You are on page 1of 2

CENTRAL DATA NODE WITH AUTOMATION

SIPROTEC 6MU85
Merging Unit - Modular, interoperable, high-performance process data acquisition

Usage and description • Centralized protection


The SIPROTEC 6MU85 merging unit, based on the flexible • Bay units for decentralized busbar protection
SIPROTEC 5 system, is designed for both conventional and
• Process-bus fault recorder
non-conventional instrument transformers (LPIT*) and
enables the digitization of all primary data close to the • Centralized synchrocheck
process.
The SIPROTEC 5 process bus offers a wide range of solutions • Detection and recording of power-quality data in the
and migration concepts for new and existing plants. medium voltage and subordinate low-voltage power
system

Main function Merging Unit,


Benefits
Breaker functions,
Backup protection functions, • Can be adjusted to a wide range of current transformer,
Additional functions voltage transformer, and low-power instrument
transformer (LPIT) sensors 2
Communication Up to 4 sampled measured value streams
according to IEC 61850-9-2LE or • The number of binary inputs and outputs can be scaled.
IEC 61850-9-2 / IEC 61869 flexible streams
• It can be expanded by a second row.
Hardware Flexibly adjustable and expandable I/O
flexibility quantity structure within the scope of the • Direct High-speed circuit-breaker tripping < 1 ms
modular SIPROTEC 5 system; 1/6
• Additional data acquisition (temperature, pressure, tap
expansion modules can be added
changer setting, ...)
Housing width 1/3 × 19 inches to 2/1 × 19 inches • Cybersecurity in accordance with NERC CIP and BDEW
Whitepaper requirements
Standard Coated modules
• Highest availability even under extreme environmental
conditions by standard coating of the modules
Merging Unit application areas

• Acquisition of analog measured values and digital


inputs, control of digital outputs
• As central merging unit for process data acquisition of a
transformer
Functions Communication
Merging Unit • Pluggable communication modules, usable for different
and redundant protocols (IEC 61850-8-1,
• 1 or 2 sampled2 measured value streams per
IEC 61850-9-2 Merging Unit, IEC 60870-5-103,
ETH-BD-2FO Ethernet module
IEC60870-5-104, MODBUS TCP, DNP3 serial and TCP,
–Up to 32 analog values in every combination of current
PROFINET IO, PROFINET IO S2 redundancy)
and voltage measured values or
– 4 x current, 4 x voltage (IEC 61850-9-2LE) • Serial protection communication via optical fibers, two-
wire connections, and communication networks
• Up to 4 ETH-BD-2FO modules possible
(IEEE C37.94 and others), including automatic
• Reliable and redundant data transmission via PRP switchover between ring and chain topology.

• Compliant with IEC 61869-9, IEC 61869-13 • Extensive cybersecurity functionality, such as role-based
access control (RBAC), logging of security-related events,
• IEC 61850-8-1 GOOSE, MMS, and Merging Unit protocol signed firmware, or authenticated IEEE 802.1X network
on the same Ethernet module access
• Measured value and date/time synchronization via • Simple, fast, and secure access to the device via a
IEEE 1588v2/PTP standard Web browser to display all information and
• Redundant power supply diagnostic data, vector diagrams, single line and device
display pages
• Expanded temperature ranges (-40 ºC to 70 ºC)
• Virtual network partitioning (IEEE 802.1Q - VLAN)
Circuit-breaker and disconnector-switch functions
• Control system with switchgear interlocking Our tip

• Circuit-breaker failure protection (50BF) Register in the Industry Mall, create an account and benefit
fully from our SIPROTEC 5 configurator.
• Circuit-breaker wear monitoring
• Switching statistics Advantages / benefits for users registered and logged in
to the Industry Mall
• Point-on-wave switching (PoW)
• Personal product list, with automatic storage of the last
• Trip-circuit supervision (74TC) 50 configurations
• Automatic reclosing (79) • Insertion of comments (e. g. naming of a branch name
• Synchrocheck (25) for the configured device)

Backup protection functions • Automatic saving of the function point calculation

• Non-directional overcurrent protection (50/51, 50N/51N) • Visibility of regional list prices (non-logged-in users get
the message: Price on request)
• Directional overcurrent protection (67/67N)
• Overvoltage and undervoltage protection (27/59)
Additional protection functions
• Phasor Measurement Unit (PMU) for synchrophasor
measured values and IEEE C37.118 protocol
• Arc protection
• Utility functions for simple commissioning and tests
• Temperature acquisition using a TR1200 RTD unit
(7XV5662-6AD10 or 7XV5662-8AD10)
• 4-mA to 20-mA measuring input for a wide range of
analog process values, for example, pressure, tap-
changer setting
• PQ – Basic: Voltage unbalance; voltage changes:
overvoltage, dip, interruptions; TDD, THD, and
harmonics

Siemens
Smart Infrastructure
Electrification & Automation
Mozartstraße 31C
91052 Erlangen, Germany
Customer Support: siemens.com/energy-automation-support-contact

© Siemens 2022. Subject to changes and errors.


SIPROTEC 6MU85_Profile.docx_05.22

For all products using security features of OpenSSL, the following shall apply: This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit
(www.openssl.org), cryptographic software written by Eric Young (eay@cryptsoft.com) and software developed by Bodo Moeller.