You are on page 1of 4

‫المملكة العربية السعودية‬

Kingdom of saudi arabia


Ministry of Education ‫وزارة التعليم‬
University of Dammam ‫جامعة الدمام‬

‫اقسام الطالبات بالمدينة الجامعية‬


UNIVERSITY OF DAMMAM - GIRLS CAMPUS

‫مالحظة تصميميه عن تضغيط المصاعد‬

  Design Note for Elevator Pressurization
 

NOVEMBER 2015 ‫ ھـ‬1437 ‫محرم‬

MOHAMED AL SABEG ‫محمــد الســابق‬


CONSULTING ENGINEERS ‫مھندسـون أستشـاريون‬

11461 : ‫الرياض‬ 2713 :‫ب‬.‫ص‬


P.O.Box: 2713, Riyadh 11461

SHAKER CONSULTANCY ‫المجموعة االستشارية شاكر‬


GROUP
 
 
 
Design Note for Elevator Pressurization. 
The design approach NFPA 92A, item 4.3 for smoke-control systems shall be one or a
combination of the following:

(1) Stairwell pressurization 
(2) Zoned smoke control 
(3) Elevator smoke control 
(4) Vestibules 
(5) Smoke refuge areas. 

From the above it is mentioned that smoke control of a building can be one or a 
combination of the all of them. From our HVAC point of view, we have applied items 
number one and 2 where we have stair well pressurization and zoned smoke control as 
indicated in the other attachments, therefore no need to apply the Elevator 
pressurization as well to avoid having many interacting systems in the same tine in case 
of fire. 

In addition as per NFPA 92A, item A.5.4. Several methods of correcting the issue of stack effect 
and elevator pressurization have been proposed and investigated. These methods include the 
following: 

(1) Exhaust of the fire floor 
(2) Pressurization of enclosed elevator lobbies 
(3) Construction of smoke‐tight elevator lobbies 
(4) Pressurization of the elevator hoist way 
(5) Closing of elevator doors after automatic recall 

In our project we applied from the above number (1) as we have a dedicated smoke 
extraction / exhaust from the fire floor in addition to that closing of elevator doors after 
automatic recall can be considered during the programming of the elevators operation. 
Taking into considerations that the buildings of the project are not high rise buildings, 
they are all of the low rise ones since the maximum floor levels are 5 including the Roof 
level. 

 
Dammam University  Rev 0|Design Note For  Elevator  1 
Pressurization 
 
 
 

You might also like