Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
Exceeding boundaries
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
with innovative energy savings
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
•Specifications, designs and other content appearing in this brochure are current as of August 2017 but subject to change without notice.
c All rights reserved
AD. Cooling Only 60 Hz
New heights in energy efficiency
during actual operation
Hardware
New Scroll Compressor* technology
The key to innovative energy •Correlation between the load factor for the rated capacity and operation time
(in office buildings in Singapore)
savings is to increase efficiency *According to a survey by Daikin (based on Air Conditioning Network Service System data)
Refrigerant leakage is minimised during low-load operation.
Operation loss due to refrigerant leakage is reduced by the proprietary
during low-load operation.
back pressure control mechanism to ensure stable low-load operation.
Using data gathered from actual operation, Load factor of 50% or less Back pressure control mechanism
Daikin discovered that air conditioning accounts for 80% of
Conventional mechanism New intermediate pressure mechanism
annual operation period. New
Operation period
systems operate at a load factor of 50% or
The movable scroll is pressed by The force pressing the movable scroll
less for 80% of their annual operation the pressure difference between
high and low pressures.
is optimised according to operating
period. conditions. The behavior of the
The force pressing the movable
This inspired us to develop new scroll decreases during low-load movable scroll has been stabilised to
technologies to enhance energy efficiency operation, resulting in
compression leakage from
increase efficiency during low-load
during low loads. movable parts. operation.
Utilising these technologies, Daikin’s new •Compressor efficiency*
VRV X and A series raise the standard for Intermediate pressure
New compressor
adjustment port
energy efficiency. Conventional compressor
Compressor efficiency
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% The intermediate pressure
(back pressure) optimises
the force pressing the
Load factor for the rated capacity movable scroll depending
on the operating condition.
energy savings during actual operation. * The new mechanism is used in all models except for RXUQ8A, RXQ6, 8, 16, and 18A. *Graph shown above is for illustration purpose only.
Software
Variable Refrigerant Temperature Smart Control (Fully Automatic Energy-saving Refrigerant Control) technology
Optimally supply only for the needed capacity of indoor units Other technologies to increase efficiency
Daikin developed Variable Refrigerant Temperature smart control by combining air volume control (VAV: valuable air Optimal amount of refrigerant is Standby power consumption is reduced
volume) for indoor units with conventional Variable Refrigerant Temperature control, which optimises compressor charged automatically The advanced oil temperature control reduces standby
speed by calculating the required load for the entire system and optimal target refrigerant temperature based on data The automatic refrigerant charge function automatically power consumption by up to 82.7%* annually compared to
sent from each indoor unit. Coordination with the air volume control reduces compressor load and minimises determines the optimal amount of refrigerant to be charged. conventional models. Standby power needed for preheating
operation loss based on detailed control. Variable Refrigerant Temperature smart control ensures energy savings and This function prevents a capacity shortage or energy loss refrigerator oil, which consumed substantial standby power,
comfortable air conditioning to meet actual operating conditions. due to excessive or insufficient refrigerant. was reduced to save energy when the air conditioner is
•Overview of the control (system control flow) stopped.
Different automatic energy-saving refrigerant control applies depending on the indoor units connected. Two compressors provide optimum operation* * Operation calculation conditions: VRV A series 14 HP
Location: Singapore
The outdoor unit is equipped with two compressors. Operation time: 08:00–18:00 on weekdays
Target indoor units
1
Temperature The speed of each compressor is automatically controlled to
Subject to Variable Refrigerant Subject to Variable Refrigerant
data received constantly optimise the overall efficiency depending on the Effective use of heat exchange area*
from indoor units
Temperature smart control Temperature control load. The start-stop loss during low-load operation is also The heat exchanger area is larger than that of conventional
minimised to increase efficiency. systems in which one compressor is operated.
C oord i nated co ntrol *Only available for VRV X series. This helps improve the efficiency of heat exchange during
low-load operation.
*Only available for VRV X series.
The following items are
The Variable Refrigerant Temperature
forecast and calculated based smart control also controls the airflow
on the required capacity: rate of indoor units automatically*, to
•Indoor fan air volume attain detailed energy-saving control. When one New Even when one
2
Select the target
3
•Target value of refrigerant * Airflow rate should be set to “Auto”. Compressor High-COP type compressor stops,
compressor stops,
refrigerant the heat exchange
temperature speed control (12 HP) area decreases to half. the heat exchange
temperature area does not decrease.
(12 HP)
The smooth control •Changes in the air-conditioned room temperature during low-load operation*
(which keeps the compressor Conventional air-conditioning method Fully automatic energy-saving Higher efficiency is provided during rated operation.
refrigerant control
running) saves energy and Changes in the room temperature: Large COP at 100% operation load
The power consumption attributed to the Changes in the room temperature: Small
ensures comfort during low-load star t-stop loss also increases the load. Wasted power consumption is also 5 4.82 4.75 4.71
Start minimised. 4.40 4.33
Cooling operation COP
Using data gathered from actual operation, Load factor of 50% or less Back pressure control mechanism
Daikin discovered that air conditioning accounts for 80% of
Conventional mechanism New intermediate pressure mechanism
annual operation period. New
Operation period
systems operate at a load factor of 50% or
The movable scroll is pressed by The force pressing the movable scroll
less for 80% of their annual operation the pressure difference between
high and low pressures.
is optimised according to operating
period. conditions. The behavior of the
The force pressing the movable
This inspired us to develop new scroll decreases during low-load movable scroll has been stabilised to
technologies to enhance energy efficiency operation, resulting in
compression leakage from
increase efficiency during low-load
during low loads. movable parts. operation.
Utilising these technologies, Daikin’s new •Compressor efficiency*
VRV X and A series raise the standard for Intermediate pressure
New compressor
adjustment port
energy efficiency. Conventional compressor
Compressor efficiency
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% The intermediate pressure
(back pressure) optimises
the force pressing the
Load factor for the rated capacity movable scroll depending
on the operating condition.
energy savings during actual operation. * The new mechanism is used in all models except for RXUQ8A, RXQ6, 8, 16, and 18A. *Graph shown above is for illustration purpose only.
Software
Variable Refrigerant Temperature Smart Control (Fully Automatic Energy-saving Refrigerant Control) technology
Optimally supply only for the needed capacity of indoor units Other technologies to increase efficiency
Daikin developed Variable Refrigerant Temperature smart control by combining air volume control (VAV: valuable air Optimal amount of refrigerant is Standby power consumption is reduced
volume) for indoor units with conventional Variable Refrigerant Temperature control, which optimises compressor charged automatically The advanced oil temperature control reduces standby
speed by calculating the required load for the entire system and optimal target refrigerant temperature based on data The automatic refrigerant charge function automatically power consumption by up to 82.7%* annually compared to
sent from each indoor unit. Coordination with the air volume control reduces compressor load and minimises determines the optimal amount of refrigerant to be charged. conventional models. Standby power needed for preheating
operation loss based on detailed control. Variable Refrigerant Temperature smart control ensures energy savings and This function prevents a capacity shortage or energy loss refrigerator oil, which consumed substantial standby power,
comfortable air conditioning to meet actual operating conditions. due to excessive or insufficient refrigerant. was reduced to save energy when the air conditioner is
•Overview of the control (system control flow) stopped.
Different automatic energy-saving refrigerant control applies depending on the indoor units connected. Two compressors provide optimum operation* * Operation calculation conditions: VRV A series 14 HP
Location: Singapore
The outdoor unit is equipped with two compressors. Operation time: 08:00–18:00 on weekdays
Target indoor units
1
Temperature The speed of each compressor is automatically controlled to
Subject to Variable Refrigerant Subject to Variable Refrigerant
data received constantly optimise the overall efficiency depending on the Effective use of heat exchange area*
from indoor units
Temperature smart control Temperature control load. The start-stop loss during low-load operation is also The heat exchanger area is larger than that of conventional
minimised to increase efficiency. systems in which one compressor is operated.
C oord i nated co ntrol *Only available for VRV X series. This helps improve the efficiency of heat exchange during
low-load operation.
*Only available for VRV X series.
The following items are
The Variable Refrigerant Temperature
forecast and calculated based smart control also controls the airflow
on the required capacity: rate of indoor units automatically*, to
•Indoor fan air volume attain detailed energy-saving control. When one New Even when one
2
Select the target
3
•Target value of refrigerant * Airflow rate should be set to “Auto”. Compressor High-COP type compressor stops,
compressor stops,
refrigerant the heat exchange
temperature speed control (12 HP) area decreases to half. the heat exchange
temperature area does not decrease.
(12 HP)
The smooth control •Changes in the air-conditioned room temperature during low-load operation*
(which keeps the compressor Conventional air-conditioning method Fully automatic energy-saving Higher efficiency is provided during rated operation.
refrigerant control
running) saves energy and Changes in the room temperature: Large COP at 100% operation load
The power consumption attributed to the Changes in the room temperature: Small
ensures comfort during low-load star t-stop loss also increases the load. Wasted power consumption is also 5 4.82 4.75 4.71
Start minimised. 4.40 4.33
Cooling operation COP
No recalculation of charge amounts due Cools areas around Cools entire room Cools areas around Cools entire room
walls using using 4-way walls using using 4-way swing flow
to minor design changes locally 2-way horizontal flow swing flow 2-way horizontal flow
*Pre-charge amount changes according to conditions, 3. Reaches every When the target temperature is reached,
and there are cases when pre-charging is unnecessary. corner of the room normal operation (all-round flow) begins.
High reliability
Note: Results may vary depending on equipment conditions, room size,
and distance from indoor unit to walls.
3 4
Easy installation New indoor units are designed with Variable Refrigerant Temperature
Contribute to simple on-site installation and higher quality smart control to be more energy efficient and comfortable.
Automatic Refrigerant Charge Function
The automatic refrigerant charge function automates the charging of the proper refrigerant amount
Ceiling Mounted Cassette Type
and the closing of shut-off valves with just one press of the switch after pre-charging. Ceiling Mounted Cassette Ceiling Mounted Cassette
Simplified installation eliminates excessive and insufficient refrigerant charge amounts due to ( Round Flow with Sensing ) Type ( Round Flow ) Type
calculation mistakes, and this has led to higher installation quality.
No recalculation of charge amounts due Cools areas around Cools entire room Cools areas around Cools entire room
walls using using 4-way walls using using 4-way swing flow
to minor design changes locally 2-way horizontal flow swing flow 2-way horizontal flow
*Pre-charge amount changes according to conditions, 3. Reaches every When the target temperature is reached,
and there are cases when pre-charging is unnecessary. corner of the room normal operation (all-round flow) begins.
High reliability
Note: Results may vary depending on equipment conditions, room size,
and distance from indoor unit to walls.
3 4
Indoor unit lineup
Enhanced range of choices
A mixed combination of VRV indoor units and residential indoor units is enabled all in one system, opening the door to stylish and quiet indoor units.
New lineup smart Indoor units subject to Variable Refrigerant Temperature smart control
VRV indoor units basic Indoor units subject to Variable Refrigerant Temperature control
Residential indoor units with connection to BP units
25 35 50 60 71
Type Model Name Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 25 35 50 60 71
New
Ceiling Mounted Cassette New FXFSQ-AVM smart
capacity
Middle Static
Pressure Ceiling New FXSQ-PAVE smart
Mounted Duct
New FXMQ-PAVE smart
Ceiling Mounted
Duct
FXMQ-MAVE basic VRV indoor units only
Max. • If a system has indoor units subject to both Variable Refrigerant Temperature smart and Variable Refrigerant Temperature
Outdoor-Air FXMQ-MFVJU 64 indoor
units
control, the system is operated under Variable Refrigerant Temperature control.
• If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, Variable Refrigerant
Processing Unit Temperature smart control and Variable Refrigerant Temperature control are disabled.
* For connection of the air handling unit, please contact our sales office. Max. Residential indoor units only
32 indoor
units • BP units are necessary for residential indoor units. Only single outdoor unit (RXUQ8-20A and RXQ6-20A) can be connected.
• If a system has only residential indoor units, the system is operated under Variable Refrigerant Temperature control.
5 6
Indoor unit lineup
Enhanced range of choices
A mixed combination of VRV indoor units and residential indoor units is enabled all in one system, opening the door to stylish and quiet indoor units.
New lineup smart Indoor units subject to Variable Refrigerant Temperature smart control
VRV indoor units basic Indoor units subject to Variable Refrigerant Temperature control
Residential indoor units with connection to BP units
25 35 50 60 71
Type Model Name Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
Capacity Index 25 35 50 60 71
New
Ceiling Mounted Cassette New FXFSQ-AVM smart
capacity
Middle Static
Pressure Ceiling New FXSQ-PAVE smart
Mounted Duct
New FXMQ-PAVE smart
Ceiling Mounted
Duct
FXMQ-MAVE basic VRV indoor units only
Max. • If a system has indoor units subject to both Variable Refrigerant Temperature smart and Variable Refrigerant Temperature
Outdoor-Air FXMQ-MFVJU 64 indoor
units
control, the system is operated under Variable Refrigerant Temperature control.
• If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, Variable Refrigerant
Processing Unit Temperature smart control and Variable Refrigerant Temperature control are disabled.
* For connection of the air handling unit, please contact our sales office. Max. Residential indoor units only
32 indoor
units • BP units are necessary for residential indoor units. Only single outdoor unit (RXUQ8-20A and RXQ6-20A) can be connected.
• If a system has only residential indoor units, the system is operated under Variable Refrigerant Temperature control.
5 6
Specifications
Outdoor Units
Model RXUQ8AYM(W) RXUQ10AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AMYM(W) RXUQ20AMYM(W) RXUQ22AMYM(W) RXUQ24AMYM(W) RXUQ26AMYM(W) RXUQ28AMYM(W) RXUQ30AMYM(W) RXUQ32AMYM(W) RXUQ34AMYM(W)
― ― ― ― ― ― ― RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ16AYM(W)
Combination units
― ― ― ― ― ― ― RXUQ10AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 19,300 24,100 28,800 34,400 38,700 43,000 48,200 43,300 48,100 53,700 58,000 62,300 67,400 71,800 77,000 81,700
Cooling capacity Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000 172,000 191,000 213,000 230,000 247,000 268,000 285,000 305,000 324,000
kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 50.4 55.9 62.4 67.4 72.4 78.4 83.5 89.5 95.0
Power consumption kW 4.65 5.89 7.11 9.09 10.4 12.1 14.8 10.5 11.8 13.7 15.1 16.8 19.5 19.2 21.9 22.5
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 163 192 213 218 268 163+192 163+213 163+218 163+268 213+268 218+268
Dimensions (H×W×D) mm 1,657×1,240×765 (1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 273 312 318 273+312 273+318 312+318 318+318
Sound level dB(A) 55 57 60 61 65 59 61 62 65 66
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 8.1 11.3 11.4 11.5 11.7 8.1+11.3 8.1+11.4 8.1+11.5 8.1+11.7 11.4+11.7 11.7+11.7
Piping Liquid mm φ9.5 (Brazing) φ12.7 (Brazing) φ15.9 (Brazing) φ15.9 (Brazing) φ19.1 (Brazing)
connections Gas mm φ19.1 (Brazing) φ22.2 (Brazing) φ28.6 (Brazing) φ28.6 (Brazing) φ34.9 (Brazing)
Model RXUQ36AMYM(W) RXUQ38AMYM(W) RXUQ40AMYM(W) RXUQ42AMYM(W) RXUQ44AMYM(W) RXUQ46AMYM(W) RXUQ48AMYM(W) RXUQ50AMYM(W) RXUQ52AMYM(W) RXUQ54AMYM(W) RXUQ56AMYM(W) RXUQ58AMYM(W) RXUQ60AMYM(W)
RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W)
Combination units RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
― ― ― RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 86,000 91,200 96,300 101,000 105,000 110,000 115,000 120,000 126,000 129,000 134,000 139,000 144,000
Cooling capacity Btu/h 341,000 362,000 382,000 399,000 416,000 437,000 457,000 478,000 498,000 512,000 532,000 553,000 573,000
kW 100 106 112 117 122 128 134 140 146 150 156 162 168
Power consumption kW 24.2 26.9 29.6 27.2 28.9 31.6 34.3 34.0 36.7 36.3 39.0 41.7 44.4
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 268+268 163+218+268 163+268+268 213+268+268 268+268+268
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 318+318 273+318+318 312+318+318 318+318+318
Sound level dB(A) 68 67 68 69 70
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 11.7+11.7 8.1+11.7+11.7 11.4+11.7+11.7 11.7+11.7+11.7
Piping Liquid mm φ19.1 (Brazing) φ19.1 (Brazing)
connections Gas mm φ41.3 (Brazing) φ41.3 (Brazing)
Note: 1. Models with (W) are the outdoor units with heavy anti-corrosion specifications. Please refer to Engineering Data Book for details.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
7 8
Specifications
Outdoor Units
Model RXUQ8AYM(W) RXUQ10AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AMYM(W) RXUQ20AMYM(W) RXUQ22AMYM(W) RXUQ24AMYM(W) RXUQ26AMYM(W) RXUQ28AMYM(W) RXUQ30AMYM(W) RXUQ32AMYM(W) RXUQ34AMYM(W)
― ― ― ― ― ― ― RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ16AYM(W)
Combination units
― ― ― ― ― ― ― RXUQ10AYM(W) RXUQ12AYM(W) RXUQ14AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 19,300 24,100 28,800 34,400 38,700 43,000 48,200 43,300 48,100 53,700 58,000 62,300 67,400 71,800 77,000 81,700
Cooling capacity Btu/h 76,400 95,500 114,000 136,000 154,000 171,000 191,000 172,000 191,000 213,000 230,000 247,000 268,000 285,000 305,000 324,000
kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 50.4 55.9 62.4 67.4 72.4 78.4 83.5 89.5 95.0
Power consumption kW 4.65 5.89 7.11 9.09 10.4 12.1 14.8 10.5 11.8 13.7 15.1 16.8 19.5 19.2 21.9 22.5
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 163 192 213 218 268 163+192 163+213 163+218 163+268 213+268 218+268
Dimensions (H×W×D) mm 1,657×1,240×765 (1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 273 312 318 273+312 273+318 312+318 318+318
Sound level dB(A) 55 57 60 61 65 59 61 62 65 66
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 8.1 11.3 11.4 11.5 11.7 8.1+11.3 8.1+11.4 8.1+11.5 8.1+11.7 11.4+11.7 11.7+11.7
Piping Liquid mm φ9.5 (Brazing) φ12.7 (Brazing) φ15.9 (Brazing) φ15.9 (Brazing) φ19.1 (Brazing)
connections Gas mm φ19.1 (Brazing) φ22.2 (Brazing) φ28.6 (Brazing) φ28.6 (Brazing) φ34.9 (Brazing)
Model RXUQ36AMYM(W) RXUQ38AMYM(W) RXUQ40AMYM(W) RXUQ42AMYM(W) RXUQ44AMYM(W) RXUQ46AMYM(W) RXUQ48AMYM(W) RXUQ50AMYM(W) RXUQ52AMYM(W) RXUQ54AMYM(W) RXUQ56AMYM(W) RXUQ58AMYM(W) RXUQ60AMYM(W)
RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ8AYM(W) RXUQ12AYM(W) RXUQ12AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W)
Combination units RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ16AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
― ― ― RXUQ18AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ18AYM(W) RXUQ20AYM(W) RXUQ20AYM(W) RXUQ20AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 86,000 91,200 96,300 101,000 105,000 110,000 115,000 120,000 126,000 129,000 134,000 139,000 144,000
Cooling capacity Btu/h 341,000 362,000 382,000 399,000 416,000 437,000 457,000 478,000 498,000 512,000 532,000 553,000 573,000
kW 100 106 112 117 122 128 134 140 146 150 156 162 168
Power consumption kW 24.2 26.9 29.6 27.2 28.9 31.6 34.3 34.0 36.7 36.3 39.0 41.7 44.4
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 268+268 163+218+268 163+268+268 213+268+268 268+268+268
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
Machine weight kg 318+318 273+318+318 312+318+318 318+318+318
Sound level dB(A) 68 67 68 69 70
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 11.7+11.7 8.1+11.7+11.7 11.4+11.7+11.7 11.7+11.7+11.7
Piping Liquid mm φ19.1 (Brazing) φ19.1 (Brazing)
connections Gas mm φ41.3 (Brazing) φ41.3 (Brazing)
Note: 1. Models with (W) are the outdoor units with heavy anti-corrosion specifications. Please refer to Engineering Data Book for details.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
7 8
Specifications
Outdoor Units
Model RXQ6AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ18AMYM(W) RXQ20AMYM(W) RXQ22AMYM(W) RXQ24AMYM(W) RXQ26AMYM(W) RXQ28AMYM(W) RXQ30AMYM(W)
― ― ― ― ― ― ― ― RXQ8AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W)
Combination units
― ― ― ― ― ― ― ― RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 13,800 19,300 24,100 28,800 34,400 38,700 43,000 48,200 43,300 48,100 52,900 57,600 63,200 67,500 71,800
Cooling capacity Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 171,000 191,000 172,000 191,000 210,000 229,000 251,000 268,000 285,000
kW 16.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0 50.4 55.9 61.5 67.0 73.5 78.5 83.5
Power consumption kW 3.38 5.17 6.84 8.70 10.7 12.9 15.3 17.7 12.0 13.9 15.5 17.4 19.4 21.6 24.0
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 119 178 191 257 297 178+178 178+191 191+191 191+257
Dimensions (H×W×D ) mm 1,657×930×765 1,657×1,240×765 1,657×1,240×765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765)
Machine weight kg 175 185 233 276 312 175+185 185+185 185+233 185+276
Sound level dB(A) 56 57 59 60 61 65 60 61 62 63
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 5.9 6.7 6.8 7.4 8.2 8.4 11.8 5.9+6.7 5.9+6.8 6.7+6.8 6.8+6.8 6.8+7.4 6.8+8.2 6.8+8.4
Piping Liquid mm φ9.5 (Brazing) φ12.7 (Brazing) φ15.9 (Brazing) φ15.9 (Brazing) φ19.1 (Brazing)
connections Gas mm φ19.1 (Brazing) φ22.2 (Brazing) φ28.6 (Brazing) φ28.6 (Brazing) φ34.9 (Brazing)
Model RXQ32AMYM(W) RXQ34AMYM(W) RXQ36AMYM(W) RXQ38AMYM(W) RXQ40AMYM(W) RXQ42AMYM(W) RXQ44AMYM(W) RXQ46AMYM(W) RXQ48AMYM(W) RXQ50AMYM(W) RXQ52AMYM(W) RXQ54AMYM(W) RXQ56AMYM(W) RXQ58AMYM(W) RXQ60AMYM(W)
RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W)
Combination units RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W)
― ― ― ― ― RXQ18AYM(W) RXQ20AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ20AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 77,400 81,700 86,000 91,200 96,300 101,000 106,000 112,000 116,000 120,000 125,000 129,000 134,000 139,000 144,000
Cooling capacity Btu/h 307,000 324,000 341,000 362,000 382,000 399,000 420,000 444,000 461,000 478,000 495,000 512,000 532,000 553,000 573,000
kW 90.0 95.0 100 106 112 117 123 130 135 140 145 150 156 162 168
Power consumption kW 26.0 28.2 30.6 33.0 35.4 32.7 35.1 36.7 38.9 41.3 43.5 45.9 48.3 50.7 53.1
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 257+257 257+297 297+297 191+191+257 191+191+297 257+257+257 257+257+297 257+297+297 297+297+297
(1,657×930×765)+(1,657×930×765)+
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
(1,657×1,240×765)
Machine weight kg 233+276 276+276 276+312 312+312 185+185+276 185+185+312 233+233+276 233+276+276 276+276+276 276+276+312 276+312+312 312+312+312
Sound level dB(A) 64 66 68 65 67 65 66 68 69 70
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 7.4+8.4 8.2+8.4 8.4+8.4 8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 7.4+7.4+8.4 7.4+8.2+8.4 7.4+8.4+8.4 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8
Piping Liquid mm φ19.1 (Brazing) φ19.1 (Brazing)
connections Gas mm φ34.9 (Brazing) φ41.3 (Brazing) φ41.3 (Brazing)
Note: 1. Models with (W) are the outdoor units with heavy anti-corrosion specifications. Please refer to Engineering Data Book for details.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
9 10
Specifications
Outdoor Units
Model RXQ6AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ18AMYM(W) RXQ20AMYM(W) RXQ22AMYM(W) RXQ24AMYM(W) RXQ26AMYM(W) RXQ28AMYM(W) RXQ30AMYM(W)
― ― ― ― ― ― ― ― RXQ8AYM(W) RXQ8AYM(W) RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W)
Combination units
― ― ― ― ― ― ― ― RXQ10AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 13,800 19,300 24,100 28,800 34,400 38,700 43,000 48,200 43,300 48,100 52,900 57,600 63,200 67,500 71,800
Cooling capacity Btu/h 54,600 76,400 95,500 114,000 136,000 154,000 171,000 191,000 172,000 191,000 210,000 229,000 251,000 268,000 285,000
kW 16.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0 50.4 55.9 61.5 67.0 73.5 78.5 83.5
Power consumption kW 3.38 5.17 6.84 8.70 10.7 12.9 15.3 17.7 12.0 13.9 15.5 17.4 19.4 21.6 24.0
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 119 178 191 257 297 178+178 178+191 191+191 191+257
Dimensions (H×W×D ) mm 1,657×930×765 1,657×1,240×765 1,657×1,240×765 (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×1,240×765)
Machine weight kg 175 185 233 276 312 175+185 185+185 185+233 185+276
Sound level dB(A) 56 57 59 60 61 65 60 61 62 63
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 5.9 6.7 6.8 7.4 8.2 8.4 11.8 5.9+6.7 5.9+6.8 6.7+6.8 6.8+6.8 6.8+7.4 6.8+8.2 6.8+8.4
Piping Liquid mm φ9.5 (Brazing) φ12.7 (Brazing) φ15.9 (Brazing) φ15.9 (Brazing) φ19.1 (Brazing)
connections Gas mm φ19.1 (Brazing) φ22.2 (Brazing) φ28.6 (Brazing) φ28.6 (Brazing) φ34.9 (Brazing)
Model RXQ32AMYM(W) RXQ34AMYM(W) RXQ36AMYM(W) RXQ38AMYM(W) RXQ40AMYM(W) RXQ42AMYM(W) RXQ44AMYM(W) RXQ46AMYM(W) RXQ48AMYM(W) RXQ50AMYM(W) RXQ52AMYM(W) RXQ54AMYM(W) RXQ56AMYM(W) RXQ58AMYM(W) RXQ60AMYM(W)
RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W)
Combination units RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ12AYM(W) RXQ12AYM(W) RXQ14AYM(W) RXQ16AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W)
― ― ― ― ― RXQ18AYM(W) RXQ20AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ18AYM(W) RXQ20AYM(W) RXQ20AYM(W) RXQ20AYM(W)
Power supply 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz 3 phase 4-wire system, 380-415V/ 380V, 50Hz/ 60Hz
kcal/h 77,400 81,700 86,000 91,200 96,300 101,000 106,000 112,000 116,000 120,000 125,000 129,000 134,000 139,000 144,000
Cooling capacity Btu/h 307,000 324,000 341,000 362,000 382,000 399,000 420,000 444,000 461,000 478,000 495,000 512,000 532,000 553,000 573,000
kW 90.0 95.0 100 106 112 117 123 130 135 140 145 150 156 162 168
Power consumption kW 26.0 28.2 30.6 33.0 35.4 32.7 35.1 36.7 38.9 41.3 43.5 45.9 48.3 50.7 53.1
Casing colour Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown Without (W): Ivory white (5Y7.5/1), With (W): Metallic brown
Airflow rate m3/min 257+257 257+297 297+297 191+191+257 191+191+297 257+257+257 257+257+297 257+297+297 297+297+297
(1,657×930×765)+(1,657×930×765)+
Dimensions (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)+(1,657×1,240×765)
(1,657×1,240×765)
Machine weight kg 233+276 276+276 276+312 312+312 185+185+276 185+185+312 233+233+276 233+276+276 276+276+276 276+276+312 276+312+312 312+312+312
Sound level dB(A) 64 66 68 65 67 65 66 68 69 70
Operation range ℃DB 10 to 49 10 to 49
Type R-410A R-410A
Refrigerant
Charge kg 7.4+8.4 8.2+8.4 8.4+8.4 8.4+11.8 11.8+11.8 6.8+6.8+8.4 6.8+6.8+11.8 7.4+7.4+8.4 7.4+8.2+8.4 7.4+8.4+8.4 8.2+8.4+8.4 8.4+8.4+8.4 8.4+8.4+11.8 8.4+11.8+11.8 11.8+11.8+11.8
Piping Liquid mm φ19.1 (Brazing) φ19.1 (Brazing)
connections Gas mm φ34.9 (Brazing) φ41.3 (Brazing) φ41.3 (Brazing)
Note: 1. Models with (W) are the outdoor units with heavy anti-corrosion specifications. Please refer to Engineering Data Book for details.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
9 10
PVVPH1739aprv
Preview
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
Exceeding boundaries
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
with innovative energy savings
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
•Specifications, designs and other content appearing in this brochure are current as of August 2017 but subject to change without notice.