01. DC SUPPLY:-The panel wiring shall be made considering a single source of 110V DC battery
but two independent protection DC circuits to be wired by providing separate DC fuses in such
a way that even with the availability of one set of protection fuses C.B. tripping should take
place. Separate Bay Control Unit for Line Bay & Transformer bay are to be considered.
02. DC FAIL INDICATION:- One No. DC fail relay energizing an AC bell shall be provided for
monitoring the DC supply to the protection circuit. The DC fail relay should have a reverse flag.
03. P.T.SUPPLY:- The panel shall be wired for a set of 132 KV PTs having metering and
protection cores.
1. PROTECTIONS AND CONTROL PROVIDED IN THE PANEL:-
a) Numerical Differential Relay:
i) A two winding numerical differential relay shall be provided. The operating time of the relay
should be less than 30 ms. The relay shall be suitable for display of load current and fault data
through a HMI.
ii) It shall have an adjustable bias setting range and dual bias slope.
iii) It shall be stable under severe through fault condition.
iv) It shall be suitable for rated current of 1 Amp.
v) It shall be IEC: 61850 compliant.
vi) The exact model of the offered relay shall be finalised at the time of the engineering based
on the requirement of protection scheme and it shall be binding on the contractor.
vii) It shall have internal feature in the relay to take care of the angle & ratio correction.
viii) It shall have second, fifth and higher harmonic and other inrush proof features and should
be stable under normal over fluxing conditions. Magnetising inrush proof feature shall not be
achieved through any intentional time delay e.g use of timers to block relay operation
ix) It shall have an operating current setting of 15% or less. Shall have settable operating
current setting.
xvii) The relay shall have a disturbance recording feature to record graphic form of
instantaneous values of current in both the windings in analogue channels, operate current,
restraining current and voltages in separate analogue channels, during faults and disturbances
for the pre fault and post fault period. The disturbance recorder shall have the facility to record
the following minimum external digital channel signals apart from the digital signals pertaining
to differential relay.
1. REF protection operated ( HV and LV)
2. HV breaker status
3. LV breaker status
4. Bucholtz /OLTC Bucholz alarm and Trip ; PRD trip
5. WTI/OTI alarm/trip of transformer
The Relay shall be suitable for : i. CT secondaries : 1A ii. PT Secondary: - 110V iii. DC auxiliary
supply: - suitable for 110V DC nominal iv. System earthing: - solidly grounded v. Max. Ambient
temperature: - 55 degrees centigrade Necessary hardware and software for down loading the
data captured by disturbance recorder to the workstation computer in the substation shall be
included in the scope.
b) Numerical Back-up Over Current and Earth fault (Directional) protection scheme with high
set feature; It shall be IEC 61850 compliant. It shall have continuous self-monitoring and
diagnostic features. It shall have a trip value recorder feature to record instantaneous fault
values of current & voltage. It shall have oscillographic disturbance recording feature facility.
It; (i) Shall have three over current and one earth fault element(s)
(ii) The scheme shall include necessary VT fuse failure relays for alarm purpose
(iii) Shall have freely configurable 4 nos each of input and output contacts. Shall have a
minimum of four nos LEDs for indications.
(iv) Over current relay shall have multiple characteristic including a directional IDMT
characteristic with a definite minimum time of 3.0 seconds at 10 times setting and have a
variable setting range of 50-200% of rated current have low transient, over reach high set
instantaneous unit of continuously variable setting range 200-2000 % of rated current have a
variable selectable characteristic angle
(v) Earth fault relay shall have multiple characteristics (including a directional and
nondirectional IDMT definite minimum time of 3.0 seconds at 10 times setting) and have a
variable setting range of 0.20-3.0 times of rated current. have low transient, high set
instantaneous unit of continuously variable setting .
(vi) It shall have power and energy measurement facility. Shall also have measurement facility
of instantaneous voltage and currents on HMI.
(vii) It shall have at least two setting groups
(viii) Shall have negative sequence over current feature also.
(ix) The O/C and E/F relay shall have disturbance recording capability and event logger. It should
display at least previous five fault data on HMI on demand.
(x) The relay model shall be Micom /Siemens /Schneider/ABB or higher version or equivalent
model of approved make of relay. The exact model of the offered relay shall be finalised at the
time of the engineering based on the requirement of protection scheme of and it shall be
binding on the contractor. All the Relays must be SCADA Compatible .
c) Transformer body protections:- A total of 08 Nos. self reset type heavy duty tripping relays
with operating time less than 12 ms having indicating flags shall be provided for the following:-
d) O.T.I. Alarm.
e) Low SF6 Alarm.
f) Low Air pressure alarm.
g) Low SF6 CB Lock out
h) Low Air Pressure CB Lock out
iii A 24-window facia enunciator with following inscription shall be provided on the front with
audible DC alarm bell. The make shall be Alan Electronics systems (P) Ltd, Bombay / Bharni.
iv Breaker indication:-
Separate breaker ON – OFF lamp indication shall be provided in addition to CB semaphore
indications.
1. Differential Protection Trip Differential Relay
2. Back Up Trip Over Current / Earth Fault
3. Over Load Trip Over Load Trip Timer
18. Low Air Pressure Alarm Auxiliary Relay For Low Air Pressure Alarm
19. SF6 / Air Pressure Low Trip Block Auxiliary Relay For SF6 / Air Pressure Low Trip Block
20. Trip Circuit-1 Fail TCH Relay Coil 1
21. Trip Circuit-2 Fail TCH Relay Coil 2.
22. Differential Relay Faulty From Differential Relay Supervision Contact
23. IDMT Relay faulty From Numerical IDMT Relay Supervision Contact
24. Spare ---
v Mimic diagram:- It is not necessary for the manufacturer to match the other details of the
switch yard. The standard mimic diagram of single main feeding the x-mer is sufficient.
The CT & PT circuit wires should be colour coded i.e. red, yellow, blue and black for three
phases and neutral respectively. The DC and control wires should be grey. The cable size shall
be 2.5 mm2 for CT & PT and 1.5 mm2 for control circuit. However, for tripcircuit, white wires
should be used & it shall be 2.5 Sq. mm
GENERAL:- Terminal connectors for control and other circuits shall be of stud type. For CT & PT
circuits the terminal connectors shall be of best quality disconnecting type. The terminal
connector size shall be 16A current rating. The DC circuit wires shall be grey of size of 1.5 Sq.
mm. However, for trip wires shall be of 2.5 Sq. mm size.