NO: SD-107 PRODUCT: S8VM Power Supplies

DATE: February 2018 TYPE: Discontinuation Notice

S8VM Power Supplies will be discontinued February 2019

Discontinuation Date: February 2019


Note: Date is subject to change based on raw materials and components availability at the factory.

Overview Summary
Product Discontinuation Recommended Replacement
Switch Mode Power Supply Switch Mode Power Supply
Model S8VM series Model S8FS-G series
15/35/50/100/150W Models 15/30/50/100/150W Models
Model S8VS series (with Indication Monitor)
Under Voltage Alarm Function Models
60/90/120/180W Models
Model S8VM series Model S8JX-P series
300W (5V, 12V, 24V) Model 300W (5V, 12V, 24V) Model
600W (5V, 12V, 24V) Model 600W (5V, 12V, 24V) Model
Model S8VM series Model S8FS-G series
300W (15V) Model 300W (15V) Model
600W (15V) Model 600W (15V) Model
1500W (15V) Model 600W (24V) Model (models with parallel
operation option)
Mounting Bracket Mounting Bracket
Model S82Y-VM□□B No recommended replacement
Model S82Y-VM□□F No recommended replacement
Model S82Y-VM□□S No recommended replacement
Model S82Y-VM□□D No recommended replacement
Under Voltage Alarm Output Wiring Cable Under Voltage Alarm Output Wiring Cable
Model S82Y-VM10H No recommended replacement
Signal I/O Connector Terminals and Housing Signal I/O Connector Terminals and Housing
Model S82Y-VM30CN No recommended replacement

1
Cautions on Applying Replacements
 Dimensions are different.
 Wire connection is different.
 Mounting method is different.
 Startup time takes longer.
 Output hold time takes shorter.
 Overcurrent protection characteristics are different.
 Some models are not designed for parallel operation.
 Some models are not designed for remote sensing function.
 Some models have different derating curve.
 As the recommended replacement of S8VM-15224C, parallel connection of S8FS-G60024C-W is
necessary.
 The output capacitance of the S8FS-G05005□□ is 40 W.
 The output capacitance of the S8FS-G10005□□ is 80 W.
 The output capacitance of the S8FS-G15005□□ is 105 W.

See the detail of differences on the following pages

Affected Parts
DIN Rail mounting / Covered type
Product discontinuation Recommended replacement
Model Model
S8VM-01505CD S8FS-G01505CD
S8VM-01512CD S8FS-G01512CD
S8VM-01515CD S8FS-G01515CD
S8VM-01524CD S8FS-G01524CD
S8VM-03005CD S8FS-G03005CD
S8VM-03012CD S8FS-G03012CD
S8VM-03015CD S8FS-G03015CD
S8VM-03024CD S8FS-G03024CD
S8VM-05005CD S8FS-G05005CD (*1)
S8VM-05012CD S8FS-G05012CD
S8VM-05015CD S8FS-G05015CD
S8VM-05024CD S8FS-G05024CD
S8VM-10005CD S8FS-G10005CD (*2)
S8VM-10012CD S8FS-G10012CD
S8VM-10015CD S8FS-G10015CD
S8VM-10024CD S8FS-G15024CD
S8VM-15005CD S8FS-G15005CD (*3)
S8VM-15012CD S8FS-G15012CD
S8VM-15015CD S8FS-G15015CD
S8VM-15024CD S8FS-G15024CD

*1. The output capacity is 40 W.


*2. The output capacity is 80 W.
*3. The output capacity is 105 W.

2
Bottom mounting / Covered type
Product discontinuation Recommended replacement
Model Model
S8VM-01505C S8FS-G01505C
S8VM-01512C S8FS-G01512C
S8VM-01515C S8FS-G01515C
S8VM-01524C S8FS-G01524C
S8VM-03005C S8FS-G03005C
S8VM-03012C S8FS-G03012C
S8VM-03015C S8FS-G03015C
S8VM-03024C S8FS-G03024C
S8VM-05005C S8FS-G05005C (*1)
S8VM-05012C S8FS-G05012C
S8VM-05015C S8FS-G05015C
S8VM-05024C S8FS-G05024C
S8VM-10005C S8FS-G10005C (*2)
S8VM-10012C S8FS-G10012C
S8VM-10015C S8FS-G10015C
S8VM-10024C S8FS-G15024C
S8VM-15005C S8FS-G15005C (*3)
S8VM-15012C S8FS-G15012C
S8VM-15015C S8FS-G15015C
S8VM-15024C S8FS-G15024C
S8VM-30005C S8JX-P30005N
S8VM-30012C S8JX-P30012N
S8VM-30015C S8FS-G30015C
S8VM-30024C S8JX-P30024N
S8VM-60005C S8JX-P60005N
S8VM-60012C S8JX-P60012N
S8VM-60015C S8FS-G60015C
S8VM-60024C S8JX-P60024N
S8VM-15224C S8FS-G60024C-W (*4)
*1. The output capacity is 40 W.
*2. The output capacity is 80 W.
*3. The output capacity is 105 W.
*4. With parallel operation.

DIN Rail mounting / Covered type Undervoltage Alarm Function Model with Cover
Product discontinuation Recommended replacement
Model Model
S8VM-01524AD S8VS-06024A
S8VM-03024AD S8VS-06024A
S8VM-05024AD S8VS-09024A
S8VM-05024PD S8VS-09024AP
S8VM-10024AD S8VS-12024A
S8VM-10024PD S8VS-12024AP
S8VM-15024AD S8VS-18024A
S8VM-15024PD S8VS-18024AP

3
Bottom mounting / Covered type Undervoltage Alarm Function Model with Cover
Product discontinuation Recommended replacement
Model Model
S8VM-01524A S8VS-06024A
S8VM-03024A S8VS-06024A
S8VM-05024A S8VS-09024A
S8VM-05024P S8VS-09024AP
S8VM-10024A S8VS-12024A
S8VM-10024P S8VS-12024AP
S8VM-15024A S8VS-18024A
S8VM-15024P S8VS-18024AP

 There are no recommended products for open-frame type.

DIN Rail mounting / Open-frame type


Product discontinuation Recommended replacement
Model Model
S8VM-01505D S8FS-G01505CD
S8VM-01512D S8FS-G01512CD
S8VM-01515D S8FS-G01515CD
S8VM-01524D S8FS-G01524CD
S8VM-03005D S8FS-G03005CD
S8VM-03012D S8FS-G03012CD
S8VM-03015D S8FS-G03015CD
S8VM-03024D S8FS-G03024CD
S8VM-05005D S8FS-G05005CD (*1)
S8VM-05012D S8FS-G05012CD
S8VM-05015D S8FS-G05015CD
S8VM-05024D S8FS-G05024CD
S8VM-10005D S8FS-G10005CD (*2)
S8VM-10012D S8FS-G10012CD
S8VM-10015D S8FS-G10015CD
S8VM-10024D S8FS-G10024CD
S8VM-15005D S8FS-G15005CD (*3)
S8VM-15012D S8FS-G15012CD
S8VM-15015D S8FS-G15015CD
S8VM-15024D S8FS-G15024CD

 There are no recommended products for open-frame type.


*1. The output capacity is 40 W.
*2. The output capacity is 80 W.
*3. The output capacity is 105 W.

4
Bottom mounting / Open-frame type
Product discontinuation Recommended replacement
Model Model
S8VM-01505 S8FS-G01505C
S8VM-01512 S8FS-G01512C
S8VM-01515 S8FS-G01515C
S8VM-01524 S8FS-G01524C
S8VM-03005 S8FS-G03005C
S8VM-03012 S8FS-G03012C
S8VM-03015 S8FS-G03015C
S8VM-03024 S8FS-G03024C
S8VM-05005 S8FS-G05005C (*1)
S8VM-05012 S8FS-G05012C
S8VM-05015 S8FS-G05015C
S8VM-05024 S8FS-G05024C
S8VM-10005 S8FS-G10005C (*2)
S8VM-10012 S8FS-G10012C
S8VM-10015 S8FS-G10015C
S8VM-10024 S8FS-G15024C
S8VM-15005 S8FS-G15005C (*3)
S8VM-15012 S8FS-G15012C
S8VM-15015 S8FS-G15015C
S8VM-15024 S8FS-G15024C

 There are no recommended products for open-frame type.


*1. The output capacity is 40 W.
*2. The output capacity is 80 W.
*3. The output capacity is 105 W.

Sold separately
Product discontinuation Recommended replacement
S82Y-VM10B No recommended replacement
S82Y-VM20B No recommended replacement
S82Y-VM10F No recommended replacement
S82Y-VM30B No recommended replacement
S82Y-VM30S No recommended replacement
S82Y-VM30F No recommended replacement
S82Y-VM30D No recommended replacement
S82Y-VM60B No recommended replacement
S82Y-VM60S No recommended replacement
S82Y-VM60F No recommended replacement
S82Y-VM60D No recommended replacement
S82Y-VM10H No recommended replacement
S82Y-VM30C No recommended replacement

5
Detail of differences
Terminal Arrangement / Wire Connection
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<15W,30W,50W Models> <15W,30W,50W Models>

<100W Model> <100W,150W Models>

<150W Model >

6
Product discontinuation Recommendable replacement
Model S8VM series Model S8VS series
(Undervoltage Alarm Function) (with Indication Monitor)
<15W,30W,50W Models> <60W Model (with Indication Monitor)>

<100W Model> <90W,120W Models (with Indication Monitor)>

<150W Model> <180W Model (with Indication Monitor)>

7
Product discontinuation Recommendable replacement
Model S8VM series Model S8JX-P series
<300W(5V,12V,24V) Model> <300W(5V,12V,24V) Model>

<600W(5V,12V,24V) Models> <600W(5V,12V,24V) Models>

8
Terminal arrangement / Wire connection
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<300W(15V) Model> <300W(15V) Model>

<600W(15V) Model> <600W(15V) Model>

9
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
(with parallel operation)
<1500W(24V) Model> <600W(24V) Model (with parallel operation)>

*Use in parallel connection. (three Power Supplies)

10
Dimensions / Mounting dimensions
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<15W Models> <15W,30W Models>
DIN Rail mounting DIN Rail mounting

Bottom mounting Bottom mounting

Front mounting

<For Undervoltage Alarm Function model>


・Model S8VS series 60W Model
(with Indication Monitor)

11
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<30W Model> <15W,30W Model>
DIN Rail mounting DIN Rail mounting

Bottom mounting Bottom mounting

<For Undervoltage Alarm Function model>


・Model S8VS series 60W Model
(with Indication Monitor)

12
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<50W Model> <50W Model>
DIN Rail mounting DIN Rail mounting

Bottom mounting Bottom mounting

<For Undervoltage Alarm Function model>


・Model S8VS series 90W Model
(with Indication Monitor)

13
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<100W Model> <100W Model>
DIN Rail mounting DIN Rail mounting

Bottom mounting Bottom mounting

<For Undervoltage Alarm Function model>


・Model S8VS series 120W Model
(with Indication Monitor)

14
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<150W Model> <150W Model>
DIN Rail mounting DIN Rail mounting

Bottom mounting Bottom mounting

<For Undervoltage Alarm Function model>


・Model S8VS series 180W Model
(with Indication Monitor)

15
Product discontinuation Recommendable replacement
Model S8VM series Model S8JX-P series
<300W(5V,12V,24V) Model> <300W(5V,12V,24V) Models>
Bottom mounting Bottom mounting

<600W(5V,12V,24V) Model> <600W(5V,12V,24V) Model>


Bottom mounting Bottom mounting

16
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<300W(15V) Model> <300W(15V) Model>
Bottom mounting Bottom mounting

<600W(15V) Model> <600W(15V) Model>


Bottom mounting Bottom mounting

17
Product discontinuation Recommendable replacement
Model S8VM series Model S8FS-G series
<1500W(24V) Models> <600W(24V) Model (with parallel operation)>
*Use in parallel connection. (three Power Supplies)

Bottom mounting Bottom mounting

18
Characteristics
Product discontinuation Recommendable replacement
Item
Model S8VM series Model S8FS-G series
Input voltage 15W,30W,50W,100W,150W Models 15W,30W,50W,100W,150W Models
100 to 240VAC free input 100 to 240VAC free input
(85 to 265VAC) (85 to 264VAC,120 to 370VDC)

Input current 15W Model 15W Model


0.5A max.(at 100VAC input) 0.35A max.(at 100VAC input)
0.25A max.(at 200VAC input) 0.25A max.(at 200VAC input)
30W Models 30W Models
0.9A max.(at 100VAC input) 0.8A max.(at 100VAC input)
0.45A max.(at 200VAC input) 0.5A max.(at 200VAC input)
50W Models 50W Models
0.8A max.(at 100VAC input) 1.2A max.(at 100VAC input)
0.4A max.(at 200VAC input) 0.7A max.(at 200VAC input)
100W Models 100W Models
1.4A max.(at 100VAC input) 2.3A max.(at 100VAC input)
0.7A max.(at 200VAC input) 1.2A max.(at 200VAC input)
150W Models 150W Models
2.0A max.(at 100VAC input) 3.3A max.(at 100VAC input)
1.0A max.(at 200VAC input) 1.9A max.(at 200VAC input)

Inrush current 15W,30W,50W,100W,150W Models 15W,30W,50W,100W,150W Models


17.5A max.(at 100VAC input) 14A max.(at 100VAC input)
35A max.(at 200VAC input) 28A max.(at 200VAC input)
*for cold start at 25℃ *for cold start at 25℃
Startup time 15W,30W Models 15W,30W,50W,100W,150W Models
1100ms max. 1000ms max.
50W,100W,150W Models
800ms max.
Output hold time 15W,30W,50W,100W,150W Models 15W,30W,50W,100W,150W Models
15ms min. 8ms min.(at 100VAC input)
16ms min.(at 200VAC input)
Overload protection 15W,30W Models 15W,30W,50W,100W,150W Models
105 to 160% of rated load current, voltage 105 to 160% of rated load current,
drop, intermittent, voltage drop, intermittent,
automatic reset automatic reset
50W,100W,150W Model
105 to 160% of rated load current,
voltage drop, intermittent (5V)
voltage drop, (12V,15V,24V)
automatic reset

Parallel operation 15W,30W,50W,100W,150W Models 15W,30W,50W,100W,150W Models


No No
Cooling method 15W,30W,50W,100W,150W Models 15W,30W,50W,100W,150W Models
Natural cooling Natural cooling

19
Product discontinuation Recommendable replacement
Item
Model S8VM series Model S8FS-G series
Derating Curves 15W,30W Models 15W,30W,50W Models

50W Models

100W Models 100W,150W Models

150W Models

20
Product discontinuation Recommendable replacement
Item Model S8VM series Model S8VS series
(Undervoltage Alarm Function) (with Indication Monitor)
Input voltage 15W,30W,50W,100W,150W Models 60W,90W,120W,180W Models
100 to 240VAC free input 100 to 240VAC free input
(85 to 265VAC) (85 to 265VAC, 80 to 370 VDC)
Input current 15W Model 60W Model
0.5A max.(at 100VAC input) 1.7A max.(at 100VAC input)
0.25A max.(at 200VAC input) 1.0A max.(at 200VAC input)
30W Models 90W Models
0.9A max.(at 100VAC input) 2.3A max.(at 100VAC input)
0.45A max.(at 200VAC input) 1.4A max.(at 200VAC input)
50W Models 120W Models
0.8A max.(at 100VAC input) 1.9A max.(at 100VAC input)
0.4A max.(at 200VAC input) 1.1A max.(at 200VAC input)
100W Models 180W Models
1.4A max.(at 100VAC input) 2.9A max.(at 100VAC input)
0.7A max.(at 200VAC input) 1.6A max.(at 200VAC input)
150W Models
2.0A max.(at 100VAC input)
1.0A max.(at 200VAC input)
Inrush current 15W,30W,50W,100W,150W Models 60W,90W,120W,180W Models
17.5A max.(at 100VAC input) 17.5A typ. (at 100VAC input)
35A max.(at 200VAC input) 35A typ. (at 200VAC input)
*for cold start at 25℃ *for cold start at 25℃
Startup time 15W,30W Models 60W Models
1100ms max. 460ms typ. (at 100VAC input)
50W,100W,150W Models 290ms typ. (at 200VAC input)
800ms max. 90W Models
660ms typ. (at 100VAC input)
420ms typ. (at 200VAC input)
120W Models
650ms typ. (at 100VAC input)
520ms typ. (at 200VAC input)
180W Models
580ms typ. (at 100VAC input)
490ms typ. (at 200VAC input)
Output hold time 15W,30W,50W,100W,150W Models 60W Models
15ms min. 33ms typ. (at 100VAC input)
154ms typ. (at 200VAC input)
90W Models
28ms typ. (at 100VAC input)
136ms typ. (at 200VAC input)
120W Models
56ms typ. (at 100VAC input)
56ms typ. (at 200VAC input)
180W Models
70ms typ. (at 100VAC input)
700ms typ. (at 200VAC input)

21
Product discontinuation Recommendable replacement
Item Model S8VM series Model S8VS series
(Undervoltage Alarm Function) (with Indication Monitor)
Overload protection 15W,30W Models 60W,90W Models
105 to 160% of rated load current, voltage 105 to 160% of rated load current, voltage
drop, intermittent, drop, intermittent,
automatic reset automatic reset
50W,100W,150W Model 120W,180W Models
105 to 160% of rated load current, 105 to 160% of rated load current,
voltage drop, intermittent (5V) voltage drop,
voltage drop, (12V,15V,24V) automatic reset
automatic reset
Parallel operation 15W,30W,50W,100W,150W Models 60W,90W,120W,180W Models
No No
Cooling method 15W,30W,50W,100W,150W Models 60W,90W,120W,180W Models
Natural cooling Natural cooling

22
Product discontinuation Recommendable replacement
Item Model S8VM series Model S8VS series
(Undervoltage Alarm Function) (with Indication Monitor)
Derating Curves 15W,30W Models 60W,90W,120W,180W Models

50W Models

100W Models

150W Models

23
Product discontinuation Recommendable replacement
Item
Model S8VM series Model S8JX-P series
Input voltage 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models
600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
100 to 240VAC free input 100 to 240VAC free input
(85 to 265VAC) (85 to 264VAC,120 to 370VDC)
Input current 300W(5V) Model 300W(5V,12V,24V) Model
4.0A max.(at 100VAC input) 4.5A max.(at 100VAC input)
2.0A max.(at 200VAC input) 2.2A max.(at 200VAC input)
300W(12V,24V) Models 600W(5V,12V,24V) Models
4.3A max.(at 100VAC input) 8.7A max.(at 100VAC input)
2.2A max.(at 200VAC input) 4.3A max.(at 200VAC input)
600W(5V) Models
8.0A max.(at 100VAC input)
4.0A max.(at 200VAC input)
600W(12V,24V) Models
8.3A max.(at 100VAC input)
4.2A max.(at 200VAC input)

Inrush current 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models


600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
20A max.(at 100VAC input) 17.5A typ.(at 100VAC input)
40A max.(at 200VAC input) 35A typ.(at 200VAC input)
*for cold start at 25℃ *for cold start at 25℃
Startup time 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models
600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
1000ms max. 1000ms max.
Output hold time 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models
600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
15ms min. 20ms min.
Overload protection 300W(5V,12V), 600W(5V,12V) Models 300W(5V,12V,24V) Models
105 to 160% of rated load current, 600W(5V,12V,24V) Models
voltage drop, intermittent (5V) 105 to 160% of rated load current,
voltage drop, (12V,15V) voltage drop, intermittent,
automatic reset automatic reset
300W(24V), 600W(24v) Models
120 to 160% (300W)
115 to 160% (600W)
voltage drop, automatic reset

Parallel operation 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models


600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
Yes (up to 2 units) Yes (up to 5 units)
Cooling method 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models
600W(5V,12V,24V) Models 600W(5V,12V,24V) Models
Forced-air cooling by a built-in fan Forced-air cooling by a built-in fan

24
Product discontinuation Recommendable replacement
Item
Model S8VM series Model S8JX-P series
Derating Curves 300W(5V,12V,24V) Models 300W(5V,12V,24V) Models
600W(5V,12V,24V) Models 600W(5V,12V,24V) Models

Product discontinuation Recommendable replacement


Item
Model S8VM series Model S8FS-G series
Input voltage 300W(15V), 600W(15V) Models 300W(15V) Model
100 to 240VAC free input 100 to 240VAC free input
(85 to 265VAC) (85 to 264VAC,120 to 370VDC)
600W(15V) Models
100 to 240VAC free input
(85 to 264VAC,120 to 350VDC)
Input current 300W(15V) Model 300W(15V) Model
4.0A max.(at 100VAC input) 4.2A max.(at 100VAC input)
2.0A max.(at 200VAC input) 2.1A max.(at 200VAC input)
600W(15V) Model 600W(5V,12V,24V) Model
8.0A max.(at 100VAC input) 7.7A max.(at 100VAC input)
4.0A max.(at 200VAC input) 3.8A max.(at 200VAC input)

Inrush current 300W(15V), 600W(15V) Models 300W(15V), 600W(15V) Models


20A max.(at 100VAC input) 14A typ.(at 100VAC input)
40A max.(at 200VAC input) 28A typ.(at 200VAC input)
*for cold start at 25℃ *for cold start at 25℃
Startup time 300W(15V), 600W(15V) Models 300W(15V), 600W(15V) Models
1000ms max. 1000ms max.

25
Product discontinuation Recommendable replacement
Item
Model S8VM series Model S8FS-G series
Output hold time 300W(15V), 600W(15V) Models 300W(15VV) Model
15ms min. 30ms typ.(at 100VAC input)
25ms typ.(at 200VAC input)
600W(15V) Model
25ms typ.
Overload protection 300W(15V), 600W(15V) Models 300W(15V) Model
105 to 160% of rated load current, 105 to 160% of rated load current,
voltage drop, voltage drop, intermittent,
automatic reset automatic reset
600W(15V Model
105 to 160% of rated load current,
voltage drop,
automatic reset

Parallel operation 300W(15V), 600W(15V) Models 300W(15V) Models


Yes (up to 2 units) No
600W(15V) Models
Yes (up to 5 units)
(with parallel operation)
Cooling method 300W(15V), 600W(15V) Models 300W(15V), 600W(15V) Models
Forced-air cooling by a built-in fan Forced-air cooling by a built-in fan

Derating Curves 300W(15V), 600W(15V) Models 300W(15V), 600W(15V) Models

26
Product discontinuation Recommendable replacement
Item Model S8VM series Model S8FS-G series
<1500W(24V) Model> <600W(24V) Model>
*Use in parallel connection. (three Power Supplies)
Input voltage 100 to 240VAC free input 100 to 240VAC free input
(85 to 265VAC) (85 to 264VAC,120 to 350VDC)
Input current 20.0A max.(at 100VAC input) 7.7A max.(at 100VAC input)
11.0A max.(at 200VAC input) 3.8A max.(at 200VAC input)
Inrush current 20A max.(at 100VAC input) 14A max.(at 100VAC input)
40A max.(at 200VAC input) 28A max.(at 200VAC input)
*for cold start at 25℃ *for cold start at 25℃
Startup time 1000ms max. 1000ms max.
Output hold time 20ms typ. (15ms min.) 30ms typ.

Overload protection 100VAC 105 to 160% of rated load current,


105 to 160% of rated load current, voltage drop,
voltage drop, intermittent, automatic reset
automatic reset
200VAC
155 to 200% of rated load current,
voltage drop, intermittent,
automatic reset

Parallel operation Yes (up to 2 units) Yes (up to 5 units)


Cooling method Forced-air cooling by a built-in fan Forced-air cooling by a built-in fan
Derating Curves

Specifications and prices in this product news are as of the issue date and are subject to change without notice.
Only main changes in specifications are described in this document. Please be sure to read the relevant catalogs, datasheets, product
specifications, instructions, and manuals for precautions and necessary information when using products.