DIRECT LOW PRESSURE

www.kanexfire.com

AUTOMATIC FIRE SUPPRESSION SYSTEM


SYSTEM DETAILS
The KATS-Fire Suppression system is a Automatic Triggering Self
actuating system that is designed for localized fire suppression. The
system works by using pressurized Fire detection tubing that is installed
throughout the risk area. This tubing is heat sensitive and when
subjected to a temperature above 110? C, or when touched by flame,
the tube will rupture and release the clean agent trough formed
Extinguishing Agent
nozzle.
HFC 236fa UL Listed HFC 227ea UL Listed FK 5-1-12

• Propellant : Nitrogen Gas • System designed as per NFPA2001


• Service Pressure : 15 bar • Operating Temperature : -20? C to
• Pressure tested : 35 bar +55? C
• Factory Tested: 35 bar
INSTALLATION
Fire Suppression System

It is mandatory to done installation from KANEX Authorized Personnel


Only.
CARE & MAINTENANCE
Inspect monthly or more frequently when circumstances require by a
trained professional:
check that all parts are free from damage or corrosion, cylinders are
firmly mounted in the bracket and detection tubing are secure and free
from obstructions.
Record date of inspection or recharge. If system fails above inspection
use only a qualified service agency to safely restore system to
operating condition.
This unit to be pressurized as intended.
At least semi-annually, the pressure shall be checked. A cylinder
shall be refilled or replaced when pressure loss (adjusted for
KATS

temperature) exceeds 10%

WARNING :
THE BALL VALVE SHALL BE IN THE CLOSED POSITION EXCEPT WHEN THE
CYLINDER ASSEMBLY IS CONNECTED TO THE PRESSURIZED
DETECTION/DISCHARGE TUBING OR WHILE THE CYLINDER IS BEING FILLED.
The discharge of clean agent system to extinguish the fire can result in
potential hazard to personnel from the natural form of the clean agent or
: from the product of combustion that result from exposure of agent with fire or
hot surfaces. unnecessary exposure of personnel either to natural agent or
Gross Wt. : product of decomposition shall be avoided.

Capacity :�
Sr No. :
Batch No. : Designed, Manufactured by:
Mfg. Yr. : KANADIA FYR FYTER PVT. LTD.
Model No. :
Content : WORKS :
Plot no-7/8 ,Paras Industrial Estate, Near
REF DUE Garibshah Pir, LPCB
Sihor - 364240, Gujarat.
LOGO
KATS-2 E-mail : marketing@kanexfire.com
Website : www.kanexfire.com