You are on page 1of 2

00 DRAWING ISSUE FOR CLIENT APPROVAL W.

S 12-06-2023

L U T I O NS
00

SO
REV. TAG DISCRIPTION / DETAIL OF REVISION DATE
PV NAME

ER

T
FOR APPROVAL

POW

LT
D
FOR MANUFACTURING

AS BUILT

DRAWING TITLE:
GENERAL ARRANGEMENT
LV PANEL LAYOUT PLAN
CLIENT:

Neophar
POWER SOLUTIONS PVT LTD PROJECT:

CABLE TRAY
POWER AND TELECOM SERVICES COMPANY CONSULTANT:
CABLE TRAY

-
Address: Plot#166/1, Mirza Street, 6km Raiwind Road Lahore Pakistan -
Contact#: +92-42-35320533, +92 -301-8498388, +92-333-4465863 MANUFACTURING:

E-mail: info@powersolutions.pk, Web: www.powersolutions.pk L U T I O NS P


SO V
POWER SOLUTIONS PVT LTD

ER

T
POW

LT
POWER AND TELECOM SERVICES COMPANY

D
Address: Plot#166/1, Mirza Street, 6kmRaiwind
Road Lahore Pakistan
Contact#: +92-42-35320533, +92-301-8498388,
+92-333-4465863
E-mail: info@powersolutions.pk
Web: www.powersolutions.pk

Authorized Channel Partner


DRAWN/DESIGN: WS
COVER SHEET
CHECKED BY: WS EcoXpert
PURCHASE ORDER#:
APPROVED BY: M.M
N/A Schneider
REV: 00
WORK ORDER#: Electric
N/A
DEPARTMENT: DRAWING#: Drawing Status: Sheet#:

DESIGN & PURPOSEL PSPL-5323NEOP-REV00 √ FOR MANUFACTURING 01 02


187,5
DOOR LOCK

DOOR LOCK

DOOR LOCK
WAPDA LIVE PHASE INDICATION GENSET LIVE PHASE INDICATION
L1 L2 L3 L3 L2 L1

000
300 415 415 500 0 5 Sec

OFF IND. ON IND. ON IND. OFF IND. U- U+ Time Relay

PFI METER

430
PFI 8888
RELAY

425
MULTI METER TP

8888
8888
8888
ON IND. ON IND. ON IND. ON IND.

OFF IND. OFF IND. OFF IND. OFF IND.


OFF PB ON PB ON PB OFF PB

AOM SS AOM SS
ON PB ON PB ON PB ON PB E/STOP
HANDLE

HANDLE

HANDLE
L
OFF PB OFF PB OFF PB OFF PB

105

400

390
AOM SS AOM SS A250

1475

1405
425

475
V A 166
DOOR LOCK

DOOR LOCK

DOOR LOCK
O

375

375

500
425
P R

175

175

187,5
A P
NOTES:
1. ALL DIMENSIONS ARE IN mm.
R
2.
3.
4.
ENCLOSURE SHOULD BE 2mm THICK (MS-14SWG).
ALL BREAKER'S ARE ACCESSIBLE WHEN FRONT DOORS ARE OPENED.
ALL CABLE'S ARE TERMINAL WHEN FRONT & REAR DOOR ARE OPENED.
F O
5. CABLE ENTRY INCOMING SHELL BE FROM BOTTOM.
6. CABLE ENTRY OUTGOING SHELL BE FROM TOP.
7. GENERAL TOLERANCE ±5 mm. COPPER CHART:
8. PAINT OF ENCLOSURE POWDER COATED THICKNESS 70-100 MICRON. MAIN BUS BAR: 1(20x5)mm PER PHASE
9. POWDER COATED PAINT RAL-7032. NEUTRAL BUS BAR: 1(15x5)mm
10. PROTECTION CLASS IP-42 (INDOOR TYPE) FLOOR STANDING.
EARTH BUS BAR: 1(15x5)mm
INTERCONNECTION:
11. PANELS SUITABLE FOR FRONT & REAR ACCESS.
MCCB 250A: 1(20x5)mm PER PHASE
12. PANEL FRONT SIDE OF LOUVER & REAR SIDE OF EXHAUST FAN. MC 265A: 1(20x5)mm PER PHASE
13. PANEL LIGHT & LIMIT SWITCH ARE INSTALL ON TOP SIDE OF PANEL. MCCB 125A: 1(15x5)mm PER PHASE
14. PANELS DESIGN IS BOLTED TYPE. MCCB 100A: 1(15x5)mm PER PHASE
L U T I O NS P MANUFACTURING: Authorized Channel Partner DRAWING TITLE: CLIENT:
SO V
POWER SOLUTIONS PVT LTD
GENERAL ARRANGEMENT OF DRAWN/DESIGN: WS
Neophar
ER

MAIN ATS WITH 50kVAR PFI PANEL


POW

LT

POWER AND TELECOM SERVICES COMPANY


EcoXpert
D

Address: Plot#166/1, Mirza Street, 6kmRaiwind


CONSULTANT: PROJECT:
CHECKED BY: WS
-
Road Lahore Pakistan
Contact#: +92-42-35320533, +92-301-8498388,
Schneider Drawing Status: REV: DEPARTMENT:
CABLE TRAY
DRAWING#: Sheet#:
E-mail:
Web:
+92-333-4465863
info@powersolutions.pk
www.powersolutions.pk
Electric FOR APPROVAL FOR MANUFACTURING AS BUILT 00
APPROVED BY: M.M
DESIGN & PURPOSEL PSPL-5323NEOP-REV00 02 02

You might also like