Grid Solutions

MiCOM Agile
P141, P142, P143 & P145
Feeder Management Relays Protection and Control
Feeder protection for solidly, impedance,
P14x is an integrated solution for the complete protection, control and monitoring of Petersen coil earthed and isolated systems
overhead lines and underground cables from distribution to transmission voltage levels. 9 stages of advanced load shedding and
restoration logic
The wide range of auxiliary functions provides the user with sufficient information to
Single box solution for high impedance
efficiently maintain the power system and its components, including circuit-breakers, CTs,
busbar protection with integrated
VTs, etc. buswire supervision
Digital inputs - deliver ESI 48-4 EB2 noise
A customisable, friendly, multi-lingual user interface and programmable graphical scheme
immunity and are suitable for H7 trip
logic allow simple and flexible applications on any network. In addition, the P145 has circuit supervision
integrated user function keys and tri-colour programmable LEDS, which provide a cost-
effective solution for full feeder scheme applications.
Application Flexibility
Use the function keys to replace control scheme switches and save on engineering time 1 A and 5 A in the same relay
and wiring costs.
Programmable function keys
and LEDs (P145)
With optional High-Speed/High-Break contacts, the high break performance ensures no
burn-out of contacts during normal operations or situations such as breaker failure or Customisable menus
defective CB auxiliary contacts. The need for external electromechanical trip relays can be Control of up to 9 switchgear elements
reduced/removed by transferring the high rating and durability duties to the MiCOM Harsh environmental coating as standard
device, thus providing further application and cost benefits.

Connecting the relay to virtually any kind of substation automation system or SCADA is made Advanced
possible by the wide range of updated communications protocols, including IEC 61850.
Communications
A range of hardware interfaces are available for easy integration into any new or legacy Wide range of supported protocols
system. Courier/K-Bus, Modbus, IEC 60870-5-103,
DNP 3.0 (RS485 or Ethernet) and IEC 61850
The MiCOM P14x Agile series extends the IEC 61850-8-1 station bus to include Parallel Latest communication protocol implementation
Redundancy Protocol (PRP), and High-availability Seamless Redundancy (HSR) which offers with IEEE 1588 precision-time (PTP)
a vendor-interoperable solution to implement redundant communications. It has the Software switchable between IEC 61850 Ed. 1 /
advantage of taking zero time to recover from a failure, as parallel alternative paths are Ed. 2 support.
continually operative. This compares to 25 ms or more healing time for legacy techniques Redundant communications with zero
such as Rapid Spanning Tree Protocol (RSTP). downtime using optional PRP/HSR protocols

The P14x Agile supports IEC Edition 1 & 2 compliance, comprehensive test mode and
simulation capability, editable IEC 61850 Logical Device and Logical Node naming, PTP Cyber Security
(IEEE 1588) time synchronisation, and SNMP. Enhanced compliance with NERC CIP,
NISTIR 7628 and EU NIS foundation norms
Role-based access control using the
industry-standard Radius protocol
Secure Syslog audit trail recording

Imagination at work
P14x Feeder Management Relays

Protection Functions Overview

2
GEGridSolutions.com
P14x Feeder Management Relays

Application
The MiCOM P14x Agile range is suitable for all applications where overcurrent protection
is required. It is suitable for solidly earthed, impedance earthed, Petersen coil earthed and
isolated systems.

The first application shows a parallel transformer protection where the P141 replaces
many of the discrete protection elements normally associated with the LV side of the
transformer. The protection includes non-directional and directional phase overcurrent
and earth fault, restricted earth fault and circuit-breaker failure protection. The second
application shows a P143 protecting a plain feeder using phase overcurrent, sensitive
earth fault, negative sequence overcurrent, thermal protection and breaker failure
protection. The integral autorecloser with check synchronising can be configured to grade
with downstream reclosers.

The MiCOM P145 relay is especially suitable where a complete scheme


solution is required and comprises function keys for integral scheme
control functionality.
.
Management Functions Typical applications of P14x

In addition to the wide range of protection functions listed in the table, all relays in the
P14x range are provided with the following measurement, control, monitoring, Programmable scheme logic
post fault analysis and self-diagnostic functions: Programmable allocation of digital
Measurement of all instantaneous & integrated values inputs and outputs
Circuit-breaker control, status & condition monitoring Sequence of events recording
Trip circuit and coil supervision Comprehensive disturbance recording
4 alternative setting groups (waveform capture)
Control inputs User configurable LEDs
Fault locator Local and remote communications ports
Multiple communications protocol and
interface options
Time synchronisation
Fully customisable menu
Multi-level password protection
Power-up diagnostics and continuous
self-monitoring of relay
User-friendly settings and analysis
software
Read-only mode
Enhanced opto input time stamping
Check synchronising with optional
compensation for CB closing delay -
contacts touch at optimal
synchronisation

Functional overview
( See Protection Functions Overview for description of ANSI codes)

GEGridSolutions.com 3
P14x Feeder Management Relays

Phase Overcurrent Standard Earth Fault Wattmetric


Six independent stages are available for There are two standard earth fault As an alternative to the directional
each phase overcurrent element. Each elements, each with four independent earthfault characteristic, a directional
stage may be selected as non-directional stages: Icos characteristic can be used for Petersen
or directional (forward/ reverse). All The first element operates from coil earth fault protection using the
stages have definite time delayed measured quantities - Earth fault sensitive earth fault input.
characteristics and three of the stages current which is directly measured
may also be independently set to one of using a separate CT, or residual Economical Busbar Protection
ten IDMT curves (IEC and IEEE). A user- connection of the three line CTs.
programmable curve tool is provided Each stage of overcurrent and earth fault
The second standard earth fault protection can be blocked by an optically
within the S1 Agile tool suite. The tool can
element operates from a residual isolated input. This enables overcurrent
be used to provide customised
current that is derived internally and earth fault protection to integrate
Operate/Reset curves, providing
from the summation of the into a blocked overcurrent busbar
additional flexibility and allowing the use
3-phase currents. protection scheme.
of the total feeder capacity with complete
protection.
All earth fault elements have the same
directionality and IDMT characteristics as Cold Load Pick-up Logic
If a standard curve is not suitable for the
the phase overcurrent element. Both earth Cold load pick-up temporarily raises the
application, the user can program and
fault elements may be enabled at the overcurrent settings following closure of
upload a customised curve to the relay.
same time providing directional earth fault the circuit-breaker, allowing the
protection and back-up standby earth protection settings to be set closer to the
The IDMT stages have a programmable
fault protection in the same device. The load profile.
reset timer for grading with electro-
directionality of the earth fault elements is
mechanical relays, to reduce autoreclose
provided by either residual voltage or
dead times and to reduce clearance times
negative sequence voltage.
Restricted Earth Fault
where intermittent faults occur.
Restricted earth fault (REF) provides
The phase fault directional elements are Sensitive Earth Fault protection for transformer faults, avoiding
internally polarised by quadrature phase- the need to install a separate discrete
A core balance CT should be used to relay. It can operate in high or low
phase voltages and will make a correct
drive the sensitive earth fault function. impedance differential mode.
directional decision down to:
The directionality of the sensitive
0.5 V (Vn = 100 - 120 V) or
earth fault element is provided by the
2.0 V (Vn = 380 - 480 V).
residual voltage.
A synchronous polarising signal is
maintained for 3.2 s after voltage collapse
to ensure that the instantaneous and
time delayed overcurrent elements
operate correctly for close-up
3-phase faults.

REF biased differential characteristics Choice of IDMT characteristics

4
GEGridSolutions.com
P14x Feeder Management Relays

2nd Harmonic Blocking RMS Thermal Overload Frequency


The 2nd harmonic blocking detects high Thermal overload protection provides Nine stages each of: overfrequency,
inrush current inflows that occur when both alarm and trip stages. The thermal underfrequency, rate of change of
transformers or machines are connected. element may be set with either a single frequency, frequency supervised rate of
The function will block the phase time constant characteristic for the change of frequency, average rate of
overcurrent, earth fault, sensitive earth protection of cables or dry transformers, change of frequency, frequency based load
fault and negative sequence overcurrent. or a dual time constant characteristic to shedding during severe system
protect oil-filled transformers. In the disturbances.
Voltage Controlled Overcurrent/ event of loss of auxiliary supply,
the thermal state is stored in Broken Conductor
Voltage Restrained Overcurrent non-volatile memory.
In order to provide backup protection for The broken conductor protection detects
phase faults, an element is included which Under/overvoltage unbalanced conditions caused by broken
can be set as either voltage controlled conductors, maloperation of single phase of
& Rate of Voltage Change switchgear or by single phasing conditions.
overcurrent or voltage restrained
overcurrent. The timing characteristic can Under/overvoltage protection may be It operates on the ratio of I2 to I1.
be set as either definite time or IDMT. configured to operate from either phase-
phase or phase-neutral quantities. Four Phase Segregated Power
Negative Sequence Overcurrent independent stages with definite time
Two stages of power protection are
elements are available, one of the stages
Negative sequence overcurrent protection can also be configured to an inverse provided and each stage can be
can be set as either non-directional or characteristic. Two stages of rate of independently configured to operate as
directional (forward /reverse) and can change of voltage protection elements overpower or underpower and forward or
operate for remote phase-phase and are also available, which can be set reverse direction. The relays provide a
phase earth faults even with delta-star independently. standard 3-phase power protection
transformers present. element and also a single-phase power
protection element.
Residual Overvoltage
Residual overvoltage protection is Sensitive Power
available for detecting earth faults in high
impedance earthed or isolated systems. Two stages of sensitive power protection
The neutral voltage is derived from the are provided and these can be
3-phase voltage inputs. Four independent independently selected as reverse power,
measuring elements with definite time overpower, low forward power or disabled
characteristics are available and one of depending on the operating conditions.
the elements can also be configured to
have an inverse characteristic. Load Encroachment
Load encroachment (load blinder), an
impedance based feature avoids tripping
for heavy load flows.

Voltage Transformer Supervision


Voltage transformer supervision is
provided to detect loss of one, two or
three VT signals, providing indication and
inhibition of voltage dependent protection
elements. An optically isolated input may
also be configured to initiate the voltage
transformer supervision alarm and
blocking when used with MCBs or other
external forms of voltage transformer
supervision.

Current Transformer Supervision


Current transformer supervision is
provided to detect loss of phase CT signals
and inhibit the operation of current
dependent protection elements.
Programmable scheme logic editor (S1 Agile) offers intuitive drag-and-drop logic customising

GEGridSolutions.com 5
P14x Feeder Management Relays

Programmable Scheme Logic Indication (P145)


Programmable scheme logic allows the user to customise the protection and control Eighteen tri-colour LEDs are available for
functions. The programmable scheme logic comprises gate logic and general purpose user programming. The LED colours (red,
timers. The gate logic includes OR, AND and majority gate functions, with the ability to green or yellow) are driven via digital
invert the inputs and outputs and provide feedback. The programmable scheme logic is databus signals in PSL and can be
configured using the graphical S1 Agile PC-based support software. programmed to indicate up to four
conditions/states, for example:
The system is optimised (event driven) to ensure that the protection outputs are not Off -Not in service
delayed by the PSL operation. Multiple protection functions, logic and control functions
Red -CB closed
may be enabled, without deterioration in performance - the platform is fully
deterministic. Green -CB open
Yellow -CB not healthy
Single Box Solution: High impedance Busbar Protection
with Integrated Buswire Supervision Cicuit Breaker Failure Protection
High impedance busbar protection is an alternative to biased differential bus protection. Two-stage circuit-breaker failure
In the latter case, stability for external faults is achieved by a percentage bias slope. protection may be used for tripping
Conversely, in high impedance schemes the stability is achieved by virtue of a deliberate upstream circuit-breakers and for
high impedance (a resistor) being added into the spill current path of the CT secondary re-tripping the local circuit-breaker if
circuit. This ensures that the differential current due to any saturated CT is minimised to a required. The circuit-breaker failure logic
level which does not cause protection zone operation. may also be initiated externally from other
protection devices if required. The
Should a CT become open-circuited in the scheme, this poses a fire and personnel safety undercurrent elements used in the CB fail
risk in the substation. Depending on the level of load current flowing, zone elements may reset mechanism have been enhanced to
also be at risk of spurious pickup. Additionally, due to the high impedance in the scheme, detect the breaker opening in real-time,
the buswires may experience a prolonged overvoltage, for which they may not be even when there are subsidence currents
thermally-rated. Supervision, to detect such scenarios, is essential. in the CT secondary caused by the
remnant flux.
In a traditional solution, GE's MVTP relay is added, to detect open circuit scenarios by
sensitive overvoltage detection. The P14x scheme now offers the advantage that in a
numerical scheme, this function is now integrated in the same device as for the zone Switchgear Control
differential element, to minimise the space occupied in relay panels, optimise cost and Circuit-breaker control is available from
engineering time, and offer faster commissioning. The relaying for the zone is in one box. the front panel user interface, optically
isolated inputs and remotely via the
substation communications. 8 sets of
switch control logic, LN XSWI for
controlling/monitoring of disconnectors
and earth switches are also available.

Typical high-impedance protection scheme - GE's P14x Agile relay provides full bus protection and
scheme supervision

6
GEGridSolutions.com
P14x Feeder Management Relays

Autoreclose Disturbance Records Circuit Breaker Condition


with Check Synchronising The internal disturbance recorder has Monitoring
The P142, P143 and P145 provide three- 8 analogue, 32 digital and 1 time channel. The circuit-breaker condition monitoring
pole multi-shot autoreclose. The user may Approximately 50 records of 0.5 s duration features include:
select a single, two, three or four shot can be stored. All channels and the trigger
Monitoring the number of breaker trip
autoreclose cycle, with independently source are user configurable. Disturbance
operations
settable dead times and reclaim time. records can be extracted from the relay via
the remote communications and saved in Recording the sum of the broken
Autoreclose can be initiated from the
the COMTRADE format. These records may current quantity
internal protection elements or from
external protection via an opto input. be examined using S1 Agile or any suitable Monitoring the breaker operating time
Advanced features include live line working software programme. Fault frequency counter
and sequence coordination (co-ordination
with downstream reclosing equipment). Local and Remote
The P143 and P145 also include check
synchronisation. Communications
Two communications ports are available
Measurement and Recording as standard: a rear port providing remote
Facilities communications and a front port
providing local communications.
The P14x series is capable of measuring
and storing the values of a wide range of The front port has been designed for use
quantities. All events, fault and disturbance with S1 Agile, which fully supports
records are time tagged to a resolution of 1 functions within the relay by providing the
ms using an internal real-time clock. An ability to: program the settings off-line,
optional IRIG-B port is also provided for Disturbance records configure the programmable scheme
accurate time synchronisation. logic, extract and view events,
disturbance and fault records, view the
Measurements Trip Circuit Supervision measurement information dynamically
and perform control functions.
The measurements provided, which may Supervision of the trip circuit in both
be viewed as primary or secondary values, circuit-breaker open and closed states The default remote communications are
can be accessed via the back-lit liquid can be realised using the optically based on RS485 voltage levels.
crystal display, or the communications isolated inputs and programmable Any of the protocols listed below can be
ports. A wide range of instantaneous and scheme logic. chosen at the time of ordering:
integrated parameters are available. The
Courier / K-bus
list includes measured signals like phase Fault Records
currents and voltages and computed Modbus
signals like power, frequency, energy, etc. Records of the last 5 faults are stored in IEC 60870-5-103 (optical interface also
Phase currents and phase to neutral battery-backed memory. available)
voltages are available in true rms and The information provided in the fault
record includes: DNP 3.0
fundamental quantities.
Indication of faulted phase IEC 61850 (over 100 Mbit/s,
fibre/copper Ethernet)
Fault Location Protection operation
A fault location algorithm provides Active setting group
distance to fault in miles, kilometres, ohms Date and time
or percentage of line length. Fault location
Relay and CB operating time
Event Recording
Currents, voltages and frequency
Up to 512 time-tagged event records are
stored in battery-backed memory and can
be extracted using the communications Industry-leading hardware reliability
ports or viewed on the front panel display.
with best-in-class digital inputs

GEGridSolutions.com 7
A variety of Communications Interfaces
IEC 61850 is available when the optional Ethernet port is ordered.
IEC 61850 offers high-speed data exchange, peer-to-peer
communications, reporting, disturbance record extraction and
time synchronisation. Redundant Ethernet is also available with
RSTP, PRP and HSR delivered in a single order option.
The P14x has 128 virtual inputs with an improved GOOSE
performance.

An optional second rear courier port is available, which may be


configured as RS232, RS485 or K-Bus.
.

Diagnostics
Automatic tests performed, including power-on diagnostics and
continuous self-monitoring, ensuring a high degree of reliability. Expansion cards are available to increase the number of digital
Test features available on the user interface display input inputs and outputs for the P142, P143 and P145. Also, depending
quantities and the states of the digital inputs and relay outputs. on the relay model, up to eight High Speed-High Break contacts
are available as an option. This will protect against burnt contacts
Hardware due to a stuck breaker or defective breaker auxiliary contact
conditions.
All models in the P14x series include:
A back-lit liquid crystal display The optically isolated inputs are independent. The digital status
An optional IRIG-B port input thresholds are programmable. Intelligent burden switching
and compliance with the ESI48-4EB2 standard provides immunity
A USB port & an RS485 port to false wiring pickup equivalent to the level offered by high
An optional RS232/RS485/K-Bus port burden trip relays such as MVAJ. The relay outputs may be
An optional Ethernet port for IEC 61850 protocol configured as latching or self reset. All CT connections have
integral shorting.
A download/monitor port
N/O and N/C watchdog contacts In addition to the standard -25°C to + 55°C operating
1 A/5 A dual rated CTs temperatures claim as per IEC 60255-6, the Px40 range has
proven withstand capability at extremes of temperature as per
IEC 60068-2. These onerous tests were passed at -40°C and
+85°C for 96 continuous hours in each case.

MiCOM P40 Agile


GE's philosophy is one of continuous improvement in our
products and solutions. Our emphasis on communications in
MiCOM has become a focus which secures our leadership in
digital substations. To mark this phase of evolution, the brand
“P40 Agile” is applied to the range. P40 Agile is a mark of
performance and quality, proudly available from GE.

GEGridSolutions.com
For more information please contact:
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
GE trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark
Grid Solutions of Schneider Automation.

GE and the GE monogram are trademarks of General Electric Company.


Worldwide Contact Centre GE reserves the right to make changes to specifications of products described at any time without
Web: www.GEGridSolutions.com/contact notice and without obligation to notify any person of such changes.
Phone: +44 (0) 1785 250 070 P14x-Brochure-EN-2019-11-Grid-GA-0629. © Copyright 2019, General Electric Company.
All rights reserved.

Imagination at work

You might also like