking:
Rotary Ronis Profalux
High setting 0.8 to 1 Ir High setting 0.8 to 1 Ir operated VCPO - by padlocks
F F
handle using
LT off a keylock LT off devices
VSPO - by keylocks:
Communication For VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) Communication Keylock kit (w/o keylock) Profalux Ronis
electrically OFF position locking. VSPO - by keylocks: 1 keylock Profalux Ronis
COM module: contact your country Account manager operated COM module: contact your country Account manager
2 identical keylocks, 1 key Profalux Ronis 2 identical keylocks, 1 key Profalux Ronis
Micrologic control unit functions: devices Micrologic control unit functions:
• 2.0: basic protection (long time+ inst.) • 2.0: basic protection (long time+ inst.) Accessories
G • 5.0: selective protection (long time + short time + inst.)
• 6.0: selective + earth-fault protection (long time +
Accessories
CDM - mechanical operation counter (not compatible with rotary handle)
• 5.0: selective protection (long time + short time + inst.)
• 6.0: selective + earth-fault protection (long time +
CDM - mechanical operation counter
Test kits Mini test kit
G
short time + inst. + earth-fault) Test kits Mini test kit short time + inst. + earth-fault)
• 7.0: selective + earth-leakage protection (long time +
Spare parts for C801/C1251 chassis • 7.0: selective + earth-leakage protection (long time + C801 / 1251 ComPactkit solution - Door option kits (operation through door)(1)
short time + inst. + earth-leakage) short time + inst. + earth-leakage) Front connection electrical 3P ref. EF593822 Qty 4P ref. EF593826 Qty
2 clusters Ref. EF533706 Qty
operation
H Set of 5 fixed female connector
Lockable bolt on fixed chassis
Ref. EF533707
Ref. EF533708
Qty
Qty
NS800/1250 connection
Front connections Top & Bottom
Rear connection electrical
operation
3P ref. EF593823 Qty 4P ref. EF593827 Qty H
Horizontal rear connections Top & Bottom Front connection toggle 3P ref. EF593824 Qty 4P ref. EF593828 Qty
Note: Vertical rear connections Top & Bottom or direct rotary handle
DE90254
DE90255
• Pre-tripping with keylock locking (included as standard). Rear connection toggle 3P ref. EF593825 Qty 4P ref. EF593829 Qty
Note: or direct rotary handle
I • If NS electrically operated: only SDE available / SD not available.
• Discrimination & cascading: refer to http://hto.power.schneider-electric.com/
Check dimensions according to the below table, i.e. dimensions
are the necessary space to be added to the existing C801/1251
(1)
Restriction in case of operation through door I
• Solution not applicable for communication. to allow installation of the ComPactkit solutions. (1) (2) Axis X &Y are the symmetry planes of the ComPact C
DE90262
• Solution not applicable for control type toggle. D2 115mm Y
3-pole device. If door opens to the left: not suitable for
DE90260
DE90261
• CTs ComPact C not compatible with ComPact NS. rotary handle operation.
X
Axis Z is the back plane of the ComPact C 3-pole device.
• ComPact Plug & Play equipped with C4 type lock (MV / LV / transformer interlocking.
J J
D1
Distance between axis Z and door is 115 mm.
• ComPact Plug & Play can not be used for ComPact C801 / 1251 drawout breaker on (1) 194 mini (3P) - 264 mini (4P) / (2) 194 mini
cradle (with RED operating handle)
≥ 160 ≥ 105
• If ComPact C behind door, pay attention to minimal distance between door and CB.
If ≤ 160: door adaptation If ≤ 105: door adaptation - In case of manual ComPact NS, the door kit is compulsory for X < 160 mm.
necessary necessary - In case of motorized ComPact NS, the door kit is compulsory for X < 105 mm. Manual. by
K K
Manual. by Manual. by Electrically Electrically
direct rotary
handle short toogle long toogle by Type T by Type TS
D1 + 0 mm + 0 mm + 0 mm + 0 mm + 0 mm
Fixed front connection
D1 D2 + 0 mm + 45 mm + 15 mm + 0 mm + 30 mm
Fixed horizontal rear D1 + 15 mm + 15 mm + 15 mm + 15 mm + 15 mm
Z connection D2 + 70 mm + 110 mm + 80 mm + 50 mm + 95 mm
Fixed vertical rear D1 + 15 mm + 15 mm + 15 mm + 15 mm + 15 mm
Axis Z is the back plane of the ComPact C 3-pole device. connection D2 + 70 mm + 110 mm + 80 mm + 50 mm + 95 mm
C34 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C35
www.se.com www.se.com
To indicate your choices, check the applicable square boxes Operation Efficiency - Controlling To indicate your choices, check the applicable square boxes Operation Efficiency - Controlling
and enter the appropriate information in the rectangles Remote control MCH - gear motor V and enter the appropriate information in the rectangles Remote control MCH - gear motor V
Quantity XF - closing voltage release V Quantity XF - closing voltage release V
A Number of Devices
* The quantity specified here will not affect the quantity
MX - opening voltage release
MN - undervoltage release
V
V
Number of devices
The quantity specified here will not affect the quantity of spare parts.
XF COM - closing voltage release
MX - opening voltage release
V
V
A
of spare parts. R - delay unit (non-adjustable) V Basic Configuration MX COM - opening voltage release V
Basic Configuration Rr - adjustable delay unit V MasterPact type MTZ2 MTZ3 MN - undervoltage release V
MasterPact type P&P MTZ2 2nd MX - opening voltage release V Rating (Masterkit 4000 A only with MTZ2) A MN COM - undervoltage release V
Rating (3200 A max) Sensor rating A R - delay unit (non-adjustable)
B
A
B
2nd MN - undervoltage release V
Sensor rating A R - delay unit (non-adjustable) for 2nd MN Circuit breaker N1, H1, H2, L1 (L1: only for M08 Rr - adjustable delay unit
to M20 drawout type) 2nd MX - opening voltage release V
Circuit breaker N1, H1, H2 Rr - adjustable delay unit for 2nd MN
Switch-disconnector Not available with MasterPact MTZ, Remote reset RES - electrical reset option V Switch-disconnector NA, HA 2 MX COM - opening voltage release
nd
V
use P&P with MasterPact NW after tripping RAR - automatic reset option Micrologic X 2.0 5.0 6.0 7.0 2nd MN - undervoltage release V
Micrologic X 2.0 5.0 6.0 7.0 Electrical Closing BPFE - electrical closing pushbutton Number of poles 3 4 2nd MN COM - undervoltage release V
C C
Number of poles 3 4(1) Option: neutral on right side (MTZ2 only up to 3200 A) R - delay unit (non-adjustable) for 2nd MN
People and property safety - Locking and interlocking
(1) 4P = neutral on left. For neutral on right side, Type of equipment Fixed
VBP - ON/OFF pushbutton no access (by transparent cover + padlocks) Rr - adjustable delay unit for 2nd MN
consult France Grenoble Ecofit Center Drawout with chassis
OFF position locking: Remote reset after RES - electrical reset option V
Type of equipment Drawout without chassis Drawout without chassis
VCPO - by padlocks tripping RAR - automatic reset option
(moving part only)
Chassis alone Electrical closing BPFE - electrical closing pushbutton
VSPO - by keylocks Keylock kit (without keylock) Profalux Ronis
Communication Chassis alone with contacts People and property safety - Locking and interlocking
D D
Kirk Castell
Consult Schneider Electric specialist to support and upgrade Connection Top Horizontal Vertical
current installation with latest communicating solution 1 keylock Profalux Ronis VBP - ON/OFF pushbutton no access (by transparent cover + padlocks)
(rear only) Bottom Horizontal Vertical
2 identical keylocks, 1 key Profalux Ronis OFF position locking:
Operation Efficiency - Signaling For M40 4P fixed type, no possible mix between horizontal and
2 keylocks, different keys (MTZ2/3) Profalux Ronis VCPO - by padlocks
OF - ON/OFF indication contacts vertical connections
Mechanical interlock (source-changeover systems) VSPO - by keylocks Keylock kit (without keylock) Profalux Ronis
4 OF 6 A - 240 V AC (10 A - 240 V AC and low level for NW) For M63 drawout horizontal connection, consult us
is supplied as standard Interlocking axle and installation kit (ref: EF548613, one per P&P ) Kirk Castell
Communication(1)
E Note: MasterPact Plug&Play is not suitable in case MasterPact
M chassis is equipped with a test position switch (CT)
Additional 1 block of 4 OF for MTZ2 Qty
Mismatch protection (ref EF547056)
People and property safety - Circuit protection
Modbus interface
Ethernet interface for 1 breaker
1 keylock
2 identical keylocks, 1 key
Profalux
Profalux
Ronis
Ronis E
TCE - external sensor (CT) for neutral Ethernet interface + Gateway 2 keylocks, different keys (MTZ2/3) Profalux Ronis
Max. 2 Blocks
Single sensor & Single wire (MTZ 1/2/3) ULP port module Chassis locking in “disconnected” position:
SDE - “fault-trip” indication contact
Rectangular sensor - for earth-leakage protection MTZ2/3 (470 x 160 mm) I/O Module VSPD - by keylocks Keylock kit (without keylock) Profalux Ronis
1 SDE 6 A - 240 V AC is supplied as standard
Kirk Castell
F F
Additional 1 SDE 6 A - 240 V AC 1 SDE low level Power availability and realiability (1) Consult Schneider Electric specialist to support and upgrade
current installation with latest communicating solution 1 keylock Profalux Ronis
Programmable contacts 2 M2C contacts VPS - voltage power supply
PF - “ready to close” contact AD - external power-supply module V Design and installation simplification 2 identical keylocks, 1 key Profalux Ronis
Interphase barriers MTZ2 fixed, drawable 2 keylocks, different keys Profalux Ronis
6 A - 240 V AC Low level Digital Module Only up to MTZ 2 25 Upstream & Downstream Optional connected / disconnected / test position locking
CDM - mechanical operation counter MTZ2 Energy per phase Wave form capture Operation Efficiency - Signaling VPEC - door interlock On right-hand side of chassis
Commomnly used spare parts Circuit Breaker restoration Circuit Breaker reclosing
G If you would like to order some spare parts, kindly indicate
here. Please note that spare parts will be delivered ECOFIT™ Plug & Play solution requires MasterPact M chassis in full working order
OF - ON/OFF indication contacts
4 OF 6 A - 240 V AC (10 A - 240 V AC and low level for NW)
is supplied as standard
VPOC - racking interlock
On left-hand side of chassis
I I
Programmable contacts 2 M2C contacts Rectangular sensor for earth-leakage protection MTZ2/3 (470 x 160 mm)
DE90248
PE90614
Auxiliary wiring connector Check for any bent or distorted parts that could hinder
plate insertion of the MasterPact circuit breaker. Carriage switches - Please refer to the catalogue PTE - external voltage connector
for the maximum number of each carriage switch
People and property safety - Mechanical protection
CE - “con.” position 6 A - 240 V AC qty Low level qty
CDP - escutcheon MTZ2/3
CD - “discon.” position 6 A - 240 V AC qty Low level qty
CP - transparent cover for escutcheon MTZ2/3
CT - “test” position 6 A - 240 V AC qty Low level qty
A B • M
easure the diagonals OP - blanking plate for escutcheon MTZ2/3
J J
PF - “ready to close” 6 A - 240 V AC Low level
to make sure the chassis is Carry out a racking test (in and out) 3 times without the circuit breaker and check the movement CB - auxiliary terminal shield for chassis MTZ2/3
contact
not distorted or warped. of the safety shutters, the auxiliary wiring connector plate and the drawer site plates.
CDM - mechanical operation counter MTZ2/3 People and property safety - Operation protection
Squareness chassis
± 3 mm (A = B). • C
heck the contact clusters. If they are in good condition, Commomnly used spare parts KMT - grounding kit MTZ2/3
DE90249
clean and lubricate them. If not, replace them. If you would like to order some spare parts, kindly indicate here. Earthing switch kit for chassis
• C
heck that all moving parts (pawls, cams) work properly. Please note that spare parts will be delivered spaperately. DAE - automatic spring discharge before breaker removal for MTZ2/3
K • C
heck visually for any • Check cradle warm screw:
Mobile PowerPact by APC Power availability and realiability
K
DE90248
C36 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 C37
Power and distribution
www.se.com www.se.com
Oil transformers............................................... D3
C38 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 D1
www.se.com www.se.com
PM10604
PE90841
PM10605
B B
ECOFIT™ solution ECOFIT™ solution
End of End of
Commercialization commercialization End of full spare parts availability Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D Dry transformer Trihal Oil transformer Minera D
Rated power 100 kVA to 15 MVA 100 kVA to 15 MVA Rated power 50 kVA to 3.15 MVA 50 kVA to 3.15 MVA
Rated insulation level Up to 36 kV Up to 36 kV Rated insulation level Up to 36 kV< Up to 36 kV
E E
Rated Frequency 50 Hz or 60 Hz 50 Hz or 60 Hz Rated frequency 50 Hz or 60 Hz 50 Hz or 60 Hz
MV windings Not available Encapsulated in cast resin Type of cooling ONAN, ONAF or KNAN ONAN, ONAF or KNAN
Thermal insulation Not available Class F Voltage regulation Off-circuit tap changer (DETC) Off-circuit tap changer (DETC)
Safety and reliability Not available IEC 60076-11 and IEC 60076-16 High Efficiency Transformer Conventional losses High efficiency ranges
• E3 Environment test
F F
Ecodesign Not applicable EN 50588-1
• C2 or C3 Climate Test
• F1 Fire Behaviour Location Indoor / outdoor Indoor / outdoor
• ≤ 5pC Special test for partial discharge
Silicone free Options Not available • Compact design (Slimtrim range)
• Breathing or sealed type
Cooling Naturally cooled or air forced Naturally cooled or air forced • Standard or low noise levels
• Biodegradable vegetable oil
G Location
IP
Indoor / outdoor
Up to 44
Indoor
Up to 44
• A wide variety of accessories G
Digitalization Not available • DGPT
Hazard proof Not available Self extinguishing • DMCR (Detection, Measurement, Control Relay)
Ecodesign Not available EU 548-2014 - EN 50588-1
K • Cloud connection to EcoStruxure Asset Advisor • Cloud connection to EcoStruxure Asset Advisor
K
D2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 D3
Upgrade with Asset Connect
www.se.com www.se.com
Asset Connect
Digitize and monitor your equipment with smart sensors
Financial impact of one hour of downtime How we can help you?
(Source: Contingency Planning Research) When the time comes to modernization, upgrade your equipment to:
• Prevent unscheduled downtimes (cf. Table 1)
Application Loss(1) in €
• Increase safety (operators and installations)
Health establishment Human lives....
• Allow condition based maintenance
Stock market transactions 6,500,000
• Maximize service continuity, anticipate possible disruptions
Credit card sales 2,600,000 • Protect the investment, maximizing the equipment lifetime.
Petrochemical 100,000
Plane ticket booking system
Mobile phone network
90,000
40,000
What if the equipment could communicate?
Easergy TH110 - Monitor connections temperature A
Automobile 30,000 Loose low or medium voltage products power connections are one of the most
sensitive concern for electrical substations
Pharmaceutical 30,000
• MV cable connections
Food processing 20,000
Cement 15,000
(1) Direct and indirect costs of non availability
• MV busbars connections or LV busways
• Withdrawable CB connections. B
Defective connections cause an increase of resistance in the contact points that
could lead to thermal runaway, connections complete destruction… and potential
fire hazard.
Preventive maintenance can be complicated due to limited accessibility and visibility
of the contacts.
Continuous thermal monitoring is an effective way to detect loose connections
C
earlier.
Easergy CL110 - Monitor ambient humidity and temperature
Humidity monitoring in the substation contributes to the efficient ventilation and
guarantee proper operating condition.
Humidity monitoring helps ventilation failure detection leading to moisture, ozone, D
partial discharge in the substation.
Arc Flash sensors - Detect arc and reduce damage on equipment
and human injuries
An arc flash is an electrical accident that creates a high-temperature explosion.
It can vaporize surrounding metal, set fires, and result in severe burns. Although
rare, arc flashes can have grave consequences so you need to ensure your people
E
and site are always protected. An arc flash can happen during abnormal use
due to a corruption of isolation, or in circumstances involving animals, flooding,
vibrations, or corrosion. Yet, it can also occur during commissioning or maintenance,
rendering equipment unusable and forcing costly downtime with serious economic
consequences. Prevent accidents and protect your site with our arc flash protection F
solutions for both safety and productivity.
H
Apps and analytics
Cloud services level
EcoStruxure
Facility Advisor
EcoStruxure
Asset Advisor
I
Edge control
Facility level J
EcoStruxure Power EcoStruxure Power
Scada Expert Monitoring Expert
Connect products
K
Equipment level
HMI (Substation
monitoring device)
D4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 E1
www.se.com www.se.com
B Environmental monitoring
Easergy CL110 wireless battery powered sensors
B
to monitor the condensation within the switchgear.
C Thermal Apps
C
Circuit breaker monitoring
Read the thermal status of complete switchgear up to
Real-time circuit breaker monitoring
10m with a smart device through “Thermal connect”
• Mechanical aging
a simple & cost effective App.
D • Operating time performance
• MV contact aging D
• Motor spring charging performance
E E
F F
I Nearby control
Operate and monitor equipment features
Power monitor / SCADA integration I
Health data can be easily integrated within Power
(temperature, environment, circuit breaker, Scada Operations or Power Monitoring Expert
transformer, etc.) from a local smart device. or even in a third party.
J J
SMS alerts
Instant SMS alert notifications if any of the health
parameters (Thermal, Environment, Circuit breaker)
E2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 E3
www.se.com www.se.com
(1)
DVCAS 3 3 Satellite Modbus Serial Box
D Motorpact 3 3
(1)
(1)
Features D
Masterclad 15kV 3 3 Zigbee concentrator 1
Pix ROF 3 3 3 Zigbee sensors (TH110 Up to 60 sensors per Zigbee concentrator (up to 180 sensors
McSET 1,2,3,4 3 3 or CL110) management with 3 units of ZBRN32)
(1)
E E
HWX 3 Communication 2 ports Serial Modbus RS485 RJ45
(1)
Masterclad 27kV 3 3
(1)
Nex 3 3
(1)
HVL 3
Asset Connect helps you to upgrade Premset 3
(1)
Digital Box
F F
(1)
your installation with smart sensors, Dry Transformer Trihal < 36kV including windings na Features
Tfos
(1)
transforming non-communicating Oil Transformer Minera 3 na Free Digital input COMX: 6 inputs
(1)
Busway - KT 3 3 Free Digital output COMX: 0 output
equipment into connected assets.
Low Volatge
(1)
Busway – I-line 3 3 Analogue inputs (PT100) COMX: 2 inputs
These upgrades open your electrical (1)
Prisma, Prisma P 3 na
installation to a full spectrum of advanced Zigbee concentrator Up to 10 ZBRN32 in daisy chain
G capabilities, such as preventive or predictive
Okken - Blokset (1)
na (1)
management Only one Zigbee concentrator available in the Digital box
Additional Zigbee concentrator installed in satellite Modbus
G
asset performance management services. TCP box
Legacy ranges and ECOFIT™ Zigbee sensors (TH110 Up to 60 sensors per Zigbee concentrator (up to 180
or CL110) management sensors)
Connection Ambiant Arc flash
H temperature
monitoring
humidity and detection
temperature
Free Ethernet switches 1 dedicated to the communication with the LAN or used by
the 3G modem H
(1) (1) 1 or 4 for Ethernet communication with devices, 4 with the
Fluair 100-200 3
(1) (1)
Ethernet switch option
HMC 3
(1) (1) Network communication Modbus Serial
YSF6 3 RS485 RJ45
I Venus
WBA
3
3
(1)
(1)
(1)
(1)
SMS
Modbus TCP/IP Ethernet
No
I
Medium Volatge
(1) (1)
WBB 3 Communication to the cloud Yes
(1) (1)
VAD2 3
(1) (1)
VAD3 3
J B200
YSF6
3
3
(1)
(1)
(1)
(1)
J
WKC mid 2021 (1) (1)
Satellite Modbus TCP Box
(1) (1)
GE mid 2021 Features
(1) (1)
B200 mid 2021 Zigbee concentrator 1, 2 or 3
K B400 mid 2021 (1) (1)
Zigbee sensors (TH110
or CL110) management
Up to 60 sensors per Zigbee concentrator (up to 180 sensors
per Satellite Modbus TCP box)
K
LV Circuit Breaker and Panels (1) (1)
3
LV
E4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 E5
Protection relays
www.se.com www.se.com
Protection relays
Protection relays
Protection relay upgrade benefits..................... F2
CDG.................................................................. F3
CO.................................................................... F4
DPU 445........................................................... F5
HCB / HCB1...................................................... F6
MCAG 34.......................................................... F8
Order forms
ECOFIT™ S2000............................................. F20
E6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F1
www.se.com www.se.com
ECOFIT™ proposal
CDG Easergy P1 / P3 / P5 With ECOFIT™, a true extended life time
Protection relay or MiCOM P40
A Protection relay 2018 A
PE90881
Improve the performance of your system Why protection upgrade? CDG
with the latest technology in micro-processor Easergy P1 / P3 / P5
By replacing solid state relays, older type electromechanical protection relays
based integrated relays. or MiCOM P40
or legacy relays with technologically advanced multi-function microprocessor-
B based digital relays, the performance accuracy and longevity of your system can
be significantly improved.
ECOFIT™ solution B
With a number of different protection functions Schneider Electric's range of End of
relays can provide a range of options to include metering; communication, Commercialization commercialization End of full spare parts availability
cyber security, event capture, monitoring and control. Units are self-diagnostic
High reliability from advanced self supervision systems. Frequency range Calibrated for 50 Hz or 60 Hz only 50 to 60 Hz +/- 20 %
H H
Safer and secure Enhance operator's safety and be better protected against cyber attacks.
Reliable and sustainable Extend products usability and maintainability in a longer term.
I Ease of use Settings and adjustments are entered via the device's keypad or via
user friendly setting software and visually displayed. I
The amalgamation of functions into one self-diagnosing device
Reduced costs
reduces expenditure and saves on space.
J J
K K
F2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F3
www.se.com www.se.com
PE90872
CO DPU 445
PE90873
MiCOM P111/115 MiCOM P123
ECOFIT™ solution
B End of End of
ECOFIT™ solution
B
Commercialization commercialization End of full spare parts availability Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D CO-1 to CO-9 MiCOM P111/115 DPU 445 MiCOM P123 D
Case FT-11 or FT 21 Fit FT-11 & FT 21 cutout Case DPU 445 Fit existing cutout
Replacement Type - 1 for 3* with minimal rewiring Replacement Type - 1 for 1 with minimal rewiring
E E
Type Electromechanical Digital Type Digital Numerical
Functionality Single phase overcurrent 3 phase + Ground overcurrent Functionality 3 phase feeder 3 phase + ground feeder overcurrent
Power supply - 24 VDC - 250 VDC Power supply 24 VDC - 125 VDC 24 VDC - 250 VDC
Communication - IEC 60870-5-103, Modbus RTU Communication - Courier, DNP 3.0, IEC 60870-5-103, Modbus RTU
G G
H H
I I
J J
K K
F4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F5
www.se.com www.se.com
PE90871
End of End of
Commercialization commercialization End of full spare parts availability Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D HCB / HCB1 MiCOM P521 IAC, IFC, DIAC and BE1-50/51 B ECOFIT 50/51 D
Case FT-42 Fit existing cutout Case S1 (IAC) - C1 (IFC) The legacy relay case is reused in Plug and Protect
Replacement Type - 1 for 1 with minimal rewiring Type Electromechanical or digital Numerical
E E
Type Electromechanical Digital Functionality Single phase overcurrent Single phase overcurrent
Functionality 3 phases differential 3 phases differential Power supply Self powered Self powered
Power supply - 24 VDC - 250 VDC The Schneider Electric ECOFIT 50/51 single phase or ground time overcurrent relays are direct plug and protect replacements for many GE IAC or GE IFC
electromechanical, GE DIAC and Basler BE1-50/51B replacements for GE IAC relays. The relays are selfpowered from 50 or 60 Hz systems and are designed
Communication - IEC 60870-5-103, Modbus RTU to be one to one replacements for existing electromechanical or digital relays.
F F
*1 ECOFIT™ P521 - IAC solution could replace 3 single phase IAC units. The relays are equipped with 31 built-in protection curves.
ECOFIT 50/51 provides information that was not available in the E/M relays:
- Twenty (20) overcurrent fault records time-tagged to the millisecond
- 200 events records time stamped to the millisecond
- Ten (10) Disturbance records up to 4 seconds per record at a sample rate of 32 samples per cycle.
Plug and Protect reduces costs in installation time because it saves existing wiring and reduces engineering costs over other options.
G G
H H
I I
J J
K K
F6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F7
www.se.com www.se.com
PE90752
PE90635
PE91037
PE90875
PE90635
MCAG 34 M range relay - MCGG 11, 21 & 22
MiCOM P126 MiCOM P120H
ECOFIT™ solution
B End of
ECOFIT™ solution
Commercialization End of full spare parts availability
B
Commercialization commercialization End of full spare parts availability
C C
Main technical characteristics Main technical characteristics
D MCAG 34 MiCOM P126 M range relay - MCGG 11, 21 & 22 MiCOM P120H D
Case 40TE size (MiDos 6) flush mounting 40TE size flush mounting Case 20TE size flush mounting 20TE size flush mounting
Installation Withdrawable case Withdrawable case Installation Withdrawable case Withdrawable case
E E
Language Multilanguage Multilanguage Language English Multilanguage
Communication No Communication Kbus / Courier, DNP3, IEC60870-5-103, Modbus RS485 Communication Kbus / Courier Kbus / Courier, DNP3, IEC60870-5-103
Power supply No Vx required 24 / 250 VDC - 55 / 250 VAC Power supply 24 / 125 VDC - 48 / 250 VDC 24 / 250 VDC - 48 / 240 VDC
Digital input supply 48 VDC only According to Power Supply (above)
F F
G G
H H
I I
J J
K K
F8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F9
www.se.com www.se.com
PE90635
PE90874
PE90875
PE90635
C C
Main technical characteristics Main technical characteristics
D M range relay - MCTI 39-40 MiCOM P821MF MCGG 62 MiCOM P126 D
Case 20TE size flush mounting 20TE size flush mounting Case Size 6 Fit existing cutout
Installation Withdrawable case Withdrawable case Replacement Type - 1 for 1 plug-and-play
E E
Language English Multilanguage Type Static Digital
Communication Kbus / Courier Kbus / Courier, DNP3, IEC60870-5-103 Functionality 3 phase overcurrent 3 phase + ground overcurrent
Power supply 24 / 125 VDC - 48 / 250 VDC 24 / 250 VDC - 48 / 240 VDC Power supply 24 VDC - 125 VDC 24 VDC - 250 VDC
Digital input supply 48 VDC only According to Power Supply (above) Communication - DNP 3.0, IEC 60870-5-103, Modbus RTU
F F
G G
H H
I I
J J
K K
F10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F11
www.se.com www.se.com
PE90635
PE88030
MVTR 51 Sepam series 20
MiCOM P123 Easergy P3
B End of
ECOFIT™ solution ECOFIT™ solution
B
Commercialization commercialization End of full spare parts availability End of End of full spare
Commercialization commercialization parts availability
J J
ECOFIT conversion tool
*.S40, *.S41, *.S42, *.S43, *.S44, *.S50, *.S51, (SCT)
*.S52, *.S53, *.S54, *.T40, *.T42, *.T50, *.T52,
*.M40, *.M41 or *.G40 for Sepam series 40 Conversion
(according to the type of application) report Flush mounting Offset mounting
F12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F13
www.se.com www.se.com
PE90635
Sepam series 40 MiCOM Px20 (20TE)
Easergy P3 Easergy P5
ECOFIT™ solution
B ECOFIT™ solution
End of End of full spare
B
End of End of full spare Commercialization commercialization parts availability
Commercialization commercialization parts availability
* Please consult Schneider Electric
* Please consult Schneider Electric
I I
Setting file Setting file
Sepam series 20 or
2 possible positions depth mounting *.epz for Easergy P5
Sepam series 40 *.epz for Easergy P3U30 ECOFIT ECOFIT
Easergy P3 SFT 2841 Easergy P5
Setting software
SFT 2841 eSetup Easergy Pro or Setting file
eSetup Easergy Pro
Setting file Setting software
Setting software Setting software
*.rpg for Sepam series 20 Easergy Studio *.rpg for Sepam series 20
ECOFIT conversion tool
J J
ECOFIT conversion tool Setting software
*.S40, *.S41, *.S42, *.S43, *.S44, *.S50, *.S51, *.S40, *.S41, *.S42, *.S43, *.S44, *.S50, *.S51, (SCT)
(SCT) *.S52, *.S53, *.S54, *.T40, *.T42, *.T50, *.T52,
*.S52, *.S53, *.S54, *.T40, *.T42, *.T50, *.T52,
*.M40, *.M41 or *.G40 for Sepam series 40 Conversion *.M40, *.M41 or *.G40 for Sepam series 40 Conversion
(according to the type of application) report (according to the type of application) report
Flush mounting Offset mounting
*.set for MiCOM P20
MiCOM P20
K To request for a quote, please use the ECOFIT™ To request for a quote, please use the ECOFIT™ K
web selector: web selector:
se.com/ecofitselector se.com/ecofitselector
F14 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F15
www.se.com www.se.com
PE88030
MiCOM Px20 (30TE) Sepam series 20
Easergy P5 Easergy P5
ECOFIT™ solution ECOFIT™ solution
B End of End of full spare End of End of full spare
B
Commercialization commercialization parts availability Commercialization commercialization parts availability
F F
Power supply 24 - 250 VDC; 48V - 240 VAC 24 - 48 VDC or 48 - 250 VDC; 100 - 230 VAC
Control LED 11 leds 10 LEDs
Control LED 8 leds 14 LEDs
Single line diagram (Mimic) No Yes
Single line diagram (Mimic) No Yes
Programmable function key No 1
Programmable function key No 7
Cyber security No Yes
Cyber security No Yes
G Arc flash No 0 to 6 sensors
Back-up memory No Yes
Sepam series 20 models compatibles with the ECOFIT™ Easergy P5 (20TE): S20 / S23 / S24 / T20 / T23 / T24 /B20 / B21 /
G
Back-up memory No Yes B22 / M20
Compatibility
Compatibility MiCOM Px20 (30TE) models compatible the ECOFIT™ Easergy P5 (30TE): P126 / P127 / P220 / P225 For Sepam + MSA141 (analog ouptup module) and/or ACE990 (Core balance CT interface) and/or DSM303
(Remote advance UMI display): Please consult Schneider Electric
F16 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F17
www.se.com www.se.com
PE90639
PE88030
PE90638
Sepam series 40 Sepam 2000
Easergy P5 Sepam series 60 or series 80
PE90637
Setting software
*.S40, *.S41, *.S42, *.S43, *.S44, *.S50, *.S51, (SCT)
*.S52, *.S53, *.S54, *.T40, *.T42, *.T50, *.T52, Flush mounting Offset mounting
*.M40, *.M41 or *.G40 for Sepam series 40 Conversion
(according to the type of application) report No mechanical or electrical impact on your installation.
*.set for MiCOM P20 Implementation and site test within a very limited time.
K MiCOM P20
To request for a quote, please use the ECOFIT™ New features enabled:
• Advanced HMI for local control functions.
K
web selector:
• Standard communication protocols (Modbus serial, Modbus Ethernet,
se.com/ecofitselector IEC60870-5-103, DNP3, IEC61850).
• Monitoring & Automation facilities.
F18 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F19
www.se.com www.se.com
F F
T04, T11 UA
T05, T16 EN (US)
Transformer application with temperature sensor Number of connected ESTOR boards
T27, T32, T33 Required polarity for logical. Standard
T21, T29, T34, T37, T39 Inputs, when non standard: H
T23, T33, T35, T38 (G=220/250 VDC ; H=110/125 VDC) G
G T22, T30
T24, T31
VT connection arrangement 3 VTs
2 VTs
G
T25, T36 1 VT
Generator application 1 V0
G01, G05, G07 other
I G18
G15
Unknown
24 VDC Power Supply delivery for Yes I
G16 the ACE949-2 Modbus module No
Capacitor bank application Confirm if you want a specific S81
C02, C04, C06 application (only if different from S82
C08 the proposed one) S84
J C01, C03
Transformer and generator bloc group application
M81
M87
J
D02, D22 (former D01, D21) M88
Line application T82
L66 T87
K Other specific application not covered
G87
G88
K
Please, confirm here Other B83
(1) Write a ''X'' in front of the original Sepam 2000 application in case of unique name, or the name of the original application if multiple choices are proposed (This selection will define
the new Sepam type within the series 60 or 80, its hardware configuration and its application). The name of the original application is repeated on the ECOFIT™ name plate reference.
(2) If a choice is possible betwen Sepam Serie 60 or 80, the Yes (Y) choice will force the delivery of a Sepam Serie 80. This will be the case if the original control logic provided with the
Sepam 2000 has been customised or if the Sepam 2000 is connected to a supervision using different addresses for remote controls (TS/TC), than those configured in factory.
F20 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F21
www.se.com www.se.com
Location:
Yes No
D Existing external wiring drawing
D
Existing Single line diagram
Yes No
H H
All of these informations are mandatory and have to be filled.
Please send all supportive documents with this completed request form to avoid any unnecessary delays.
To request for a quote, please use the ECOFIT™ web selector: se.com/ecofitselector
I I
J J
K K
F22 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 F23
Distribution Automation
www.se.com www.se.com
Distribution Automation
and Substation Automation and Substation Automation
ADVC1............................................................. G7
ADVC2............................................................. G8
ADVC lite.......................................................... G9
DCX............................................................... G11
GE Fanuc....................................................... G12
PTCC............................................................. G15
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G1
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
Talus or Easergy T200 S or I, Easergy R200/ATS100, Talus or Easergy T200 S or I, Easergy R200/ATS100,
RCV420 or RNS11 with Easergy T300 RCV420 or RNS11 with Easergy T300
Original brand: Merlin Gerin, Schneider Electric Original brand: Merlin Gerin, Schneider Electric
E E
BTA solution
K K
G2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G3
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
Talus or Easergy T200 E, P or I Talus or Easergy T200 E, P or I
with Easergy T300 with Easergy T300
Original brand: Merlin Gerin, Schneider Electric Original brand: Merlin Gerin, Schneider Electric
ECOFIT™ proposal
Easergy T200 Easergy T300 With ECOFIT™, a true extended life time
cabinet cabinet Remote Control and
A 1999 2018 2019 2020 2021 2026 2028 2030 Monitoring Applications A
PM106098
PE57920G
End of commercialization*
End of spare Remote Control and Monitoring MV substation
Easergy T200E part availability* (4 switchgears/circuit breakers)
End of commercialization*
B Easergy T200P
End of spare
part availability*
Remote Control and Monitoring MV substation
(2 overhead switchgears)
B
End of commercialization*
Remote Control and Monitoring MV substation
Easergy T200I (16 switchgears/circuit breakers)
Easergy T300
C Easergy T300 Commercialization Commercialization C
* Please consult Schneider Electric
E management
Uninterruptible power
1 to 4 1 to 16 1 to 2 (overhead) 1 to 24
SCADA communication
security (IEC 62351-5)
No No No Yes E
24 or 48 VDC 24 or 48 VDC 24 or 48 VDC 24 or 48 VDC
supply Local and remote access
Fault passage indicator Yes Yes Yes Yes security based on RBAC No No No Yes
(IEC 62351-8)
Current measurements Yes Yes Yes Yes
F Voltage measurements No No Yes Yes
Connection security for
maintenance (local and No No No Yes F
Voltage monitoring + Sensor remote): HTTPS, SSH
MV and LV Power Protocol security for file
No No No Yes according to IEC 61557-12 No No No Yes
measurement transfer: SFTP
G G
MV and LV Power quality No No No Yes according to IEC 61000-4-30 Class S Authentication by
No No No Yes
centralized Radius client
Advanced non-directional and directional fault
current detection for all neutral systems
Protection No No No
MV broken conductor detection based on voltage
LV broken conducteur detection (fuse detection)
MV network reconfiguration
H automation functions
Yes Yes Yes Yes
H
Local display and control Yes Yes Yes Yes
IEC 870-5-101 and 104, IEC 870-5-101 and 104, IEC 870-5-101 and 104, Client and server protocols: IEC 60870-5-101/104,
Communication protocols DNP3/DNP3 IP, Modbus/ DNP3/DNP3 IP, Modbus/ DNP3/DNP3 IP, Modbus/ DNP3, Modbus, IEC 61850
ModbusTCP ModbusTCP ModbusTCP Multi-protocol and redundancy management
I Transmission system
Ethernet, RS232, Radio, Ethernet, RS232, Radio, Ethernet, RS232, Radio, Flexible communication media: Ethernet, USB, 2G,
PSTN, GSM/GPRS, 3G, PSTN, GSM/GPRS, 3G, PSTN, GSM/GPRS, 3G, 3G, 4G, RS232/485
I
private line private line private line Wi-Fi connectivity for local operation
Peer to peer communication Yes Yes Yes Yes
Calculation formulas for
J basic customer defined
logic
Yes Yes Yes Yes
J
Yes
IEC61131 soft PLC No Yes Yes Sectionalizer; Auto transfer source; Self-healing and
dedicated, based on IEC 61131-3 PLC
G4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G5
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
Control System upgrade benefits ADVC 1
with ADVC 3
Original brand: Schneider Electric
ECOFIT™ proposal
ADVC 1 ADVC 3 With ECOFIT™, a true extended life time
Protection relay Protection relay
A 2001 2011 2017 A
PE91033
Improve the performance of your automation control Why Control Systems upgrade? ADVC 1
system with the latest technology offered by EcoStruxure
Upgrade solutions intend to improve the performance of your control system ADVC 3
Substation Operation offer and components.
with the latest technology in computers. This is also the opportunity to
B benefit from computer and OS upgrading to Windows® 10 to get enhances
performances and advanced features for the new HMI.
ECOFIT™ solution
B
End of
Commercialization commercialization End of full spare parts availability
Considering the large variety of legacy control systems still in operation with
limited extension and maintenance facilities, these Ecofit solutions provide an
Ready for future Enables smooth and consistent legacy Control System solutions Memory 16 MB 512 MB
extensions modernization. Storage 32 MB 1 GB
E Open, flexible and scalable architecture facilitating aggregation CPU Frequency 40 MHz 800 MHz E
of several systems at substation level. Ethernet 10 Base-T 100 Base-T
USB N/A USB 2.0
Easiness for future extensions.
H H
Zoom in / Zoom out.
J J
K K
G6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G7
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
ADVC 2 ADVC Lite
with ADVC 3 with ADVC 3
Original brand: Schneider Electric Original brand: Schneider Electric
PM106602
ADVC 2 ADVC Lite
ADVC 3 ADVC 3
B ECOFIT™ solution
C C
Main technical characteristics Main technical characteristics
D ADVC 2 ADVC 3 ADVC Lite ADVC 3 D
Design Element Design Element
Memory 32 MB 512 MB Memory 512 kB 512 MB
Storage 64 MB 1 GB Storage 2 MB 1 GB
E CPU Frequency 48 MHz 800 MHz CPU Frequency 22.5 MHz 800 MHz E
Ethernet 10 Base-T 100 Base-T Ethernet N/A 100 Base-T
USB Serial USB 2.0 USB Serial USB 2.0
F Communication Ports
Ethernet 1 x 10 Base-T 2 x 100 Base-T
Communication Ports
Ethernet N/A 2 x 100 Base-T F
RS-232 4 2 RS-232 1 2
RS-485 1 N/A RS-485 N/A N/A
G V23
USB Type B
1
1 x UART Based USB
N/A
1 x USB 2.0
V23
USB Type B
N/A
1 x UART Based USB
N/A
1 x USB 2.0
G
USB Type A N/A 3 x USB 2.0 USB Type A N/A 3 x USB 2.0
H H
I I
J J
K K
G8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G9
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
Bay controller BM9x00 DCX
with MiCOM C264 with MiCOM C264
Original brand: Alstom, AREVA Original brand: Alstom, AREVA
PM106603
BM9x00 DCX
MiCOM C264 MiCOM C264
B ECOFIT™
solution
ECOFIT™ solution
B
End of
End Commercialization commercialization End of full spare parts availability
Commercialization End of commercialization of maintenance
C C
Main technical characteristics Main technical characteristics
D BM9x00 MiCOM C264 DCX MiCOM C264 D
Communication through legacy EFIP protocol with the SCADA level Standard communication through IEC 61850 protocol to SCADA level Installation Plug'n play adapters original 40TE case
Connection with Modbus, IEC 103 or Conection with Modbus, IEC 870-5-103, IEC 870-5-101, Kbus (through HMI - equipment mimic Yes, hardware dependent Yes, user friendly mimic configuration
Kbus communication with protection relays K101CVT converter) and IEC 61850 protocol for downstream relays
E E
Power supply 24, 48/60, 10/127, 220 V DC 24, 48/60, 10/127, 220 V DC
No front side communication available for setting files management Rugged to match substation cyber security requirements
Digital inputs voltage 24, 48/60, 10/127, 220 V DC 24, 48/60, 10/127, 220 V DC
Modbus RTU Modbus RTU and TCP, IEC 61850
Communication
Fixed Modbus mapping User configurated Modbus mapping
F F
G G
H H
I I
J J
K K
G10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G11
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
GE FANUC PACIS OI V3.X up to V4.6
with Quantum or M580 PLC & EcoSUI EWS with PACIS EcoStruxure Substation Operation user interface
Original brand: General Electric Original brand: AREVA
GE FANUC PACIS OI
Quantum or M580 PLC & EcoSUI EWS PACIS EcoSUI
B ECOFIT™ solution
End of Windows ®
ECOFIT™ solution
End of Microsoft
B
End of
Commercialization commercialization End of full spare parts availability 2000, XP support End of
Commercialization commercialization for Windows® XP commercialization
C C
Main technical characteristics Main technical characteristics and performances
D GE FANUC Quantum or M580 PLC EcoSUI EWS PACiS OI PACIS EcoStruxure Substation Operation user interface D
® ®
IEC 61850 ready No No Yes Windows 2000 or XP Windows 10 (32/64 bits)
Hot-stand by or Multiple IEC 61850 client access points
No Yes N/A One Ethernet network management Multi-LAN through IEC/IEC Gateways
hot-hot solution Direct IEC 61850 configuration by import of SCD file
F F
Asset management N/A N/A Yes
and maintenance display
Language UnityPRO UnityPRO N/A
I Migration to
ECOSUI HMI
• Open to Schneider Electric asset performance and monitoring system
I
J J
K K
G12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G13
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
PSCN3020 HMI PTCC
with EcoStruxure Substation Operation user interface with ADVC 3
Original brand: AREVA Original brand: Schneider Electric
PM106602
PSCN3020 HMI PTCC
EcoStruxure ADVC 3
Substation Operation
B user interface ECOFIT™ solution
B
ECOFIT™ solution End of
Commercialization commercialization End of full spare parts availability
End of Microsoft support
Commercialization for Windows® NT End of commercialization
C C
Main technical characteristics
D PSCN3020 HMI EcoStruxure Substation Operation user interface PTCC ADVC 3 D
® ®
Windows NT4 OS / 2 Windows 10 Design Element
Open to Ethernet IEC 61850 for all future extension and step by step Memory 512 kB 512 MB
One EFIP network management
replacement of bay controllers
Storage 2 MB 1 GB
E Configuration & database generation using proprietary & obsolete software Direct IEC 61850 configuration by import of SCD file for all new extensions
CPU Frequency 22.5 MHz 800 MHz E
Redundancy switch over within 1 mn Hot redundancy seamless switchover
Ethernet N/A 100 Base-T
Handled dataflow up to 3000 MV archived / sec / server, once fully migrated
Handled dataflow limited by EFIP protocol USB N/A USB 2.0
to IEC 61850
F Communication Ports
Ethernet N/A 2 x 100 Base-T F
RS-232 3 2
RS-485 N/A N/A
Typical HMI migration steps by the manufacturer
G Customer site Schneider Electric site What are the benefits?
V23
USB Type B
1
N/A
N/A
1 x USB 2.0
G
• No impact on existing ethernet network, bay controllers, gateways & IEDs,
USB Type A N/A 3 x USB 2.0
as well as electrical drawings or process wiring
DB migration to • Fast implementing without substation shutdown
J J
K K
G14 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G15
www.se.com www.se.com
Distribution Automation and Substation Automation Distribution Automation and Substation Automation
Seefox HMI
with EcoStruxure Substation Operation user interface
Original brand: Schneider Electric
ECOFIT™ proposal
EcoStruxure Substation Operation user interface With ECOFIT™, a true extended life time
C C
E Configuration tools no more supported or with limited upgrade facilities Ready for all standard substation extension using IEC 61850 standard E
Compliant with substation cyber security requirements
F F
I Graphical views
Modernization to I
ECOSUI HMI
J J
K K
G16 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 G17
Digital Power solutions
www.se.com www.se.com
Substation Automation
AccuSine SWP................................................. H3
Varset............................................................... H4
Varlogic............................................................ H5
Gateway......................................................... H13
H
REMEMBER
Full Support
• Technical investigation and assistance for customer issues,
including creation of critical and cybersecurity hotfixes where
deemed necessary by the factory
Limited Support
• Answering questions
• When possible, providing workarounds and fixes that are available
for known problems but no new hotfixes or cybersecurity hotfixes
for new issues
• Provide information on migration to a newer product release that
has Full Support
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H1
www.se.com www.se.com
B B
C Product Release Release date Lifecycle End of Sales date End of Services date New recommended solution
C
phase
AccuSine SWP / SineWave APC 1998 Obsolete 12/2018 12/2026 AccuSine PCSn
(3ph+Ground)
Product Release Release date Lifecycle End of Sales End of Services New recommended solution
D AccuSine PCS (3ph) 1999
phase
Obsolete
date
12/2015
date
12/2023 AccuSine PCS+
AccuSine PCSn 2018 Commercialized
F - All other models with SN prior to October 2010 (WO1010xxxx), are not serviceable and should be replaced • 35° C operating temperature •
•
Building bricks from AccuSine+
Withdrawal of SWP F
Main technical characteristics
G Performances
AccuSine PCS or PFV
- Filtering degree: TDD ≤ 5%
AccuSine PCS+ or PFV+
Vastly improved
G
- Harmonic attenuation factor: 10:1 - Filtering degree: THDi ≤ 3% • SineWave MGE • Refresh project
- Faster dynamic VAR support @ ½ cycle - Harmonic attenuation factor: 20:1 • Primarly used coupled with UPS • SinWave AccuSine SWP
- Faster dynamic VAR support @ ¼ cycle • 2nd to 25th harmonic spectrum • 2nd to 50th harmonic spectrum
• 25° C operating temperature • EMC perf. & 3ph3w enhancements
Heat losses (300A unit) - 400V: 8.3kW - 400V: 5.9kW
H - 480V: 10kW - 480V: 7kW
•
•
Modbus capable
Magelis HMI (2015:17) H
Operational capability Target PF Target THDi or THDv setpoint
Target PF
Optimized PF
Main technical characteristics
Footprint & Modes Wall mounted & Floor standing Reduced footprint from 17% to 41%
I of Installation Chassis, wall mounted
Floor standing AccuSine SWP AccuSine PCSn I
Redundancy Load share only Multi-client/multi-server Performance THDi ≤ 5% THDi ≤ 3%
Client-Server Lower losses 2-level IGBT 3-level IGBT
Load share and make up capacity ≤ 2400W (60A) ≤ 1500W (60A)
J Connectivity to monitoring
systems
EcoStruxure Power ready. Native device driver PME, PQ
Advisor, Com’X510
Modbus RTU or TCP/IP
Operational modes
Smaller footprint (60A wall
Harmonic + PF mitigation Harmonic + PF + load balancing
J
780 x 590 x 325 mm 960 x 440 x 265 mm, wall mount
mount)
Serviceability Modbus TCP/IP Diagnostics via laptop USB to Control Board
Installation type Wall mount Wall mount, Chassis, rack mount
User Interface Key pad interface Larger screen with more information provided
Easier to read with excellent color graphics Operator display Keypad Magelis HMI touchscreen
K Compatibility with AccuSine AccuSine PCS+ is 100% compatible with AccuSine PCS for Operator menu None Built on AccuSine+ platform K
PCS/PFV parallel operations Parallel operation Up to 4 units, same rating Up to 12 units, any rating
Inter-operability with AccuSine Can work in parallel with AccuSine PCS+,
None
PCS+ integratd into EcostruXure Power
H2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H3
www.se.com www.se.com
B B
E E
condensator)
VarPlus Logic VPL6, 2014 Commercialized
Varset direct (fixed) 2006 Obsolete 04/2013 04/2021 VarSet; refer to substitution guide VPL12, Optimum offer
Varset fast 2006 Obsolete 04/2013 04/2021 VarSet Fast or AccuSine; refer to substitution guide
Varset classic 2006 Obsolete 04/2013 04/2021 VarSet "no polluted"
(not polluted)
Main technical characteristics
Varset comfort 2006 Obsolete 04/2013 04/2021 VarSet "low polluted"
VarPlus Logic series
F F
(low polluted)
Varset harmony (poluted) 2006 Obsolete 04/2013 04/2021 VarSet "polluted" Capacitor bank step monitoring Monitoring of all the connected capacitor steps.
Varpact (classic, comfort, 2006 Obsolete 04/2013 04/2021 Varpact R stand alone module (condo, contactor, fuse or CB) Real time power in "kvar" for the connected steps.
harmony) Remaining step capacity per step as a % of the original power since installation.
• Upgradation process: Refer to substitution guides. Replacement of stand alone components may be also possible depending on Derating since installation.
obsolescence date. Number of switching operations of every connected step.
G • Recommended Engineering:
PQ audit or local measurement from point of connection is recommended due to load change condition from first installation.
System Measurement and
monitoring
THD(u) and THD(i) Spectrum 3rd to 19th – Measurement, Display and Alarm.
Measurement of DQ – "kvar" required to achieve target cos phi.
G
• Life time reduction factors: 7 years without maintenance on condensator or operation out of normal operating ranges. Present cabinet temperature and maximum recorded temperature.
• Selection Guide: System parameters – Voltage, Current, Active, reactive and apparent power.
Load variation Compensation Network harmonic pollution level Replacement Solution Large LCD display to monitor real step status and other parameters.
to choose
H H
Easy Commissioning Automatic Initialization and automatic step detection to do a auto commissioning.
Variable or unstable load Automatic No polluted (Gh/Sn ≤ 15 %, Thdu ≤ 3 %; Thdi ≤ 5 %) VarSet Easy for "no polluted network". Automatic wiring correction - voltage and current input wiring correction.
Low polluted (Gh/Sn ≤ 25 %, Thdu ≤ 4 %; Thdi ≤ 10 %) VarSet for "low polluted network". 1 A or 5 A CT secondary compatible.
Polluted (Gh/Sn ≤ 50 %, Thdu ≤ 7 %; Thdi ≤ 20 %) VarSet for "polluted network". Flexibility to the panel builder No step sequence restriction like in the traditional relays.
Stable load Fixed Low polluted (Gh/Sn ≤ 25 %, Thdu ≤ 4 %; Thdi ≤ 10 %) VarSet for "low polluted network". and retrofitting Any step sequences with auto detect. No programming needed.
Polluted (Gh/Sn ≤ 50 %, Thdu ≤ 7 %; Thdi ≤ 20 %) VarSet for "polluted network". Easy to retrofit the faulty capacitor with different power.
H4 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H5
www.se.com www.se.com
A or or
A
or
D D
V, 0 to 63 A kWh, 63A pulse MID PM700, PM700P and PM710 Obsolete 04/2015 PM5100 Type B
ME4 3ph+N Modular Energy Meter, 17070 Obsolete 09/2012 iEM3100 3ph. Energy Merter, A9MEM3100 PM750 Obsolete 04/2015 PM5300 Type B
400 V, 0 to 63 A kWh, 63A
PM810 and PM820 Obsolete 01/2016 PM5500 Type B
ME4zr 3ph+N Modular Energy Meter, 17071 Obsolete 09/2012 iEM3110 3ph. Energy Merter, A9MEM3110
400 V, 0 to 63 A kWh, 63A pulse MID PM850 and PM870 Obsolete 01/2016 PM8000 Type B
ME4zrt 3ph+N Modular Energy Meter, 17072 Obsolete 09/2012 iEM3210 Compteur kWh triphasé A9MEM3210 PM1000, PM1200 Obsolete 12/2016 PM21xx (for countries where PM2200 Type C for PM2000
E E
400 V, 40 to 6000 A TC pulse MID range is launched) range
Acti9, iME3 3ph Modular Energy Meter, 400 A9M17075 Obsolete 09/2012 iEM3100 3ph. Energy Merter, A9MEM3100 PM5100 or PM5110 (for all other Type B for PM5000
V, 0 to 63 A kWh, 63A countries) range
Acti9, iME3zr 3ph Modular Energy Meter, 400 A9M17076 Obsolete 09/2012 iEM3110 3ph. Energy Merter, A9MEM3110 PM5100, 5300, 5500 range 03/2013 Commercialized no plan
V, 0 to 63 A kWh, 63A pulse MID PM8000 03/2015 Commercialized no plan
Acti9, iME4 3ph+N Modular Energy Meter, A9M17070 Obsolete 09/2012 iEM3100 3ph. Energy Merter, A9MEM3100 ION9000 10/2018 Commercialized no plan
400 V, 0 to 63 A kWh, 63A
F Acti9, iME4zr 3ph+N Modular Energy Meter,
400 V, 0 to 63 A
A9M17071 Obsolete 09/2012 iEM3110 3ph. Energy Merter,
kWh, 63A pulse MID
A9MEM3110
ION7300
ION 7330 & ION7350
Obsolete
Obsolete
2016
2016
PM5500
PM8000 F
Acti9, iME4zrt 3ph+N Modular Energy Meter, A9M17072 Obsolete 09/2012 iEM3210 3ph. Energy Merter, A9MEM3210 ION7400 Utility Meter 10/2016 Commercialized no plan
400 V, 40 to 6000 A kWh, CT pulse MID ION8650 Utility Meter 06/2011 Commercialized no plan
EN40 Energy meter 40A 15238 Obsolete 09/2009 iEM2000 Energy meter 40A A9MEM2000 ION8800 Utility Meter 07/2006 Commercialized no plan
G G
EN40P Energy meter 40A, pulse output 15239 Obsolete 09/2009 IEM2010 Energy meter 40A, A9MEM2010
pulse output • Upgradation process: Type A: Different form factor, need to be rewired, different Modbus mapping. Type B: Same form factor, need to be
rewired, different Modbus mapping. Type C: Same form factor, same wiring, different Modbus mapping
• Note 1: ION7550 & 7650 concerned by Phase 1 are those which do not use these features. All Power Meters using one of these features will
Product Release Lifecycle End of Sales and Full Replacement solution Modernization be on phase 2
Release date phase spare parts date process - Current options F and G (current probes / LVCT inputs)
PM200 & PM200Px Obsolete 12/2016 PM2210 or PM2220 (for countries where PM2200 Type C for
- Power supply option C (LVDC)
H H
& PM210 range is launched) PM2000 range
PM5100 or PM5110 (for all other countries) Type B for - Communication options D7 and F1 (Ethernet fiber)
PM5000 range - Security options 3 and 4 (RMICAN)
PM1000, PM1200 Obsolete 12/2016 PM21xx (for countries where PM2200 range is Type C for
- RTU option N9
launched) PM2000 range - I/O options H and P
PM5100 or PM5110 (for all other countries) Type B for • Note 2: Products (PM200, PM2000 and PM5000) are 96mm x 96mm flush mount meters with varying depths
PM5000 range • Note 3: CM4000T, stock available (contact us)
I DM6000, DM6200
PM2200 range 2016
Obsolete
Commercialized
06/2018
no plan
DM6000H & DM6200H • Note 4: ION7550 & 7650, can be repaired, stock available
I
PM2000 2016 Commercialized no plan
iEM 2xxx (worldwide 2011 Commercialized no plan
launch) Main technical characteristics
iEM 3xxx (worldwide 2011 Commercialized no plan
J launch)
PM32xx (xx=00,10, 06/2012 Commercialized no plan Compliance with standards
PMx000, ION9000
Complying with most demanding international metering standards
J
50, 55)
Security 96 mm (3.5”) color display: Simple installation with
EM4200 2017 Commercialized no plan a 30 mm pushbutton hole (reduces arc flash exposure)
EM 4300 wireless 2015 Obsolete 06/2019 PowerTag Rope starting June 2020
energy meter Modular architecture Multiple mounting and communication options: Adaptable to meet the needs of rapidly changing, IoT-enabled electrical
H6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H7
www.se.com www.se.com
B Product Release Release date Lifecycle End of Sales End of full Limited support Modernization
B
phase date support up to up to Solution version
ION-E 6.0 06/2009 Obsolete 03/2012 06/2013 06/2015 PME 2020
SPM 7.0 03/2012 Obsolete 09/2013 06/2015 12/2017 PME 2020
C PME 7.2
PME 8.0
09/2013
06/2015
Obsolete
Obsolete
06/2015
04/2016
12/2016
12/2018
12/2018
12/2020
PME 2020
PME 2020 Product Release Release date Lifecycle End of Sales End of full Limited support Modernization Solution C
PME 8.1 04/2016 Limited Service 04/2017 12/2019 12/2021 PME 2020 phase date support up to up to version
Power Manager 1.0 02/2015 Obsolete 12/2015 12/2018 12/2020 PME 2020 or latest
PME 8.2 04/2017 Limited Service 09/2018 12/2020 12/2022 PME 2020
Power Manager 1.1 12/2015 Obsolete 04/2016 12/2018 12/2020 PME 2020 or latest
PME 9.0 09/2018 Full Service 12/2019 12/2021 12/2023 PME 2020
Power Manager 1.2 04/2016 Limited Service 04/2017 12/2019 12/2021 PME 2020 or latest
D PME 2020 11/2019 Commercialized 12/2022 12/2024
Power Manager 1.3
Energy Expert 2.0
04/2017
08/2018
Limited Service
Full Service
08/2018
12/2020
12/2020
12/2021
12/2022
12/2023
PME 2020 or latest
PME 2020 or latest
D
• Upgradation process:
- Existing database (configuration file) can be extracted directly from the server and communicated to the Technical Support. Energy Expert 3.0 11/2019 Full Service 12/2020 12/2022 12/2024 PME 2020 or latest
- Upgrade tools existing. As the system is usually not redundant, shut down of the current version is recommended.
- Commissioning can be done by Local Field & Services team depending on training level.
• Upgradation process:
E • Recommended Engineering:
- Upgradation must be done by Application Centers or Technical Support teams or EcoXpert.
- Existing database (configuration file) can be extracted directly from the server and communicated to the Technical Support,
- Upgrade tools existing. As the system is usually not redundant, shut down of the current version is recommended.
E
- Workload (engineering work) could be affected in case of customized reports Commissioning can be done by Local Field & Services team depending on training level.
• Limitation scope: In case the Server is not replaced, the existing computer must support Windows® 10 • Recommended Engineering:
• Application case with PSO: Application case of PSO delivered with Advanced Monitoring option (PME): same process but both - Upgradation must be done by Application Centers or Technical Support teams or EcoXpert.
H H
Windows Server 2016, 2019 Standard
SQL Server Versions SQL Server 2012 Express/Standard/Enterprise/Business Intel. SP2
SQL Server 2014, 2016, 2017 Express/Standard/Enterprise/Business Intel.
Browser Firefox, Chrome, Safari, Opera
Office Excel 2013, 2016 and 365
I Possible upgrade paths: PME license upgrade is done by purchasing software assurance.
I
Please, refer to your technical support for more details
Energy Expert
2.0 Software Upgrade
H8 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H9
www.se.com www.se.com
B B
E • Upgradation process:
XD312 110V
230V
50535
50536
Obsolete 12/2018 12/2018 None Not applicable IMDIFL12 A type
E
- Existing database (configuration file) can be extracted directly from the server and communicated to the Technical Support.
380V 50537
- Upgrade tools existing.
- Commissioning can be done by Local Field & Services team depending on training level. XD312-H 50536-H Obsolete 12/2018 12/2018 None Not applicable IMDIFL12H A type
- Redundant HMI is migrated first and refreshed, therefore, no Shutdown is required. XL308 110V 50606 Obsolete 12/2018 12/2018 XL316 C type IMD-IM400 + IMDIFL12MC A type
F Additional details around upgrades can be found in Upgrade section of PSO 9.0 or PS0 2020 System Guide.
• Recommended Engineering:
230V
380V
50607
50608
F
System upgrade should be done by Application Centers or Technical Support teams or EcoXperts XL316 110V 50615 Service 12/2018 2026 XL316 C type IMD-IM400 + 2x IMDIFL12MC B type
• Limitation scope: In case the Server is not replaced, the existing computer must support following Operating Systems: 230V 50616
380V 50617
Power SCADA Operation version
G Operating System
Windows Server 2019
2020
9.0 8.2
-
8.1
- -
8.0
-
7.4
-
XM300C 110V
230V
50540
50541
Service 12/2018 2026 XM300C C type IMD-IM400 A type
G
Windows Server 2016 - - - 380V 50542
Windows 10 4 1 2 - XML308 110V 50490 Obsolete 12/2018 12/2018 XML316 C type IMD-IM400 + IMDIFL12MC A type
Windows Server 2012 R2 3 - 230V 50491
H H
Windows 8.1 - - 3 - 380V 50492
Windows Server 2012 - XML316 110V 50322 Service 12/2018 2026 XML316 C type IMD-IM400 + 2x IMDIFL12MC A type
Windows Server 2008 R2 - - 230V 50323
Windows 7 - 380V 50324
Windows Server 2008 - - - - - XLI300 115V 50515 Service 12/2018 2026 XLI300 C type No replacement needed IMD Not applicable
230V 50516 and IFL are Modbus RS485
I (1) Available with 8.1 update 6 or later. (2) Available with 8.0 service release 1 update 3 or later. (3) Available with 8.0 service release 1.
(4) Requires Windows 10 version 1607 and later (64 bit only).
XTU300
380V
110V
50517
50545 (3) Service 12/2018 2026 XTU300 C type No replacement needed IMD Not applicable
I
Note: as of May 2018, Power Scada Anywhere is only supported on Windows Server 2012 R2 and Windows 2008 R2.
230V 50546 and IFL are Modbus RS485 +
PLC to manage inhibition
380V 50547
• Application case with Advanced Monitoring views:
Application case of PSO delivered with advanced monitoring (PME): same process but both software need to be upgraded
J • New release advantages:
For complete details on reasons to upgrade, please contact us
• Upgradation process:
- Type A: Different form factor, need to be rewired, different register mapping
J
- Type B: Same form factor, need to be rewired, different register mapping
• Possible upgrade paths: Please, refer to your technical support for more details - Type C: Same form factor, need to be rewired, same register mapping.
• Note 1: For all EoL references, no repair is possible. A stock of devices has been constituted to replace on-field defective products.
No extension nor new projects are possible with products from the EoL stock.
K • Note 2: Schneider Electric has managed to have a security stock of manufactured products. Please, check with your local Field & Services
representative or through SPEED application the real time available stock.
K
PowerLogic PowerSCADA PowerSCADA PowerSCADA PSO 9.0,
Older than PowerSCADA PowerSCADA
7.20 SR1 SCADA Expert 7.30 Expert 7.40 Expert 8.0 Expert 8.1 Expert 8.2 Resp. • Note 3: These Power Supply values are no more available as spare parts. Select the 230V model, associated with an interface transformer.
7.20 SR1 and 7.30 SR1 and 7.40 SR1 and 8.0 SR1 PSO 2020
• Main technical characteristics: Refer to VigilOhm catalogue 2019.
Special considerations for advanced reporting and Dashboard module
H10 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H11
www.se.com www.se.com
A A
or
C C
Commercial Part Lifecycle End of End of Replacement Modernization Description Description of
name Number Phase Sales date Services date solution process of original replacement
device device Product Release Lifecycle End of End of Services Replacement Modernization process
MR 621 772-000-00-1 Service 06/2021 Not confirmed yet IMD-IM20 Retrofit Release Date Phase Sales date date solution
F MR 627C
Microprocessor
775-000-20-010 Service
MR627
06/2021 Not confirmed yet IMD-IM400 Retrofit Smartlink SIB
Link 150
Commercialized
Commercialized
03/2022 (Note 3) 03/2024 (Note 2)
H12 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 H13
Achieve higher sustainable
www.se.com www.se.com
Sustainability offers
a Green Premium™ service Green Premium stands for our commitment to deliver customer valued
sustainable performance. It provides our customers with healthier products
and superior transparency on material content, regulatory information and
the environmental transparency on material content, regulatory information
and the environmental impact of our products.
It has been upgraded with recognized environmental claims and extended
to cover all offers including Products, Services and Solutions. Green A
Premium brings improved resource efficiency throughout an asset’s
lifecycle. This includes efficient use of energy and natural resources,
along with the minimization of CO2 emissions.
We’re helping our customers optimize the total cost of ownership their
assets. To do this, we provide IoT-enabled solutions, as well as upgrade,
B
repair, retrofit, and remanufacturing services.
Green Premium products are RoHS and REACh compliant. We’re going
beyond regulatory compliance with step-by-step substitution of certain
materials and substances from our products.
C
Green Premium delivers strong value propositions through third-party
MasterPact MTZ, a Green Premium product used labels and services. By collaborating with third-party organizations we can
D
for ECOFIT™ service.
support our customers in meeting their sustainability goals such as green
building certifications.
Resource
performance
Circular
performance
Well-being
performance F
Our retrofit service is Our retrofit service Our upgraded
helping you to reduce is giving you an equipment is made
your energy and carbon option with less with less toxic materials
Sustainability offers
Complementing ECOFIT™, SF6 Recovery Services
the sustainability offer is our environmental treatment package
D
Get help
with SF6 gas disposal thanks to 2 Material sorting
Recycling of metals and
other components parts
1 E
SF6 Recovery Services Offer Equipment
collection
H
4 Certificate
of destruction
I
3 Recovery and recycling
of SF6 gas or oil
when applicable
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 I3
Maximize your electrical system
www.se.com www.se.com
Complementary Services
Consulting Services
uptime and performance
Your electrical system is one of the most important parts
of your operation.
Schneider Electric Services:
MPS Consulting Services
Your partner for electrical system
operation and workplace safety. MPS stands for Modernization, Performance, and Safety. Those three
A
Our subject-matter experts on goals are at the heart of what we deliver for your electrical system.
electrical distribution can offer Our consulting portfolio is designed to offer you the right level of depth
and analysis for your site so that you can focus on your core mission.
B
you comprehensive, cost-effective
solutions to help you optimize We help you prevent unplanned outages and minimize safety
the reliability and safety of your risks by understanding the life-cycle and operating conditions
power system. of your critical electrical assets, employing effective maintenance
& management practices, and intelligently modernizing equipment
where necessary. C
A good first step before a modernization project is to assess
the safety, lifecycle and operation of your electrical installation.
€10 billion
annual industrial losses due to
D
power disruptions in Europe
100+
consulting experts worlwide
F
G
3 000+
assessments delivered worldwide H
with consistent expertise tools,
and deliverables
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 J1
Training your team part
www.se.com www.se.com
Complementary Services
Training
of the answer...
90% of unexpected events in a Grow your staff’s electrical safety, operation &
network, such as power outages,
accidents, and near misses,
maintenance competencies to:
are caused by human error! • Enable your team members to make the right decision in their daily
A
operations and in case of unexpected events
• Protect your people
• Mitigate risks of accident
61+
• Avoid downtime and damages
• Enhance on-site technical skills and safety level B
training locations worldwide • Save time and costs
• Manage Capex
Thanks to C
350+
Online competency assessment and e-Learning offer: optimize
your teams technical skills and safety installation performance with our
1 400+
virtual working situations and practice the correct response so
that they are able to make the right decision automatically,
by duplicating your own electrical installation with them.
equipment and process specific Certified trainers: benefit from technical specialists as well as
F
courses to choose from experienced educators; hands-on training with full size equipment.
44 000+
active e-Learners
G
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 J3
Legacy range /brand from
www.se.com www.se.com
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 K1
www.se.com www.se.com
A A
Alstom, AREVA MIDOS MRSU05 MV Switchgears Protection (1989-2004) Merlin Gerin KA/KD MV Other Contactors Air (1958-1972)
Alstom, AREVA PSEL, PSET MV Switchgears Protection (1985-2006) Merlin Gerin Lamisec MV Indoor Disconnectors & Switches (1960-1980)
Alstom, AREVA TROPIC MV Switchgears Protection (1975-1999) Merlin Gerin MCC MODEL 2, 3, 4, 5 LV panels (1950-1960, 1960-1970, 1970-1980, 1980-1995)
Alstom, AREVA DAX-I MV Switchgears Protection (2000-2015) Merlin Gerin Mecabloc LV panels (1959-1974)
Alstom, AREVA FLUOPACK MV Switchboards GIS (1998-2006) Merlin Gerin Motorstart P12/30, P12D/P30D MV Switchboards AIS (1960-1980)
CEM AMB MV Switchboards AIS (1958-1965) Merlin Gerin Murbloc LV panels (1962-1974)
CEM AV MV Other Circuit breakers Air (1950-1960) Merlin Gerin OB1 MV Oil Circuit Breakers (19xx-1990)
B CEM
CEM
CEM
CHT
DNG6
FJ
MV Other Contactors Air (1960-1976)
MV Switchboards AIS (1969-1980)
MV Oil Circuit Breakers (1953-1973)
Merlin Gerin
Merlin Gerin
Merlin Gerin
P400
P6, P12
POWER ZONE 2, POWER ZONE 3
100- LV Capacitors (19xx-2006)
LV panels (1974-1995, 1972-1982)
LV panels (1960-1985, 1985-2001)
B
CEM FLUOMATIC F500, F900, NF500 MV Switchboards AIS (-, 1978-1987, 1975-1987) Merlin Gerin POWERPACT N/P_Frame LV Molded Case Circuit Breakers (1980-2008)
CEM FR MV SF6 Circuit Breakers (1970-1985) Merlin Gerin Pragma C, D, F LV panels (19xx-2002, -2003, -2003)
CEM FRAD MV SF6 Circuit Breakers (1961-1980) Merlin Gerin Prebloc LV panels (1949-1974)
CEM FRUR 620, 640 MV SF6 Circuit Breakers (1972-1985) Merlin Gerin Propivar generation1, Propivar generation2 MV Capacitors (1985-1997, 1997-2001)
C CEM
CEM
HF
KIT 23, 25, 26, 27, 28, 36
MV SF6 Circuit Breakers (1980-1984)
MV Switchboards AIS (1965-1969, 1969-1978, 1981-1987, 1981-1987, 1981-1984,
1981-1987)
Merlin Gerin
Merlin Gerin
Merlin Gerin
RCV-420
Reactivar
Rectibloc
MV Swithgears Protection (1993-2007)
MV/LV Capacitors (1993-2017)
LV Capacitors (19xx-2006)
C
CEM MAGNETOR MV Other Circuit breakers Air (1950-1965) Merlin Gerin Rectimat, Rectimat 2 LV Power factor correction (19xx-1999, 19xx-2006)
CEM NDB7 MV Switchboards AIS (1964-1980) Merlin Gerin Ringmaster RN1.5, RN2.0 MV Switchboards GIS (1986-1991, 1991-1999)
CEM NDS1/NDS2 MV Switchboards AIS (1964-1980) Merlin Gerin RM6 MV Switchboards GIS (1983-1988)
CEM NORMABLOC DN, DNL, DNT MV Switchboards AIS (1964-1972, 1969-1980, 1964-1972) Merlin Gerin RNS11 MV Switchgears Protection (1995-2007)
D CEM
CEM
CEM
NORMABLOC DNV 4, 5, 5/2B MV Switchboards AIS (1986-????, 1992-xxxx, 1987-xxxx)
NORMABLOC N10, N100, N1100, N160, N300, N964 MV Switchboards AIS (1950-1958, 1958-1971, 1969-1973, 1958-1971)
NORMABLOC NC3T MV Switchboards AIS (1964-1972)
Merlin Gerin
Merlin Gerin
Merlin Gerin
ROLLARC R100/R200
Rotabloc_MDA
Secovar, Secomat
MV SF6 Contactors (1974-1984)
LV panels
LV Capacitors (19xx-1988, 19xx-1999)
D
CEM NORMABLOC ND MV Switchboards AIS (1957-1965) Sepam 15, Sepam 1000, Sepam 100LA, Sepam
Merlin Gerin MV Switchgears Protection (1985-1997, 1993-2001, 1995-2016, 1995-2018)
CEM NORMADIS SERIE C, D MV Switchboards AIS (1970-1973, 1969-1973) 100LD/100RT
CEM NORMADIS SERIE N 500 MV Switchboards AIS (1967-1970) Merlin Gerin ST (COMPACT C) 081- LV Switchgear Protection (19xx-19xx)
MV Switchboards AIS(1971-1972, 1972-1981, 1977-1982, 1965-1968, 1968-1971, Merlin Gerin T12 LV panels (1972-1980)
E E
CEM NORMAFLUOR DNF 23, 24, 35, 370, 430, 500
1977-1985) Merlin Gerin Taillefer 900/1080 MV Switchboards AIS (1965-1974)
CEM NORMASEPT N700, N1700 MV Switchboards AIS (-, 1970-1978) Merlin Gerin TD8, TD9 LV panels (1969-1979, 1980-1994)
CEM SERIE 2F MV Switchboards AIS (1982-1984) Merlin Gerin TDI, TMD, TMI LV panels (1975-1995)
CEM SFC MV SF6 Contactors (1976-1987) Merlin Gerin TDS LV panels (1980-1995)
CEM VC TOYO MV Vacuum Contactors (1974-1981) Merlin Gerin Temeg MV Switchboards AIS (1965-1974)
CEM, Delle Alsthom, GEC-Alsthom, Alstom FLUOKIT C24 MV Switchboards GIS (1987-2002) Merlin Gerin Thyrimat LV Capacitors (19xx-2006)
CEM, Delle Alsthom GF, GF2 MV SF6 Contactors (1980-1988, 1962-1970)
F F
Merlin Gerin TLC11MS MV Switchgears Protection
CEM, Delle Alsthom, GEC-Alsthom FI MV Oil Circuit Breakers (1984-1990) Merlin Gerin TM, TD, TM7 LV panels (1967-1995, -1995, -1994)
CEM, Delle Alsthom, GEC-Alsthom, Alstom FBA MV Switchboards GIS (1987-2003) Merlin Gerin TMG LV panels (1963-1966)
Concordia Sprecher, Alstom PG-100 MV Switchboards GIS ( 19xx-2001) Merlin Gerin Turbovar LV Capacitors (19xx-2006)
Concordia Sprecher, Sprecher & Schuh Alstom HV, HVEW, HVW, HVTW MV Vacuum Circuit Breakers (1993-2001) Merlin Gerin UNELEC CNP LV Circuit Breakers (1968-1986)
Delle Alsthom Fluomatic F943 MV Switchboards AIS Merlin Gerin V23/V60, V500/V700 MV Switchboards AIS (1960-1974, 1966-1980)
Delle Alsthom MESURISOL MC4, MESURISOL PL2 MV Switchgears Protection (1975-1999) Merlin Gerin Varpact LV Capacitors (2006-2013)
G G
Delle Alsthom VB, VC, VD MV Vacuum Contactors (199x-2001) Merlin Gerin Varplus 2 LV Capacitors (19xx-2013)
Delle Alsthom, Alstom CX MV SF6 Circuit Breakers (1976-1982) Merlin Gerin Varplus M LV Capacitors (19xx-2006)
Delle Alsthom, GEC-Alsthom BS MV SF6 Circuit Breakers (19xx-1993) Merlin Gerin Varset Direct LV Capacitors (19xx-2013)
Delle Alsthom, GEC-Alsthom, AREVA Normasept N743 MV Switchboards AIS (19xx-1981) Merlin Gerin VIGIRACK, VIGIRACK_Nuclear MV Swithgears Protection (1960-1996, 1990-2015)
Delle Alsthom-GEC-Alsthom, Alstom 20CB MV Outdoor Disconnectors & Switches (1988-1998) Merlin Gerin VIP 11, 11R/12R, 13/17, 200- 201 MV Switchgears Protection
Delle Alsthom, Alstom DIMAX MV Switchgears Protection (1975-1999) Merlin Gerin Visibloc LV panels (1968-1974)
Delle Alsthom, Alstom EPAC MV Switchgears Protection (1990-2003) Merlin Gerin Visucompact CM LV Molded Case Circuit Breakers (1981-2002)
H H
Delle Alsthom, Alstom HV400 MV Vacuum Circuit Breakers (1993-2001) Nulec, AREVA PTCC, ADVC1 Teleconduite MT (1999-2007, 2001-2011)
Delta H96 MV Switchboards AIS (19xx-1998) OBSAD - SAD CSI MV Oil Circuit Breakers
GEC MX36 MV Vacuum Circuit Breakers (1974-1981) Sachsenwerk, AEG A, D, F, G MV Oil Circuit Breakers (19xx-1990)
GEC-Alsthom MX51, MX81 MV Vacuum Circuit Breakers (1974-1981) Sachsenwerk, AEG BT (CS0) MV Oil Circuit Breakers (1965-1980)
GEC-Alsthom-Alstom FBE, FBT MV Switchboards GIS (1991-2003) Square D FC MV SF6 Circuit Breakers (1975-1988)
Long & Crawford, GEC-Alsthom J, J2, J3, J4 MV Vacuum Circuit Breakers (1958-2003) Square D POWER STYLE QED3, QED4 LV panels (1985-2004)
Magrini DH, DHE, DHF, DHM MV Other Circuit breakers Air (19xx-1969 , 1969, 1997, 1969) VEB, Otto Buchwitz CSIM 1-12, CSIM 3-12, CSIM 3-24 MV Switchboards AIS
I Magrini
Magrini
Magrini
DISTRIVAN B, C
F (CS4)
FS
MV Switchboards AIS
MV Switchboards AIS (1970-1980)
MV Other Circuit breakers Air (1969-1997)
VEI, AREVA
Sachsenwerk, AEG
Square D
ISARC (Old version)
BT
POWER STYLE QED3, QED4
Inter et Sectionneurs Interieur MT (19xx-2006)
MV Oil circuit breaker (1965-1980)
LV panels (1985-2004)
I
Magrini Multiclad LV panels (19xx-1975) Square D FC MV SF6 circuit breaker (1975-1988)
Magrini, VEI GIE generation1, GIE generation2 MV SF6 Circuit Breakers (1987-1991, 1992-1995) Square D MULTIFORM LV Circuit breaker (till 1981)
Merlin Gerin 36BX MV Switchboards AIS (1979-1988) Square D SE LV Circuit breaker (1983-2003)
Merlin Gerin B Control LV Circuit Breakers (1972-1990) Square D VAD2, VAD3 MV Vacuum circuit breaker (1985-1995)
J Merlin Gerin
Merlin Gerin
Biovar
Canalis KB, KJ, KLA, KM, KR, KU, KX
MV Capacitors (1978-1985)
LV panels (1975-1998, 1966-1997, 1982-1995, 1962-1983, 1971-1984, 1964-1984,
1971-1981)
Télémécanique
VAMP
VEB, Otto Buchwitz
TMG
V57
BSIG – 10, BSIG-20
LV panels (1963-1966)
MV Switchgears Protection (20xx-2019)
MV Switchboards AIS
J
Merlin Gerin Chamrousse MV Switchboards AIS (1968-1974) VEB, Otto Buchwitz CSIM 1-12, CSIM 3-12, CSIM 3-24 MV Switchboards AIS
Merlin Gerin CI, DC, DCR LV Circuit Breakers (1950-1966) VEI, AREVA ISARC (old version) 061- Inter et Sectionneurs Interieur MT (till 2006)
Merlin Gerin CM14 LV panels (1972-1988)
Merlin Gerin Compact CM LV Molded Case Circuit Breakers (1981-2002)
K Merlin Gerin
Merlin Gerin
Merlin Gerin
COQ
DB 33 Marine
Dialpact
MV Switchboards AIS (1954-1968)
LV Circuit Breakers (1993-1998)
LV Circuit Breakers (1993-1999)
K
Merlin Gerin DSExxK, DSExx / SOLENARC Disjoncteurs MT Autres Air (1971-1988, 1972-1988)
Merlin Gerin DSG LV Circuit Breakers (1950-1966) Please contact your local Services sales department to know more on modernization
Merlin Gerin DSL LV Circuit Breakers (1983-1998)
Merlin Gerin Equipunit LV Capacitors (19xx-1980) solution for those obsolete ranges
K2 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 K3
ECOFIT reference centers
™ www.se.com www.se.com
AREVA 3 3 3 3
Alstom 3 3
A
CEM 3
DELLE 3
AEG 3
Sprecher +
Schuh
3 B
Concordia
3
Sprecher
VEM 3 C
GEC 3
GEC
Alsthom
3 3
D
AEI 3
3 3
E
3
3 F
3
Competitors** 3 3 3 3 3 3 3
* Not current ECOFIT™ reference centre
** ABB, Ansaldo, General Electric, Otto Buchwitz, VEB, Westinghouse, Siemens...
G
J
ECOFIT™ Reference Centers are in charge of:
• Design and development of ECOFIT™ offers using Schneider Offer Creation
Process methodology.
• Industrialise, manufacture and optimise ECOFIT™ solutions to address
K
customers’ requests with optimum conditions.
• Testing, validation and certification of ECOFIT™ solutions using a standard
quality directive procedure linked to international standards.
Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 K5
www.se.com www.se.com
Notes Notes
K6 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 Medium & Low Voltage Distribution - Modernization of switchboards - ECOFIT™ 2021 K7
Schneider Electric Industries SAS
06-2021