Internal Use Only

http://biz.lgservice.com

System
Indoor Unit R410A
SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series

CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Air Conditioner Service Manual

TABLE OF CONTENTS
Safety Precautions............................................................................................................................3
Part 1 General Information.............................................................................................................10
Model Names .............................................................................................................................11
External Appearance .................................................................................................................12
Nomenclature .............................................................................................................................15

Part 2 Indoor Units.......................................................................................................................7


Ceiling Mounted Cassette Type (1 way) ........................................................................................8
Ceiling Mounted Cassette Type (1 way)(Art type) .......................................................................13
Ceiling Mounted Cassette Type (2 way) ......................................................................................19
Ceiling Mounted Cassette Type (4 way)(1)..................................................................................24
Ceiling Mounted Cassette Type (4 way)(2)..................................................................................29
Ceiling Mounted Cassette Type (4 way)(3)..................................................................................36
Art Cool Type(Mirror) ...................................................................................................................42
Art Cool Type(Gallery) .................................................................................................................53
Ceiling Concealed Duct Type (Low static) ...................................................................................63
Ceiling Concealed Duct Type (Built in) ........................................................................................70
Ceiling Concealed Duct Type (High static) ..................................................................................76
Wall Mounted Type ......................................................................................................................85
Ceiling & Floor Ceiling Suspended ..............................................................................................98
Floor Standing Type...................................................................................................................105

Part 3 Trouble shooting guide...............................................................................112

Copyright ©2014 LG Electronics. Inc. All right reserved. -2-


LGE Internal Use Only
Only for training and service purposes
Part 1
General Information

1. Model Names .............................................4

2. External Appearance .................................5

3. Nomenclature .............................................6

Copyright ©2014 LG Electronics. Inc. All right reserved. -3-


LGE Internal Use Only
Only for training and service purposes
Model Names

1. Model Names
Capacity(Btu/h(kW))
Category Chassis
Name 5k 7k 9k 12k 15k 18k 21k 24k 28k 36k 42k 48k 54k 76k 96k
(1.5) (2.2) (2.8) (3.6) (4.5) (5.6) (6.4) (7.1) (8.2) (10.6) (12.3) (14.1) (15.8) (22.4) (28)
SE ARNU07 ARNU09 ARNU12 ARNU15
GSE*2 GSE*2 GSE*2 GSE*2
Wall Mounted ARNU18G ARNU24G
S5
S5*2 S5*2
(General)
ARNU05 ARNU07 ARNU09 ARNU12 ARNU15
SB
GSBL2 GSBL2 GSBL2 GSBL2 GSBL2
SC ARNU18 ARNU24
GSCL2 GSCL2
ARNU07 ARNU09 ARNU12 ARNU15
SE
Mirror GSE*2 GSE*2 GSE*2 GSE*2
ART COOL ARNU18 ARNU24
S3
GS3*2 GS3*2
ART Cool ARNU07 ARNU09 ARNU12
SF
Gallery GSF*2 GSF*2 GSF*2
TJ ARNU07 ARNU09 ARNU12
GTJ*2 GTJ*2 GTJ*2
1 Way ARNU07 ARNU09 ARNU12
TU
GTU*2 GTU*2 GTU*2
ARNU18 ARNU24
TT
GTT*2 TT*2
ARNU18 ARNU24
2 Way TL GTL*2 GTL*2
ARNU07 ARNU09 ARNU12 ARNU15 ARNU18
Ceiling TE GTE*2 GTE*2 GTE*2 GTE*2 GTE*2
Cassette ARNU05 ARNU07 ARNU09 ARNU12
TR
TR*2 TR*2 TR*2 TR*2
ARNU15 ARNU18
TQ TQ*2 TQ*2
4 Way
ARNU24G ARNU28G
TP
TP*2 TP*2
ARNU36
TN
GTN*2
TM ARNU42G ARNU48G
TM*2 TM*2
BH ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24
GBHA2 GBHA2 GBHA2 GBHA2 GBHA2 GBHA2
ARNU12 ARNU15 ARNU18 ARNU24 ARNU28 ARNU36 ARNU42
BG
High GBGA2 GBGA2 GBGA2 GBGA2 GBGA2 GBGA2 GBGA2
Static ARNU18 ARNU24 ARNU28 ARNU36 ARNU42 ARNU48 ARNU54
BR GBRA2
GBRA2 GBRA2 GBRA2 GBRA2 GBRA2 GBRA2
ARNU36 ARNU42 ARNU48 ARNU76GB8 ARNU96GB8
Ceiling B8
GB8A2 GB8A2 GB8A2 A2/D2 A2/D2
Concealed
ARNU07 ARNU09 ARNU12 ARNU15
Duct B1
GB1G2 GB1G2 GB1G2 GB1G2
ARNU18 ARNU24
B2
GB2G2 GB2G2
Low Static ARNU05 ARNU07 ARNU09
L1 GL1G2 GL1G2 GL1G2
ARNU12 ARNU15 ARNU18
L2
GL2G2 GL2G2 GL2G2
ARNU21 ARNU24
L3
GL3G2 GL3G2
ARNU07 ARNU09 ARNU12 ARNU15
B3
GB3G2 GB3G2 GB3G2 GB3G2
Built In
B4 ARNU18 ARNU24
GB4G2 GB4G2
ARNU09G ARNU12G
Ceiling & Floor VE VEA2 VEA2
ARNU18 ARNU24
Ceiling Suspended VJ GVJA2 GVJA2
ARNU07 ARNU09 ARNU12 ARNU15
CE
GCEA2 GCEA2 GCEA2 GCEA2
With Case
ARNU18 ARNU24
CF
Floor GCFA2 GCFA2
Standing ARNU07 ARNU09 ARNU12 ARNU15
CE GCEU2 GCEU2 GCEU2 GCEU2
Without
Case ARNU18 ARNU24
CF
GCFU2 GCFU2

h *ART COOL- B: Blue, M:Metal, D:Wood, R:Mirror, W:White Wood, V:Silver, E:Red, G:Gold, 1: Kiss (Photo changeable)
*Wall Mounted- A: Basic, L:Plasma
*Ceiling Cassette- A: Basic, C:Plasma

Copyright ©2014 LG Electronics. Inc. All right reserved. -4-


LGE Internal Use Only
Only for training and service purposes
External Appearance

2. External Appearance
Ceiling Cassette- 1Way Ceiling Cassette -2Way
ARNU07GTJ*2 ARNU07GTU*2 ARNU18GTL*2
ARNU09GTJ*2 ARNU09GTU*2 ARNU24GTL*2
ARNU12GTJ*2 ARNU12GTU*2
ARNU18GTT*2 * A:Basic, C:Plasma
ARNU24GTT*2
* A:Basic, C:Plasma Ceiling Concealed Duct - High Static
ARNU07GBHA2 ARNU24GBRA2
ARNU09GBHA2 ARNU28GBRA2
Ceiling Cassette- 4Way ARNU12GBHA2 ARNU36GBRA2
ARNU07GTE*2 ARNU05GTR*2 ARNU24GTP*2 ARNU15GBHA2 ARNU42GBRA2
ARNU09GTE*2 ARNU07GTR*2 ARNU28GTP*2 ARNU18GBHA2 ARNU48GBRA2
ARNU12GTE*2 ARNU09GTR*2 ARNU36GTN*2 ARNU24GBHA2 ARNU54GBRA2
ARNU15GTE*2 ARNU12GTR*2 ARNU42GTM*2 ARNU12GBGA2 ARNU36GB8A2
ARNU18GTE*2 ARNU15GTQ*2 ARNU48GTM*2 ARNU15GBGA2 ARNU42GB8A2
ARNU18GTQ*2 ARNU18GBGA2 ARNU48GB8A2
ARNU24GBGA2 ARNU76GB8A2
ARNU28GBGA2 ARNU96GB8A2
* A:Basic, C:Plasma ARNU36GBGA2 ARNU76GB8D2
ARNU42GBGA2 ARNU96GB8D2
Ceiling Concealed Duct - Low Static ARNU18GBRA2
ARNU07GB1G2 ARNU15GB1G2
ARNU09GB1G2 ARNU18GB2G2 Wall Mounted
ARNU12GB1G2 ARNU24GB2G2 ARNU07GSE*2 ARNU05GSBL2
ARNU09GSE*2 ARNU07GSBL2
ARNU12GSE*2 ARNU09GSBL2
ARNU05GL1G2 ARNU15GL2G2 ARNU15GSE*2 ARNU12GSBL2
ARNU07GL1G2 ARNU18GL2G2 ARNU18GS5*2 ARNU15GSBL2
ARNU09GL1G2 ARNU21GL3G2 ARNU24GS5*2 ARNU18GSCL2
ARNU12GL2G2 ARNU24GL3G2 ARNU24GSCL2
* A:Basic, L:Plasma

Ceiling Concealed Duct – Built-in ART COOL Gallery


ARNU07GB3G2 ARNU15GB3G2 ARNU07GSF*2
ARNU09GB3G2 ARNU18GB4G2 ARNU09GSF*2
ARNU12GB3G2 ARNU24GB4G2 ARNU12GSF*2
* E:Red V:Silver
G:Gold 1: Kiss (Photo changeable)

ART COOL Mirror Floor Standing


ARNU07GSE*2 S3: * B : Blue SE: * R:Mirror With case
ARNU09GSE*2 M : Metal V:Silver
ARNU07GCEA2
ARNU12GSE*2 D : Wood B : Blue
ARNU09GCEA2
ARNU15GSE*2 R : Mirror
ARNU12GCEA2
ARNU18GS3*2 W : White Wood
ARNU15GCEA2
ARNU24GS3*2
ARNU18GCFA2
ARNU24GCFA2
Ceiling & Floor
ARNU09GVEA2 Without case
ARNU12GVEA2 ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2
Ceiling Suspended ARNU15GCEU2
ARNU18GVJA2 ARNU18GCFU2
ARNU24GVJA2 ARNU24GCFU2

Copyright ©2014 LG Electronics. Inc. All right reserved. -5-


LGE Internal Use Only
Only for training and service purposes
Nomenclature

3. Nomenclature
ARN U 07 G TJ A 2

Serial Number
Combinations of functions
A:Basic function
L:Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
ART COOL Type Panel Color
B:Blue D:Wood M:Metal R:Mirror W:White Wood
V: Silver E:Red G:Gold 1: Kiss (Photo changeable)
Chassis Name
Electrical Ratings
1:1Ø, 115V, 60Hz 2: 1Ø, 220V, 60Hz
6:1Ø, 220 ~ 240V, 50Hz 7: 1Ø, 100V, 50/60Hz
G:1Ø, 220 ~ 240V, 50Hz / 220V 60Hz
Total Cooling Capacity in Btu/h
EX) 5,000 Btu/h → '05' 18,000 Btu/h → '18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
❈ LGETA:U Ex) URN

Copyright ©2014 LG Electronics. Inc. All right reserved. -6-


LGE Internal Use Only
Only for training and service purposes
Part 2
Indoor Units

Ceiling Cassette
1 Way .................................................................................8
1 Way(Art Type) ...............................................................13
2 Way...............................................................................19
4 Way(1)...........................................................................24
4 Way(2)...........................................................................29
4 Way(3)...........................................................................36
Art Cool Series
ART COOL Miror..............................................................42
ART COOL Gallery ..........................................................53
Ceiling Concealed Duct
Low Static ........................................................................63
Built In ..............................................................................70
High Static........................................................................76
Wall Mounted(General)
Wall Mounted ...................................................................85
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................98
Floor Standing
Floor Standing................................................................105

Copyright ©2014 LG Electronics. Inc. All right reserved. -7-


LGE Internal Use Only
Only for training and service purposes
Ceiling Mounted Cassette Type (1Way)

1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12

Copyright ©2014 LG Electronics. Inc. All right reserved. -8-


LGE Internal Use Only
Only for training and service purposes
Specification

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. -9-


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 10 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 11 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 1-way
Dimensions

ARNU07GTJ*2
ARNU09GTJ*2
ARNU12GTJ*2

961.2
19.1 16.5 860

32.8 (unit : mm)

Only for training and service purposes


Number Name Description
1 Liquid pipe connection ø6.35 flare

410
2 Gas pipe connection ø12.7 flare
3. Dimensions

344.4
3 Air suction grill

Copyright ©2014 LG Electronics. Inc. All right reserved.


4 Air discharge grill

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
198.8 131 .

16.4
2 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

- 12 -
110
1

242.5
173
151
100
56
83 30
36
138 50
1070
83
939

480
3

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TJ


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Mounted Cassette Type (1Way)(Art Type)

1. Functions ....................................................................................14
2. Operation Details........................................................................15
3. Dimensions .................................................................................17

Copyright ©2014 LG Electronics. Inc. All right reserved. - 13 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter(Grill Type)
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Robot Cleaner(Optional) • It is operating automatically clean function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 14 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 15 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 16 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 1-way(Art Type)

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

(unit : mm)

Only for training and service purposes


Number Name Description
1 Liquid pipe connection Unit size(07,09,12K) Ø6.35
3. Dimensions

2 Gas pipe connection Unit size(07,09,12K) Ø12.7


3 Air suction grill

Copyright ©2014 LG Electronics. Inc. All right reserved.


4 Air discharge grill

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or

- 17 -
applicable national codes.

CHASSIS CODE: TU
Dimensions

LGE Internal Use Only


Ceiling Cassette 1-way(Art Type)
Dimensions

ARNU18GTT*2
ARNU24GTT*2

(unit : mm)

Only for training and service purposes


Number Name Description
1 Liquid pipe connection Unit size(18K) Ø6.35 (24K) Ø9.52
2 Gas pipe connection Unit size(18K) Ø12.7 (24K) Ø15.88
3 Air suction grill

Copyright ©2014 LG Electronics. Inc. All right reserved.


4 Air discharge grill

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or

- 18 -
applicable national codes.

CHASSIS CODE: TT

LGE Internal Use Only


Ceiling Mounted Cassette Type (2Way)

1. Functions ....................................................................................20
2. Operation Details........................................................................21
3. Dimensions .................................................................................23

Copyright ©2014 LG Electronics. Inc. All right reserved. - 19 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 20 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 21 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 22 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 2-way

ARNU18GTL*2
ARNU24GTL*2

A
830 B
47.9

(unit : mm)

Only for training and service purposes


Number Name Description

275
1 Liquid pipe connection (18k) ø6.35, (24k)ø9.52
2
2 Gas pipe connection (18k) ø12.7, (24k)ø15.88
3. Dimensions

550
3 Air suction grill

69.5

Copyright ©2014 LG Electronics. Inc. All right reserved.


4 Air discharge grill
1

Note
1. Unit should be installed in compliance with the installation manual
889.2 in the product box.
TL 2. Unit shall be grounded in accordance with the local regulations or
A 225 applicable national codes.

- 23 -
B 126.5

1050
28.5

640
4

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TL


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Ceiling Mounted Cassette Type (4Way) (1)

1. Functions ....................................................................................25
2. Operation Details........................................................................26
3. Dimensions .................................................................................28

Copyright ©2014 LG Electronics. Inc. All right reserved. - 24 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Swirl Swing Control • It is operating swirl swing

Copyright ©2014 LG Electronics. Inc. All right reserved. - 25 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

n Swirl Swing Control Vane 2


Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely

Vane 1 Vane 3

Vane 4

Copyright ©2014 LG Electronics. Inc. All right reserved. - 26 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 27 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 4-way
ARNU07GTE*2
Dimensions

ARNU09GTE*2
ARNU12GTE*2
269
ARNU15GTE*2
670 ARNU18GTE*2
670
(unit : mm)

Only for training and service purposes


Number Name Description
1 Liquid pipe connection Unit size(7k, 9k, 12k, 18k):ø6.35
2 Gas pipe connection Unit size(7k, 9k, 12k, 18k):ø12.7
3. Dimensions

670 570 3 Drain pipe connection

Copyright ©2014 LG Electronics. Inc. All right reserved.


450 4 Power supply connection
5 Air discharge grill
6 Air suction grill

5
Note
1. Unit should be installed in compliance with the installation manual

- 28 -
570
521
in the product box.

670
6 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

40
4
1 2

30
110 110

269
90
90

30
120.4
3

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TE


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Mounted Cassette Type (4Way) (2)

1. Functions ....................................................................................30
2. Operation Details........................................................................31
3. Dimensions .................................................................................33

Copyright ©2014 LG Electronics. Inc. All right reserved. - 29 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Swirl Swing Control • It is operating swirl swing

Copyright ©2014 LG Electronics. Inc. All right reserved. - 30 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

n Swirl Swing Control Vane 2


Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely

Vane 1 Vane 3

Vane 4

Copyright ©2014 LG Electronics. Inc. All right reserved. - 31 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 32 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 4-way
804 ARNU24GTP*2
ARNU28GTP*2

154
204
R35

126
62

A direction View
618

0
292 787

R2
4-
A

Only for training and service purposes


(unit : mm)
Number Name Description
1 Liquid pipe connection Unit size(24k, 28k):ø9.52
3. Dimensions

2 Gas pipe connection Unit size(24k, 28k):ø15.88


3 Drain pipe connection

Copyright ©2014 LG Electronics. Inc. All right reserved.


618
671
684
840

950
4 Power supply connection

500(Air outlet hole)


5 Air discharge grill
6 Air suction grill

- 33 -
500(Air outlet hole) 787
54 734 Note
950 840
6 1. Unit should be installed in compliance with the installation manual
5 in the product box.
4
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
204

25
82
99
60

65 40
108 60 80
2 840 3
1

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TP


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Ceiling Cassette 4-way
840

195
ARNU36GTN*2
Dimensions

246
R35

126
62
A

A direction View

Only for training and service purposes


(unit : mm)
Number Name Description

Copyright ©2014 LG Electronics. Inc. All right reserved.


1 Liquid pipe connection Unit size(36k):ø9.52
2 Gas pipe connection Unit size(36k):ø15.88
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill

- 34 -
6 Air suction grill

6
5 4
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
2 3
1

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TN


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Cassette 4-way

ARNU42GTM*2
ARNU48GTM*2
840

R35

126

237

288
109

A direction View

Only for training and service purposes


A

(unit : mm)
Number Name Description
1 Liquid pipe connection Unit size(42k):ø9.52

Copyright ©2014 LG Electronics. Inc. All right reserved.


2 Gas pipe connection Unit size(48k):ø15.88
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill

- 35 -
6 Air suction grill

Note
1. Unit should be installed in compliance with the installation manual
4 in the product box.
6
5 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

3
2

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TM


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Ceiling Mounted Cassette Type (4Way) (3)

1. Functions ....................................................................................37
2. Operation Details........................................................................38
3. Dimensions .................................................................................40

Copyright ©2014 LG Electronics. Inc. All right reserved. - 36 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • Jet, High, Med, Low, Lolow

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Airflow Direction Control • The louver can be set at swing up and down automatically.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25°C.

• To install a unit is very convenient because of smaller


Compact and light design
size than textile.

• The most advanced low-noise design.


Low noise
• The adoption of turbo fan and round type heat exchang-
er give the quietest operation.
• Long life wrinkle(type) and washable and anti-bacteria
Long life filter
filter is adopted.
• Built-in drain pump automatically drains water.
High head Drain pump
• A standard drain-head height of up to 700mm is possible.

High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.

Central Control(Optional) • It is operating individually or totally by central control function.

Swirl Swing Control • It is operating swirl swing

Copyright ©2014 LG Electronics. Inc. All right reserved. - 37 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail

2. Operation Detail
(1) The function of main control
n Auto Swing Control
• This function is to swing the louver up and down automatically.

n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air Temperature

Thermo. ON
(SET TEMPERATURE +0.5°C)

Thermo. OFF
(SET TEMPERATURE -0.5°C) More than More than
3 minutes 3 minutes

Selected Selected Selected


INDOOR FAN Low Low
Speed Speed Speed

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

n Swirl Swing Control Vane 2


Vane 2, 4 is almost vane closed while vane1, 3 is opened.
Vane 1, 3 and vane 2,4 turn over minutely

Vane 1 Vane 3

Vane 4

Copyright ©2014 LG Electronics. Inc. All right reserved. - 38 -


LGE Internal Use Only
Only for training and service purposes
Operation Detail
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor pipe
Temperature
36(42)°C

33(39)°C

25°C
22(20)°C

Room
Temperature

Thermal Off

Thermal On

Minimum

3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON

Thermal ON Thermal OFF


Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2

n Hot-start Control
• The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
• The operation diagram is as following.

Pipe
temperature

35 °C
30 °C
27 °C
25 °C

22 °C
LO
LOW

Indoor fan SELECTED


OFF LOW FAN
LOW LOLOW
speed
COMP ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 39 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Cassette 4-way
ARNU05GTR*2
ARNU07GTR*2
ARNU09GTR*2
ARNU12GTR*2

Only for training and service purposes


(unit : mm)
Number Name Description
1 Liquid pipe connection Unit size(05,07,09,12K) Ø6.35
3. Dimensions

2 Gas pipe connection Unit size(05,07,09,12K) Ø12.7

Copyright ©2014 LG Electronics. Inc. All right reserved.


3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill

- 40 -
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

CHASSIS CODE : TR

LGE Internal Use Only


Ceiling Cassette 4-way

ARNU15GTQ*2
ARNU18GTQ*2

Only for training and service purposes


(unit : mm)
Number Name Description

Copyright ©2014 LG Electronics. Inc. All right reserved.


1 Liquid pipe connection Unit size(15,18K) Ø6.35
2 Gas pipe connection Unit size(15,18K) Ø12.7
3 Drain pipe connection
4 Power supply connection

- 41 -
5 Air discharge grill
6 Air suction grill

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

CHASSIS CODE : TQ

LGE Internal Use Only


Art Cool Type(Mirror)

1. Functions ....................................................................................43
2. Operation Details........................................................................44
3. Dimensions .................................................................................51

Copyright ©2014 LG Electronics. Inc. All right reserved. - 42 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control


• High, Med, Low, CHAOS

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

Soft Dry Operation Mode


• Intermittent operation of fan at low Speed.

Sleep Mode Auto Control


• The fan is switched to low(Cooling), med(Heating) Speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operation ing defrosting.
• The fan Speed is automatically switched from high to low Speed.
Hot-start Control (Heating)

Airflow Direction Control • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing at 28°C.
up and down automatically.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 43 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow Speed set by the remote controller. While in compres-
sor not running, operating with the low airflow Speed regardless of the setting.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 44 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Healthy Dehumidification Mode


• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C => 18°C
• While in compressor off, the indoor fan repeats low airflow Speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow Speed.

n Heating Mode Operation


• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C
Themo OFF Temp. => Setting Temp.+4°C
• While in compressor on, when above 38°C, it operates with setting airflow Speed (while in sleep mode, with
the medium airflow Speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow Speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the tem-
perature

Copyright ©2014 LG Electronics. Inc. All right reserved. - 45 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Fuzzy Operation (Outdoor unit H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 46 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan repeats the low airflow Speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp + 2°C
Compressor OFF Temp => Setting Temp + 4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.

n Airflow Speed Selection


• The airflow Speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow Speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 47 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Off-Timer <=> On-Timer Operation


• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow Speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow Speed of the indoor fan is set to
the medium.

n Chaos Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low Speed of the
airflow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory

Copyright ©2014 LG Electronics. Inc. All right reserved. - 48 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation (Outdoor unit C/O Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C and the high Speed of
airflow.

n Forced Operation (Outdoor unit H/P Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low Speed for around 15 sec and then the opera-
tion condition is set according to the intake air temperature as follows.
24°C ≤ Intake Air Temp => Cooling Mode Operation, 22°C, High Speed
21°C ≤ Intake Air Temp < 24°C => Dehumidification Operation, 23°C, High Speed
Intake Air Temp < 21°C => Heating Mode Operation, 24°C, High Speed

n Test Operation Control


• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high Speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow Speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.

n Protection of the evaporator pipe from frosting


• In the temperrature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compres-
sor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of
the indoor pipe is over 7°C, the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C and restarts at the pipe temperature above
6°C or after 90 seconds, if the pipe temperature does not rise to 6°C, outdoor fan motor runs continuously at
even below 3°C.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 49 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Buzzer Sounding Operation


• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.

n Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 50 -


LGE Internal Use Only
Only for training and service purposes
ART COOL Mirror
H
ARNU07GSE*2
2 ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2

Only for training and service purposes


W
(unit : mm)
Model W H D

165
1
3. Dimensions

ARNU07GSE*2
169 ARNU09GSE*2 915 282 169
ARNU12GSE*2

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU15GSE*2

(unit : mm)
Number Name Description

282

282
1 Air discharge grill

- 51 -
53
2 Air suction grill
915 51

567
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
265

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SE


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


ART COOL Mirror
H ARNU18GS3*2
2
Dimensions

ARNU24GS3*2

Only for training and service purposes


W

173
1
(unit : mm)
1170 Model W H D

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU18GS3*2 1170 315 173
ARNU24GS3*2

315
(unit : mm)
Number Name Description

- 52 -
1 Air discharge grill
2 Air suction grill

Note

567 1. Unit should be installed in compliance with the installation manual


in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
304

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: S3


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


ArtCoolGallery

1. Functions ....................................................................................54
2. Operation Details........................................................................55
3. Dimensions .................................................................................62

Copyright ©2014 LG Electronics. Inc. All right reserved. - 53 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control


• High, Med, Low, CHAOS

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.

Soft Dry Operation Mode


• Intermittent operation of fan at low Speed.

Sleep Mode Auto Control


• The fan is switched to low(Cooling), med(Heating) Speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operation ing defrosting.
• The fan Speed is automatically switched from high to low Speed.
Hot-start Control (Heating)

Airflow Direction Control • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing at 28°C.
up and down automatically.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 54 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow Speed set by the remote controller. While in compres-
sor not running, operating with the low airflow Speed regardless of the setting.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 55 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Healthy Dehumidification Mode


• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C => 18°C
• While in compressor off, the indoor fan repeats low airflow Speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow Speed.

n Heating Mode Operation


• When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2˚C
Themo OFF Temp. => Setting Temp.+4°C
• While in compressor on, when above 38°C, it operates with setting airflow Speed (while in sleep mode, with
the medium airflow Speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow Speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the tem-
perature

Copyright ©2014 LG Electronics. Inc. All right reserved. - 56 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Fuzzy Operation (Outdoor unit H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 57 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan repeats the low airflow Speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp + 2°C
Compressor OFF Temp => Setting Temp + 4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
n Airflow Speed Selection
• The airflow Speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow Speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 58 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Off-Timer <=> On-Timer Operation


• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation
is carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow Speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow Speed of the indoor fan is set to
the medium.

n Chaos Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low Speed of the
airflow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory

Copyright ©2014 LG Electronics. Inc. All right reserved. - 59 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation (Outdoor unit C/O Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation button is on
the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• The forced operation is carried out in cooling mode with the setting temperature 22°C and the high Speed of
airflow.

n Forced Operation (Outdoor unit H/P Model)


• To operate the appliance by force in case that the remote controller is lost, the forced operation selection
switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• Press the forced operation button, the forced operation is carried out.
• Press the forced operation button once again to stop operation.
• In the forced operation mode, the indoor fan is operated at low Speed for around 15 sec and then the opera-
tion condition is set according to the intake air temperature as follows.
24°C ≤ Intake Air Temp => Cooling Mode Operation, 22°C, High Speed
21°C ≤ Intake Air Temp < 24°C => Dehumidification Operation, 23°C, High Speed
Intake Air Temp < 21°C => Heating Mode Operation, 24°C, High Speed

n Test Operation Control


• To check the condition of the installation when installing the appliance, the appliance is operated at cooling
mode, high Speed of airflow, compressor-on for 18 min without controlling the room temperature.
• After supplying power to the main body, keep pressing the forced operation button for about 3 seconds.
• While in test operation, a key can be input by the remote controller.
When a key (operation start/stop, operation mode selection, airflow Speed selection, temperature control, Jet
Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according
to the setting by the remote controller.

n Protection of the evaporator pipe from frosting


• In the temperrature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compres-
sor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of
the indoor pipe is over 7°C, the compressor and the outdoor fan are reoperated.
• Outdoor fan motor stops when indoor pipe temperature is blow 3°C and restarts at the pipe temperature above
6°C or after 90 seconds, if the pipe temperature does not rise to 6°C, outdoor fan motor runs continuously at
even below 3°C.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 60 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Buzzer Sounding Operation


• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.

n Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 61 -


LGE Internal Use Only
Only for training and service purposes
2 ART COOL Gallery
W D
ARNU07GSF*2
Dimensions

ARNU09GSF*2
ARNU12GSF*2

H (unit : mm)
Model W H D

Only for training and service purposes


1
ARNU07GSF*2
1 ARNU09GSF*2 600 600 146
ARNU12GSF*2
3. Dimensions

(unit : mm)

Copyright ©2014 LG Electronics. Inc. All right reserved.


Pipe Hole
Number Name Description
1 Air discharge grill
2 Air suction grill
1
Hanger Hole

- 62 -
500
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

525
Fix Hole

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SF


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct Type (Low static)

1. Funtions ......................................................................................64
2. Operation Details........................................................................65
3. Dimensions .................................................................................68

Copyright ©2014 LG Electronics. Inc. All right reserved. - 63 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C.

High head height Drain pump • A standard drain-head height of up to 700mm is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 64 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature

SET TEMPERATURE +0.5°C


(Thermo. ON)

SET TEMPERATURE -0.5°C


(Thermo. OFF) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan Speed fan Speed fan Speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 65 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
Speed Speed Speed
4way valve ON

• Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low Speed, when it becomes lower than 40°C fan stops.
- B For eluminating latent heat-loss, fan operates at low Speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation

Low Static
Chassis B1 B2 L1 L2 L3
Hotstart On T On 19°C 19°C 19°C 19°C 19°C
Hotstart Off T Off 22°C 22°C 22°C 22°C 22°C
Low temperature T LT 25°C 25°C 25°C 25°C 25°C
Setting Temperature T ST 27°C 27°C 27°C 27°C 27°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 66 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2014 LG Electronics. Inc. All right reserved. - 67 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Concealed Duct (Low Static)
Dimensions

ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
ARNU15GB1G2
ARNU18GB2G2
D 5 13 ARNU24GB2G2

Only for training and service purposes


(unit: mm)

161
A B C D
3. Dimensions

ARNU07GB1G2
190

14
ARNU09GB1G2
65 60 820 728 856 794

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU12GB1G2
ARNU15GB1G2
1
ARNU18GB2G2

216
ARNU24GB2G2 1100 1008 1131 1072
2

277
24
(unit : mm)

575
383

- 68 -
Number Name Description
Unit size(7k,9k,12k,18k):ø6.35
3 1 Liquid pipe connection Unit size(24k):ø9.52
Unit size(7k,9k,12k,18k):ø12.7
2 Gas pipe connection Unit size(24k):ø15.88
C
3 Drain pipe connection
4 4 Power supply connection

18
6
5 Air discharge
6 Air suction

190
154
Note
18 B
1. Unit should be installed in compliance with the installation manual
A in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B1/B2


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct (Low Static)
ARNU05GL1G2
ARNU07GL1G2
ARNU09GL1G2
ARNU12GL2G2
ARNU15GL2G2
ARNU18GL2G2

Only for training and service purposes


5 ARNU21GL3G2
20 D
ARNU24GL3G2
(unit: mm)

135
A B C D

34

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU05GL1G2
190
100 ARNU07GL1G2 774 700 733 660
94 ARNU09GL1G2
ARNU12GL2G2
2 ARNU15GL2G2 974 900 933 860
ARNU18GL2G2

292
67 119
1

- 69 -
ARNU21GL3G2
1,174 1,100 1,133 1,060
3 ARNU24GL3G2
(unit : mm)

700
628
Number Name Description
Unit size(5k,7k,9k,18k) :6.35
1 Liquid pipe connection Unit size(21k,24k) :9.52
4
Unit size(5k,7k,9k,18k) :12.7
2 Gas pipe connection Unit size(21k,24k) :15.88
L1 : 366
L2 : 561 3 Drain pipe connection
L3 : 755

C 4 Power supply connection


6
5 Air discharge

20
6 Air suction
Note

190
155
L1 : 75
L2 : 78
L3 : 81 1. Unit should be installed in compliance with the installation manual
B in the product box.
A
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: L1/L2/L3


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Ceiling Concealed Duct Type (Built in)

1. Funtions ......................................................................................71
2. Operation Details........................................................................72
3. Dimensions .................................................................................75

Copyright ©2014 LG Electronics. Inc. All right reserved. - 70 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25°C.

High head height Drain pump • A standard drain-head height of up to 700mm is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 71 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature

SET TEMPERATURE +0.5°C


(Thermo. ON)

SET TEMPERATURE -0.5°C


(Thermo. OFF) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan Speed fan Speed fan Speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 72 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation

Built in
Chassis B3 B4
Hotstart On T On 19°C 19°C
Hotstart Off T Off 22°C 22°C
Low temperature T LT 25°C 25°C
Setting Temperature T ST 27°C 27°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 73 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2014 LG Electronics. Inc. All right reserved. - 74 -


LGE Internal Use Only
Only for training and service purposes
Ceiling Concealed Duct (Built in)
B3/B4
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
With Suction Grille ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
With Suction Grille & Suction Canvas
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Only for training and service purposes


190
6
65 60
3. Dimensions

216

277
2

24

575

Copyright ©2014 LG Electronics. Inc. All right reserved.


388
388
618
1

3
5

A
With Suction Grille 4
B

- 75 -
Btu/h A
7,9,12k 820

190
18,24k 1100 (unit : mm)

250
A
Number Name Description
C Unit size(7k,9k,12k,18k):ø6.35
With Suction Grille & Suction Canvas 1 Liquid pipe connection Unit size(24k):ø9.52
A B C
Unit size(7k,9k,12k,18k):ø12.7
2 Gas pipe connection Unit size(24k):ø15.88
PBSGB30 910 359 56

190
PBSGB40 1188 359 56 3 Drain pipe connection
4 Power supply connection
A B C

500(Max)
PBSC30 821 274 42~250 5 Air discharge
PBSC40 1100 274 42~250 6 Air suction
C
Note
A B 1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B3/B4


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Ceiling Concealed Duct Type (High Static)

1. Funtions ......................................................................................77
2. Operation Details........................................................................78
3. Dimensions .................................................................................81

Copyright ©2014 LG Electronics. Inc. All right reserved. - 76 -


LGE Internal Use Only
Only for training and service purposes
Funtion

1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

• Although the air-conditioner is turned off by a power failure, it is restarted auto-


Auto Restart
matically previous operation mode after power supply.

• Both the indoor and outdoor fan stops during defrosting.


Deice (defrost) control (Heating)
• Hot start after defrost ends.

• The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 30°C.

High head height Drain pump • A standard drain-head height of up to 700mm is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 77 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature

SET TEMPERATURE +0.5°C


(Thermo. ON)

SET TEMPERATURE -0.5°C


(Thermo. OFF) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan Speed fan Speed fan Speed

COMPRESSOR ON OFF ON OFF ON

Copyright ©2014 LG Electronics. Inc. All right reserved. - 78 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Heating Mode Operation


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
Speed Speed Speed
4way valve ON

• Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low Speed, when it becomes lower than 40°C fan stops.
- B For eluminating latent heat-loss, fan operates at low Speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation

High Static
Chassis BH BG BR B8
Hotstart On T On 19°C 19°C 19°C 19°C
Hotstart Off T Off 22°C 22°C 22°C 22°C
Low temperature T LT 25°C 25°C 25°C 25°C
Setting Temperature T ST 27°C 27°C 27°C 27°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 79 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22°C.

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low Speed Off Low Speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2014 LG Electronics. Inc. All right reserved. - 80 -


LGE Internal Use Only
Only for training and service purposes
745 115 4 Ceiling Concealed Duct (High Static)

20
ARNU07GBHA2

175
ARNU09GBHA2
ARNU12GBHA2
ARNU15GBHA2
6 ARNU18GBHA2
49 101
ARNU24GBHA2
51 31

Only for training and service purposes


932 70
24
29
48
50
114 52 165 (unit : mm)

224
R3
3. Dimensions

7.
5
100 Number Name Description

355
60

450

355

450
Unit size(7k,9k,12k,18k):ø6.35
1 Liquid pipe connection

Copyright ©2014 LG Electronics. Inc. All right reserved.


123 140 Unit size(24k):ø9.52
1

133
Unit size(7k,9k,12k,18k):ø12.7
47 47 2
2 Gas pipe connection Unit size(24k):ø15.88
21 3 3 Drain pipe connection
87 30 260
4 Power supply connection
750
5 5 Air discharge
882 108

- 81 -
6 Air suction
65

75

158
Note

260
1. Unit should be installed in compliance with the installation manual
in the product box.
64 243 212 243 119 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

450
882

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BH


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


4 Ceiling Concealed Duct (High Static)
1,043 115
ARNU28GBGA2 ARNU12GBGA2
Dimensions

20
ARNU36GBGA2 ARNU15GBGA2
ARNU42GBGA2 ARNU18GBGA2

220
ARNU24GBGA2

(unit : mm)
6

Only for training and service purposes


1,230 Number Name Description
102
51 32 1 Liquid pipe connection Unit size : ø9.52
23

47 2 Gas pipe connection Unit size : ø15.88


50
152 53 165
ø1

224
00 3 Drain pipe connection
100

450
60

355
4 Power supply connection

Copyright ©2014 LG Electronics. Inc. All right reserved.


122 140 5 Air discharge
87 1
6 Air suction
2
49 3
87 29 75 261
830
5

- 82 -
1,182 108

Note

158

186
1. Unit should be installed in compliance with the installation manual

298
in the product box.

113
2. Unit shall be grounded in accordance with the local regulations or
232 243 232 243 232 applicable national codes.

450
1,182

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BG


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct (High Static)
1,092 120 4
ARNU18GBRA2 ARNU36GBRA2

25
ARNU24GBRA2 ARNU42GBRA2
ARNU28GBRA2 ARNU48GBRA2

303
ARNU54GBRA2

6 (unit : mm)
101
1,284
83 Number Name Description
1,230 115 26
1 Liquid pipe connection Unit size : ø9.52

Only for training and service purposes


72
123
2 Gas pipe connection Unit size : ø15.88

221
198

312
R6
0
3 Drain pipe connection

90
60

477
590
4 Power supply connection

122
144
1 5 Air discharge

Copyright ©2014 LG Electronics. Inc. All right reserved.


2

56
6 Air suction
50 3

32
118 114 135
1,004 190
260
5
Note
1. Unit should be installed in compliance with the installation manual
in the product box.

- 83 -
168

140
2. Unit shall be grounded in accordance with the local regulations or

380
applicable national codes.

185
215 279 241 279 215

590
1,230

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BR


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


4 Ceiling Concealed Duct (High Static)
1,396 115 ARNU36GB8A2 ARNU76GB8A2

20
Dimensions

ARNU42GB8A2 ARNU96GB8A2
ARNU48GB8A2

440
2

70
6

Only for training and service purposes


120
460 1,622
1,562 3
40
99 1

58 1
18
(unit : mm)

122 60 70 64
Number Name Description

Copyright ©2014 LG Electronics. Inc. All right reserved.


109

688
560
68 1 Liquid pipe connection Ø9.52
358
Ø19.05(Unit 36k, 42k, 48k, 76k)
2 Gas pipe connection Ø22.2 (Unit 96k)

64
3 Drain pipe connection

30
1,220
4 Power supply connection

- 84 -
5 5 Air discharge
6 Air suction

290

318
Note

460
1. Unit should be installed in compliance with the installation manual

161
in the product box.

293 329 320 329 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

688
1,562

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B8


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Concealed Duct (High Static)

ARNU76GB8D2
ARNU96GB8D2

Only for training and service purposes


(unit : mm)
Number Name Description

Copyright ©2014 LG Electronics. Inc. All right reserved.


1 Liquid pipe connection Unit size(76k,96k):ø9.52
Unit size(76k):ø19.05
2 Gas pipe connection Unit size(96k):ø22.2
3 Drain pipe connection
4 Power supply connection

- 85 -
5 Air discharge
6 Air suction

Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B8


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Wall Mounted Type

1. Functions ....................................................................................86
2. Operation Details........................................................................87
3. Dimensions .................................................................................94

Copyright ©2014 LG Electronics. Inc. All right reserved. - 86 -


LGE Internal Use Only
Only for training and service purposes
Functions

1. Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control


• Maintains the room temperature in accordance with the Setting temperature

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Indoor Fan Speed Control

• High, Medium, Low, CHAOS/AUTO (optional)

Operation indication Lamps (LED)


Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode : Lights up during Defrost Mode or Hot Start operation.
Temperature : Indicate the setting temperature.
• In the case of SB/SC only indicator lamps for Cooling, heating, Preheating and on/off

Soft Dry Operation Mode


• Intermittent operation of fan at low Speed.

Sleep Mode Auto Control


• The fan is switched to low(Cooling), Medium(Heating) Speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air control by CHAOS/AUTO Logic • Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operation ing defrosting.
• The fan Speed is automatically switched from high to low Speed.
Hot-start Control (Heating)

Airflow Direction Control • The indoor fan does not rotate until the
evaporator pipe temperature will be reached
• The louver can be set at the desired position or swing
at 28°C.
up and down automatically.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 87 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
Function of Controls
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator (Not available in SB/SC)
• On while in appliance operation, off while in appliance pause
Timer(on/off) and Sleep timer Indicator (Not available in SB/SC)
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator (Not available in SB/SC)
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator (Not available in SB/SC)
• On while in plasma mode, off while plasma mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow Speed set by the remote controller. While in com-
pressor not running, operating with the low airflow Speed regardless of the setting.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 88 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp < 26°C => Intake Air Temp-1°C
18°C ≤ Intake Air Temp < 24°C => Intake Air Temp-0.5°C
Intake Air Temp < 18°C => 18°C
• While in compressor off, the indoor fan repeats low airflow Speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C
Compressor OFF Temp. => Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow Speed.

n Heating Mode Operation


• When the intake air temp reaches +3°Cabove the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Thermo ON Temp. => Setting Temp. +2°C
Thermo OFF Temp. => Setting Temp. +4°C
• While in compressor on, when above 38°C , it operates with or setting airflow Speed (while in sleep mode, with
the medium airflow Speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C , when above 35°C , it
operates with the low airflow Speed.
• While in defrost control, both of the indoor and outdoor fans are turned off.

n Defrost Control
• While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost the outdoor unit.

n Fuzzy Operation (Outdoor unit C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 89 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp<18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the temper-
ature

n Fuzzy Operation (Outdoor unit H/P Model)


• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp => Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C => Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is automatically selected according to the temperature.

2) Fuzzy Operation for Dehumidification


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp => Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp+0.5°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 90 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp => 25°C
24°C ≤ Intake Air Temp<26°C => Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C => Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C => Intake Air Temp
Intake Air Temp < 18°C => 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan repeats the low airflow Speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp => Setting Temp. +2°C
Compressor OFF Temp => Setting Temp. +4°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C ≤ Intake Air Temp => Intake Air Temp + 0.5°C
Intake Air Temp < 20°C => 20°C

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow Speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
n Airflow Speed Selection
• The airflow Speed of the indoor fan is set to high, medium, low, or chaos/auto by the input of the airflow Speed
selection key on the remote controller.

n On-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.

n Off-Timer Operation
• When the set time is reached after the time is input by the remote controller, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 91 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is
carried out according to the set time.

n Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in
appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow Speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow Speed of the indoor fan is set to
the medium.

n Chaos/Auto Swing Mode


• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.

n Chaos Natural Wind Mode (Auto mode in the case of SB/SC)


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low Speed of the air-
flow mode is operated for 2~15 sec randomly by the Chaos Simulation.”

n Jet Cool Mode Operation (Outdoor unit C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at
extremely high Speed for 30 minutes setting the room temp. automatically to 18°C.

n Jet Cool Mode Operation (Outdoor unit H/P Model)


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.”
• In the Jet Cool mode, the indoor fan is operated at super-high Speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at
extremely high Speed for 60 minutes setting the room temp. automatically to 30°C.

n Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF

Copyright ©2014 LG Electronics. Inc. All right reserved. - 92 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)

n Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.

Heat pump Model


Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor Fan Speed High High High High
Setting Temperature 22°C 22°C 23°C 24°C

• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.

n Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high Speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep".
• If you want to stop the operation, re-press the button.

n Protection of the evaporator pipe from frosting


• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.

n Buzzer Sounding Operation


• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the
remote control signal cannot be received.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 93 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 94 -


LGE Internal Use Only
Only for training and service purposes
Wall Mounted
ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2

165
ARNU15GSE*2

(unit : mm)

Only for training and service purposes


Model W H D
2
895 ARNU07GSE*2
ARNU09GSE*2 895 282 165
3. Dimensions

ARNU12GSE*2
ARNU15GSE*2

Copyright ©2014 LG Electronics. Inc. All right reserved.


(unit : mm)

282
Number Name Description
1 Air discharge grill
2 Air suction grill
1

- 95 -
Note

567 1. Unit should be installed in compliance with the installation manual


in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

265

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SE


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Wall Mounted
1,090 ARNU18GS5*2
Dimensions

ARNU24GS5*2

(unit : mm)

Only for training and service purposes


2 178 Model W H D
ARNU18GS5*2
1090 300 178
ARNU24GS5*2

(unit : mm)

Copyright ©2014 LG Electronics. Inc. All right reserved.


300
Number Name Description
1 Air discharge grill
2 Air suction grill

- 96 -
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
804 applicable national codes.
281

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: S5


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


WALL MOUNTED
341 323 128 ARNU05GSBL2
ARNU07GSBL2
ARNU09GSBL2
ARNU12GSBL2
ARNU15GSBL2

No. Part Name Remark

Only for training and service purposes


895 1 Front panel
205
2 Display & signal receiver
3 Air suction grille
4 Knockout hole
5

Copyright ©2014 LG Electronics. Inc. All right reserved.


Installation plate

289
50

37
45
215 Model W H D
790
ARNU05GSBL2

- 97 -
ARNU07GSBL2
ARNU09GSBL2 885 285 210
ARNU12GSBL2
ARNU15GSBL2

Note
675 1. Unit should be installed in compliance with the installation manual
327 in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

264
422 70 [Unit : mm]

76, Seongsan-dong, Changwon City, Gyeongnam,


CHASSIS CODE: SB
641-713, Korea
www.lge.com/airconditioner
Dimensions

LGE Internal Use Only


WALL MOUNTED
ARNU18GSCL2
Dimensions

ARNU24GSCL2

210
1030
250

Only for training and service purposes


No. Part Name Remark
1 Front panel
2 Display & signal receiver

325
3 Air suction grille
4 Knockout hole
5

Copyright ©2014 LG Electronics. Inc. All right reserved.


Installation plate

Model W H D
ARNU07GSBL2

- 98 -
ARNU09GSBL2
885 285 210
ARNU12GSBL2
Place a level on raised tab
Unit Outline ARNU15GSBL2
460 570
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
ÿ 70
applicable national codes.
ÿ 70 Installation Plate
Left rear Measuring Tape Right rear
piping piping
69 56

105 Measuring Tape 207


Hanger
[Unit : mm]

76, Seongsan-dong, Changwon City, Gyeongnam,


CHASSIS CODE: SC
641-713, Korea
www.lge.com/airconditioner

LGE Internal Use Only


Ceiling & Floor
Ceiling Suspended

1. Funtions ......................................................................................97
2. Operation Details........................................................................98
3. Dimensions ...............................................................................101

Copyright ©2014 LG Electronics. Inc. All right reserved. - 99 -


LGE Internal Use Only
Only for training and service purposes
Function

1. Function
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.

High head height Drain pump • A standard drain-head height of up to 700mm is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 100 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature

SET TEMPERATURE +0.5°C


(Thermo. ON)

SET TEMPERATURE -0.5°C


(Thermo. OFF) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan Speed fan Speed fan Speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 101 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation

Convertible
Chassis VE VJ
Hotstart On T On 26°C 26°C
Hotstart Off T Off 27°C 27 °C
Low temperature T LT 28°C 28°C
Setting Temperature T ST 30°C 30°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 102 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2014 LG Electronics. Inc. All right reserved. - 103 -


LGE Internal Use Only
Only for training and service purposes
Ceiling & Floor
879
ARNU09GVEA2
Dimensions

24
ARNU12GVEA2

(unit : mm)
Signal receiver & Operation indicator Model W H D
900 1 200 ARNU09GVEA2 900 490 200

Only for training and service purposes


ARNU12GVEA2
Air discharge grill
(unit : mm)
Number Name Description
3. Dimensions

1 Air discharge grill

Copyright ©2014 LG Electronics. Inc. All right reserved.


2 Air suction grill

490
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

- 104 -
Air suction grill
<Ceiling Installation> 2 <Floor Installation>

587

273

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: VE


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Ceiling Suspended
800 ARNU18GVJA2
ARNU24GVJA2
41

(unit : mm)

Only for training and service purposes


Model W H D
950 1
220 ARNU18GVJA2 950 650 220
ARNU24GVJA2

Copyright ©2014 LG Electronics. Inc. All right reserved.


(unit : mm)
Number Name Description
1 Air discharge grill
2 Air suction grill

650

- 105 -
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
(Ceiling Suspended type)
2

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: VJ


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Floor Standing Type

1. Function ....................................................................................104
2. Operation Details......................................................................105
3. Dimensions ...............................................................................108

Copyright ©2014 LG Electronics. Inc. All right reserved. - 106 -


LGE Internal Use Only
Only for training and service purposes
Function

1. Function
Indoor Unit
Operation ON/OFF by Remote controller

Sensing the Room Temperature • Room temperature sensor. (Thermistor)

Room temperature control • Maintains the room temperature in accordance with the Setting Temperature.

Starting Current Control • Indoor fan is delayed for 5 seconds at the starting.

Indoor Fan Speed Control • High, Med, Low

Soft Dry Operation Mode • Intermittent operation of fan at low Speed.

Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.

Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.

Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.

High head height Drain pump • A standard drain-head height of up to 700mm is possible.

Central Control(Optional) • It is operating individually or totally by central control function.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 107 -


LGE Internal Use Only
Only for training and service purposes
Operation Details

2. Operation Details
(1) The function of main control
n Soft-Dry Operation
• The indoor fan Speed is automatically set to the low, so the shift of the indoor fan Speed is impossible because of
already being set to the best Speed for Dry Operation by microcontroller control.

n Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.

Intake Air Temperature

SET TEMPERATURE +0.5°C


(Thermo. ON)

SET TEMPERATURE -0.5°C


(Thermo. OFF) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan Speed fan Speed fan Speed

COMPRESSOR ON OFF ON OFF ON

Thermal ON Thermal OFF


Indoor Unit mode ST+0.5 ST-0.5
To be selected higher temperature To be selected higher temperature
2TH (Remo.+Indoor)
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5

Copyright ©2014 LG Electronics. Inc. All right reserved. - 108 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Indoor unit 40°C


Heat-Exchanger
temperature
T ST
A
T LT

T Off
T On

Intake Air Temperature


3min
B Low fan during 10sec
Setting Temperature
+3°C
(Thermal OFF)

Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min

Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON

• Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation

Low Static (Floor Standing Type)


Chassis CE CF
Hotstart On T On 19°C 19°C
Hotstart Off T Off 22°C 22 °C
Low temperature T LT 25°C 25°C
Setting Temperature T ST 27°C 27°C

Copyright ©2014 LG Electronics. Inc. All right reserved. - 109 -


LGE Internal Use Only
Only for training and service purposes
Operation Details
n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C.

• The operation diagram is as following.

Indoor unit
Heat-Exchanger
temperature

Hotstart Off

Hotstart On
1 min 1 min

Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON

• Initial Hotstart On state


¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation

Copyright ©2014 LG Electronics. Inc. All right reserved. - 110 -


LGE Internal Use Only
Only for training and service purposes
1067 Floor Standing
ARNU07GCEA2 ARNU07GCEU2
1
ARNU09GCEA2 ARNU09GCEU2
ARNU12GCEA2 ARNU12GCEU2
1067 203 ARNU15GCEA2 ARNU15GCEU2

(unit : mm)

Only for training and service purposes


Model W H D

635
ARNU07GCEA2
ARNU09GCEA2 1067 635 203
3. Dimensions

ARNU12GCEA2
ARNU15GCEA2

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU07GCEU2

70

49
ARNU09GCEU2 978 639 190
148.3 148.3
<With Case> 2 ARNU12GCEU2
ARNU15GCEU2

(unit : mm)
Number Name Description

- 111 -
1 Air discharge grill
978 190
2 Air suction grill
794 13 161 14

20.4
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or

639
applicable national codes.

62.8
<Without Case>

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CE


641-713, Korea
www.lgeaircon.com
Dimensions

LGE Internal Use Only


Floor Standing

203
ARNU18GCFA2 ARNU18GCFU2
1
Dimensions

ARNU24GCFA2 ARNU24GCFU2
203
1345

(unit : mm)

Only for training and service purposes


635
Model W H D
ARNU18GCFA2
ARNU24GCFA2 1345 635 203

70

49.4
ARNU18GCFU2
148.3 1048.4 148.3 1256 639 190

Copyright ©2014 LG Electronics. Inc. All right reserved.


ARNU24GCFU2
2
<With Case> (unit : mm)
Number Name Description
1 Air discharge grill
2 Air suction grill

- 112 -
1256 Note
1098 109.8 190
1072 30

21.4
161 14 1. Unit should be installed in compliance with the installation manual
in the product box.

81.4
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.

639
145

70
<Without Case>

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CF


641-713, Korea
www.lgeaircon.com

LGE Internal Use Only


Part 3
Trouble shooting guide

Copyright ©2014 LG Electronics. Inc. All right reserved. - 113 -


LGE Internal Use Only
Only for training and service purposes
Trouble shooting guide

Self-diagnosis function ...................................................................112

Copyright ©2013 LG Electronics. Inc. All right reserved. - 114 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Self-diagnosis function
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
•  If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 ’ 051 : No.105 error of master unit

Display Title Cause of Error


0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Transmission error : wired remote controller Failing to receive wired remote controller signal in indoor unit PCB
0 3 -
÷ indoor unit
Indoor unit related error

0 4 - Drain pump Malfunction of drain pump


Transmission error : outdoor unit ÷ indoor Failing to receive outdoor unit signal in indoor unit PCB
0 5 -
unit
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
0 7 - Different operation mode Operation mode between indoor unit and outdoor unit is different
Serial No. In case when the serial number marked on
0 9 -
EEPROM of Indoor unit is 0 or FFFFFF
Poor fan motor operation Disconnecting the fan motor connector/Failure of indoor fan motor
1 0 -
lock
Transmission error: indoor unit ’ main PCB When the addressing signal doesn't respond for 3mins. suddenly,
1 1 - of outdoor.
while the indoor unit gets the calling signal from the outdoor unit,

Copyright ©2013 LG Electronics. Inc. All right reserved. - 115 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

01 Indoor unit air sensor error 1. Indoor unit PCB wrong connection
02 Indoor unit pipe inlet sensor error Indoor unit sensor is 2. Indoor unit PCB failure
open/short
06 Indoor unit pipe outlet sensor error 3. Sensor problem (main reason)

n Error diagnosis and countermeasure flow chart

Is sensor properly No
Connect properly to PCB
connected to PCB?

Yes

Is the resistance value No


Change the sensor
of sensor normal?*

Yes

Change the PCB

** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ‘ Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ : 25°C= 5kΩ : 50°C= 1.8kΩ

CN-ROOM : Indoor air temp sensor

CN-PIPE2 : Pipe outlet temp sensor

CN-PIPE1 : Pipe inlet temp sensor

Measure the resistance of outlet pipe temp sensor.

Copyright ©2013 LG Electronics. Inc. All right reserved. - 116 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

1. Remote controller fault


The remote controller
03 No transmission between cabled did not receive the sig- 2. Indoor unit PCB fault
remote controller & indoor unit nal from indoor unit 3. Connector fault, Wrong connection
during specific time 4. transmission cable problem

n Error diagnosis and countermeasure flow chart

Does the error happens No Replace cabled remote


again if the remote
controller
controller is replaced?*

Yes

Does the error occurred No


when the cable of remote Check connection &
controller is replaced? transmission cable **

Yes

Replace indoor unit PCB ***

* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
‘ make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

CN-REMO : Remote controller connection

❇ The PCB can differ from model to model.


Check from the right source.

Checking transmission cable connection status

Copyright ©2014 LG Electronics. Inc. All right reserved. - 117 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Float switch is open due to 1. Drain pump/float switch fault


rising of condensate water 2. Improper drain pipe location, clog-
04 Drain pump error level because of drain ging of drain pipe
pump fault or drain pipe
3. Indoor unit PCB fault
clogging

n Error diagnosis and countermeasure flow chart

Is the drain pan filled Is Float switch short


No No
half with condensate On measuring its Replace float switch
water? (half level of resistance?
float switch)*
Yes
Yes

Replace Indoor PCB or


reconnect the connector

In indoor unit PCB


Is drain pump working? No Does the terminal voltage No
(Sound/drain noise/ Replace indoor unit PCB
for drain pump has
contact etc.) 220V output?**
Yes Yes

Replace Drain Pump

Mn
Drain pump blocked by Bgdbjsgdcq`hmgd`cgdhfgs
foreign particles? `mcrknod)))

Yes Bgdbjhmfekn`s
rvhsbg
'Knvonrhshnm➠rgnqs /ngl(

Remove it & clean the pump

* If the float goes up higher than a half of float


switch then the circuit is open & the unit is
stopped automatically.

ekn`s
'Ghfgonrhshnm➠Nodm(

Bnmcdmr`sdv`sdq

Copyright ©2014 LG Electronics. Inc. All right reserved. - 118 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

float

A:Point to check rotating *** Indoor PCB drain pump connector


(Check input of 220V)
(Marked as CN-DPUMP)

Float switch connector

Float switch Housing (CN-FLOAT)

[***] Standard of drain pipe head height / slope

MAX 450

Copyright ©2014 LG Electronics. Inc. All right reserved. - 119 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

1. Auto addressing is not done


2. transmission cable is not connected
3. Short circuit of transmission cable
No signal transmission 4. Indoor unit transmission circuit fault
05 Indoor & Outdoor unit between indoor & outdoor 5. Outdoor unit transmission circuit fault
transmission error units. 6. Not enough distance between power and trans-
mission cable?

n Error diagnosis and countermeasure flow chart


Replace the PCB of indoor unit
No Is total number of indoor No displayed error
Does all the IDUs show
units connected displayed
same error code CH05? Re-connect after check the
after auto addressing?
transmission cable of indoor
Yes unit displayed error**
END
Replace outdoor PCB after
No Check the main power No checking
Is outdoor PCB LED
supply at the ODU
blinking?
terminal block? Replace TRANS after checking

Yes
Yes

No Check the insulation of inverter


Is main circuit breaker off? / constant compressor and replace
if required
Yes
Check the capacity of main circuit
breaker and replace if required
Improper connection of power supply cable
If all ok,
Turn on main circuit breaker
Main power supply problem

Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking

* (Note1) Transmission from IDU is normal if voltage * If the DC voltage between transmission terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU transmission from outdoor unit is normal

Copyright ©2014 LG Electronics. Inc. All right reserved. - 120 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Indoor unit outlet pipe Indoor unit outlet pipe Refer to CH02
06 temperature sensor temperature sensor open
error or short

Error
Error Type Error Point Main Reasons
No.

The Indoor units started 1. Indoor units are in different mode


07 All Indoor units are not later are operated in dif- 2. PCB fault
running in same mode ferent mode from earlier 3. cabled remote controller fault
one. j Checking ch07 method
IDU doesn’t operate as Operation mode is
flickering at IDU wired remote controller and IDU
display window.

n Error diagnosis and countermeasure flow chart

Does error code


Is operation mode of No No
disappear
outdoor & Indoor units Replace Indoor PCB***
after set operation
same?
mode same?**

Yes Yes

END

Adjust outdoor main PCB


dip switch setting *

* Check mode selection setting of wired remote controller.


** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may occur because the operation mode is fixed by dip switch setting.

© Dip switch Setting ©

ON ON

1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14

ON ON

1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14

*** Dissolution method CH07 with remote controller


1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after few seconds.
With cableless remote controller: Turn off indoor unit, and then turn on by changing the operation
mode. The error will disappear.

Copyright ©2014 LG Electronics. Inc. All right reserved. - 121 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function
**** After replacing the indoor unit PCB, make sure to be done to do Auto addressing and input the address of central control
***** If ODU Dry Contact function is set , different mode operation error may be occurred because the operation mode is fixed.

Error
Error Type Error Point Main Reasons
No.

1. Error developed in transmission between the


09 Indoor unit EEPROM micro- processor and the EEPROM on the sur-
error face of the PCB.
2. ERROR due to the EEPROM damage

n Error diagnosis and countermeasure flow chart

- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control

Copyright ©2014 LG Electronics. Inc. All right reserved. - 122 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault

n Error diagnosis and countermeasure flow chart

Is connector No
connection proper? Connect properly

Yes

Is fan motor No
Replace indoor unit fan motor
normal?*

Yes

Replace indoor unit PCB **

* It is normal when check hall sensor of indoor fan motor as shown below

Each termainl with the tester


Tester Normal resistance (10%)
+ - TH chassis TD chassis L1 chassis L2 chassis L3 chassis
① ④ ∞ ∞ ∞ ∞ ∞
⑤ ④ hundreds kΩ hundreds kΩ hundreds kΩ hundredskΩ hundreds kΩ
⑥ ④ ∞ ∞ ∞ ∞ ∞
⑦ ④ hundreds kΩ hundreds kΩ hundreds kΩ hundredskΩ hundreds kΩ

1 4 5 6 7

<Checking connection state of fan motor connector>

** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)

Copyright ©2014 LG Electronics. Inc. All right reserved. - 123 -


LGE Internal Use Only
Only for training and service purposes
Self-diagnosis function

Error
Error Type Error Point Main Reasons
No.

Indoor unit transmission error Indoor unit doesn’t get sig- 1. Indoor 485 transmission PCB fault
11 nal from ODU for 3 minutes 2. After PCB replacing, auto addressing
continuously was not done

n Error diagnosis and countermeasure flow chart

After ODU main PCB No No


After Auto addressing, Replace indoor unit 485
reset, error code
error code disappears? transmission PCB
disappears?

Yes Yes

END

Copyright ©2014 LG Electronics. Inc. All right reserved. - 124 -


LGE Internal Use Only
Only for training and service purposes
P/NO : MFL50459501 JANUARY, 2014