SIPROTEC 5 Devices and Fields of Application

Transformer Differential Protection – SIPROTEC 7UT85

Description
The SIPROTEC 7UT85 transformer differential protection device
has been designed specifically for the protection of two-winding
transformers (2 sides). It is the main protection for the trans-
former and contains many other protection and monitoring
functions. The additional protection functions can also be used
as backup protection for subsequent protected objects (such as
cables or lines). The modular expandability of the hardware also
supports you in this process. With its modular structure, flexi-
bility, and the high-performance DIGSI 5 engineering tool,
SIPROTEC 7UT85 offers future-oriented system solutions with
high investment security and low operating costs.

Main function 1 differential protection function (standard or


auto transformer) with additional stabilization;
up to 2 restricted ground-fault protection func-
tions
Usable measuring 5 x 3-phase current measuring points, 3 x
[SIP5_GD_SS_W3, 1, --_--]
points 1-phase current measuring points, 3 x 3-phase
voltage measuring points; expandable to 3 Figure 2.11/5 SIPROTEC 7UT85 Transformer Differential Protection
sides (1/2 Device = Standard Variant P1)
Inputs and outputs 2 predefined standard variants with 8 current
transformers, 7 to 19 binary inputs, 7 to of inrush and overexcitation processes, safe behavior in case
23 binary outputs
of current-transformer saturation with different degrees of
Hardware flexibility Flexibly adjustable and expandable I/O quantity saturation
structure within the scope of the SIPROTEC 5
modular system. • Adaptive adaptation of the operate curve to the transformer
Housing width 1/3 × 19 inches to 2/1 × 19 inches tap position
• Increased sensitivity with ground faults near the neutral point
Benefits through a separate restricted ground-fault protection

• Safety due to high-performance protection functions • Additional current and voltage inputs can be added for
standard protection functions, such as overcurrent, voltage, 2.11
• Data security and transparency over the entire lifecycle of the frequency protection, etc.
plant, saving time and money
• Purposeful and easy handling of devices and software thanks • Arc protection
to a user-friendly design • Voltage-controller function ANSI 90V for two-winding trans-
formers, three-winding transformers, and grid coupling trans-
• Increased reliability and quality of the engineering process formers with parallel control (master/follower, circulating
• Highest availability even under extreme environmental condi- reactive current minimization)
tions by “conformal coating“ of electronic boards
• Graphical logic editor to create high-performance automation
• Cyber security in accordance with NERC CIP and BDEW White- functions in the device
paper requirements
• Up to 4 pluggable communication modules, usable for
• High-performance communication components warrant safe different and redundant protocols (IEC 61850,
and effective solutions IEC 60870-5-103, IEC 60870-5-104, Modbus TCP, DNP3 serial
• Full compatibility between IEC 61850 Editions 1 and 2 and TCP, PROFINET IO)
• Reliable data transmission via PRP and HSR protocols
Functions
• Extensive cyber-security functionality, such as role-based
DIGSI 5 permits all functions to be configured and combined as access control (RBAC), logging security-related events or
required. signed firmware
• Transformer differential protection for two-winding trans- • Simple, quick, and secure access to device data via a standard
formers with versatile, additional protection functions; Web browser – without additional software
expandable to 3 windings
• Secure serial protection data communication, also over great
• Transformer differential protection for phase-angle regulating distances and all available physical media (optical fiber, two-
transformers of the single-core type and special transformers wire connections, and communication networks)
• Universal usability of the permissible measuring points • Detecting operational measured variables and protection-
function measured values to evaluate the systems, to support
• Applicable from average up to extra-high voltage commissioning, and to analyze faults
• Protection of standard power transformers, auto trans-
formers, and motors
• Typical properties of a transformer differential protection such
as flexible adaptation to the transformer vector group, control

SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 125
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

• Frequency tracked protection functions over a wide frequency • Two-winding transformer 1.5 CB (DIFF protection, CBFP, REF)
range (10 Hz to 80 Hz) and the option to assign the protection
functions in a single device to different frequency tracking
• Two-winding-transformer (Diff. protection, voltage controller)
groups. • Motor (DIFF. protection, CBFP)
• Phasor Measurement Unit (PMU) for synchrophasor measured Application Examples
values and IEEE C37.118 protocol
Two-winding transformer basis (Figure 2.11/6)
• High-performance fault recording (buffer for a max. record
time of 80 s at 8 kHz or 320 s at 2 kHz) • Differential protection
• Auxiliary functions for simple tests and commissioning • Overload protection, backup protection for the downstream
power system
• Flexibly adjustable I/O quantity structure within the scope of
the SIPROTEC 5 modular system Two-winding transformer with restricted ground-fault protec-
tion (REF) (Figure 2.11/7)
Applications • Differential protection
DIGSI 5 provides application templates for standard applications. • Restricted ground-fault protection on the neutral side
They include basic configurations and default setting. These can
be used directly or as a template for application-related adapta- • Overload protection, backup protection for the downstream
power system
tion. The available measuring points make varied applications
possible. Before ordering a device, please configure the applica- • Circuit-breaker failure protection
tion with DIGSI 5. The table "Functions and application Two-winding transformer in breaker-and-a-half layout (Figure
templates" shows the functional scope of the device. Use the 2.11/8)
configurator to determine the necessary function points.
• Differential protection
Application Templates • Restricted ground-fault protection on the neutral side
Application templates are available in DIGSI 5 for the applica- • Overload protection, backup protection for the downstream
tions of the device 7UT85. The application templates contain power system
the basic configurations, required functions, and default • Circuit-breaker failure protection.
settings.
Figure 2.11/6 shows the typical structure of an application
The following application templates are available for the template, the measuring points used, the function groups used,
device 7UT85 in the DIGSI 5 function library: their internal circuiting, and the predefined functions. The
2.11
• Two-winding-transformer base (Diff. protection) example shows the two-winding transformer with restricted
ground-fault protection.
• Two-winding transformer with restricted ground-fault protec-
tion (Diff. protection, CBFP, REF)

126 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

[dw_two-winding-temp_01, 2, en_US] 2.11


Figure 2.11/6 Application Example: Protection of a Two-Winding Transformer

SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 127
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

2.11

[dw_two-winding-temp_02, 3, en_US]

Figure 2.11/7 Application Example: Protection of a Two-Winding Transformer with Restricted Ground-Fault Protection

128 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

2.11

[dw_two-winding-temp_03, 3, en_US]

Figure 2.11/8 Application Example: Protection of a Two-winding Transformer in Breaker-and-a-Half Layout

SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 129
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

ANSI Function Abbr. Application Templates

Available
1 2 3 4 5

Expandable hardware quantity structure I/O ■


21/21N Distance Protection Z<, V< /I>/∠(V, ■
I)
21T Impedance protection for transformers Z< ■
24 Overexcitation protection V/f ■
25 Synchrocheck, synchronization function Sync ■
32, 37 Power protection active/reactive power P<>, Q<> ■
27 Undervoltage protection: "3-phase" or "positive- V< ■ ■
sequence system V1" or "universal Vx"
32R Reverse-power protection - P< ■
Reactive power-undervoltage protection (QU Q>/V< ■
protection)
37 Undercurrent I< ■
37 Power-plant disconnection protection -dP ■
38 Temperature supervision θ> ■
46 Negative-sequence system overcurrent protection I2> ■ ■
46 Unbalanced-load protection (thermal) I2² t> ■
47 Overvoltage protection, negative-sequence V2> ■
system
47 Overvoltage protection, negative-sequence V2/V1> ■
system/positive-sequence system
49 Thermal overload protection θ, I²t ■ ■ ■ ■ ■ ■
49 Thermal overload protection, user-defined charac- θ, I²t ■
teristic curve
49H Hotspot calculation θh, I²t ■
50N/ 51N TD Overcurrent protection, ground IN> ■ ■
50/51 TD Overcurrent protection, phases I> ■ ■ ■ ■ ■ ■
2.11
Instantaneous tripping at switch onto fault SOTF ■
50HS Instantaneous high-current tripping I>>> ■
50N/ 51N TD Overcurrent protection, 1-phase IN> ■ ■
50Ns/ 51Ns Sensitive ground-fault detection for grounded arc INs> ■
suppression coils and isolated power systems
including a) 3I0> b) admittance V0>, c) 3I0-harm>
(from V7.8)
Sensitive ground-fault detection via pulse detec- IN pulse ■
tion; hint: this stage also requires the func-
tion 50Ns/51Ns or 67Ns "sensitive ground-fault
detection for grounded arc suppression coils and
isolated power systems"
Intermittent ground-fault protection IIE> ■
50BF Circuit-breaker failure protection, 3-pole CBFP ■ ■ ■ ■ ■
50RS Circuit breaker reignition monitoring CBRM ■
51V Voltage-controlled overcurrent protection t=f(I, V) ■
59, 59N Overvoltage protection: "3-phase" or "zero- V> ■ ■ ■
sequence system V0" or "positive-sequence
system V1" or "universal Vx"
59 Overvoltage protection: "3-phase" or "positive- V> ■
sequence system V1" or "universal Vx"
60 Voltage-comparison supervision ΔV> ■
67 Directional overcurrent protection, phases I>, ∠(V, I) ■
67N Directional ground-fault protection in grounded IN>, ∠(V, I) ■
power systems
67N Directional overcurrent protection, ground IN>, ∠(V, I) ■ ■
67Ns Sensitive ground-fault detection for grounded arc ■
suppression coils and isolated power systems
including a) 3I0> b) V0>, c) cos/sine Phi, d)
fleeting contact, e) Phi(V, I), f) admittance

130 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

ANSI Function Abbr. Application Templates

Available
1 2 3 4 5

Directional tripping stage with one harmonic; ∠(V0h,I0h) ■


hint: this stage also requires the function "67Ns
sensitive ground-fault detection for grounded arc
suppression coils and isolated power systems"
Directional intermittent ground-fault protection IIEdir> ■
68 Power-swing blocking ΔZ/Δt ■
74TC Trip-circuit supervision ■ ■ ■ ■ ■
79 Automatic reclosing, 3-pole AREC ■
81 Frequency protection: "f>" or "f<" or "df/dt" f<>; df/dt<> ■ ■
81U Underfrequency load shedding f<(ULS) ■
81 AF Abnormal frequency protection fBand ■
Vector-jump protection Δφ> ■
85/21 Teleprotection scheme for distance protection ■
85/27 Weak or no infeed: Echo and tripping ■
85/67N Teleprotection scheme for directional ground- ■
fault protection
86 Lockout ■ ■ ■ ■ ■
87T Differential protection for transformers ΔI ■ ■ ■ ■ ■
87T Differential protection for special transformers ΔI ■
87T Node Differential protection (nodal point protection for ΔI nodes ■
auto transformer)
87T Differential protection for phase-angle regulating ΔI ■
transformers (single core)
87N T Restricted ground-fault protection ΔIN ■ ■ ■
87M Differential protection for motors ΔI ■ ■
87G Differential protection for generators ΔI ■
87L Line differential protection for 2 line ends ΔI ■
2.11
for 7UT8 (communication
with 7SD82, 85, 86, 7SL86, 87)
Option for differential protection: Charging- ΔI ■
current compensation
87 STUB STUB fault differential protection (for 1 1/2 CB ■
applications)
90V Voltage controller for 2-winding transformer ■ ■
90V Voltage controller for 2-winding transformer with ■
parallel control
Number of 2-winding transformers with parallel ■
control (hint: only together with the function
"voltage controller for 2-winding transformer with
parallel control"
90V Voltage controller for 3-winding transformer ■
90V Voltage controller for grid coupling transformer ■
FL Fault locator, single-ended FL-one ■
PMU Synchrophasor measurement (1 PMU can be used PMU ■
for max. 8 voltages and 8 currents)
AFD Arc protection (only with plug-in module ARC- ■
CD-3FO)
Measured values, standard ■ ■ ■ ■ ■ ■
Measured values, extended: Min, max, average ■
Switching statistics ■ ■ ■ ■
Circuit breaker monitoring ΣIx, I²t, 2P ■
CFC (standard, control) ■ ■ ■ ■ ■ ■
CFC arithmetic ■
Switching sequence function ■
Inrush-current detection ■ ■ ■ ■ ■
External trip initiation ■ ■

SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 131
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

ANSI Function Abbr. Application Templates

Available
1 2 3 4 5

Control ■ ■ ■ ■ ■ ■
Fault recording of analog and binary signals ■ ■ ■ ■ ■ ■
Monitoring ■ ■ ■ ■ ■ ■
Protection interface, serial ■
Circuit breaker ■ ■ ■ ■ ■ ■
Disconnector/grounding conductor ■
Transformer side 7UT85 ■
Frequency group manual update (from V7.8) ■
Cyber security: role-based access control (from ■
V7.8)
Temperature measurement via log ■
Function point class: 0 30 30 175 50
The configuration and function point class for your application can be determined in the SIPROTEC 5 order configurator at www.siemens.com/siprotec.

Table 2.11/4 SIPROTEC 7UT85 – Functions, Application Templates


(1) 2-Winding Transformer Base (DIFF protection)
(2) 2-Winding Transformer (DIFF protection, SVS, REF)
(3) 2-Winding Transformer 1.5 CB (DIFF protection, SVS, REF)
(4) 2-Winding Transformer (DIFF. Protection, Voltage Controller)
(5) Motor (DIFF protection, CBFP, voltage protection)

2.11

132 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85

Standard Variants for SIPROTEC 7UT85


O1 1/3, 7 BI, 7 BO, 8 I
Housing width 1/3 x 19",
7 binary inputs,
7 binary outputs (1 life contact, 2 standard, 4 fast),
8 current transformers
Includes the printed circuit board assembly modules: Base module with
PS201 and IO203.
O2 1/2, 19 BI, 23 BO, 8 I
Housing width 1/2 × 19",
19 binary inputs,
23 binary outputs (1 life contact, 18 standard, 4 fast),
8 current transformers
Includes the printed circuit board assembly modules: Base module with
PS201 and IO203
Expansion module IO205.

Table 2.11/5 Standard Variants for Transformer Differential Protection Devices

You can find the technical data in the manual


www.siemens.com/siprotec.

2.11

SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 133