You are on page 1of 9

Grid Solutions

Multilin T60
Full-Featured, Multiple-Winding Transformer Protection & Control
Protection • Dual-slope, dual-breakpoint differential
restraint characteristic, restrained and
The MultilinTM T60 transformer protection system is a comprehensive three-phase transformer relay unrestrained differential
designed to protect medium and large power transformers. The T60 provides automatic or user-definable • Transformer overexcitation overload and
magnitude reference winding selections for CT ratio matching, and performs automatic phase shift inhibit, thermal overload protection, 2nd
compensation for all types of transformer winding connections. Harmonic inrush and Inter-turn fault detection
The T60 algorithm allows the user to enable removal of the zero-sequence current even for delta connected • Five-zone backup distance protection
transformer windings, accommodating transformers with a variety of grounding configurations. with power swing detection and load
encroachment function

Key Benefits • Protection and control functionality in one


box, reducing the number of devices
• Secure, high-speed protection for transformers, compliant with IEEE C37.91 for maximum asset life
®

• High density inputs/outputs to support the


• Improved security for transformer energization and inrush provided through an adaptive 2nd
control of many switchyard assets – all from
harmonic restraint algorithm
one powerful device
• Sensitive ground fault protection provides low-impedence differential protection down to 5% of the
• Integrated large, full color display, for real-time
winding to limit transformer damage
visualization and control of the protected bay
• Integrated transformer thermal monitoring for asset management and maintenance optimization
• Embedded Synchrophasor measurement capabilities (per IEEE® C37.118), eliminating the need for
dedicated PMUs and support for synchrophasor multi-cast (per IEC® 61850-90-5) reducing bandwidth Cyber Security
and communications infrastructure costs • CyberSentry™ provides high-end cyber
• An integrated large, full color display, provides real-time visualization and control of the protected bay, security aligned to industry standards and
via a bay mimic as well as annunciator functionality and graphical visualization of phasors. services (NERC® CIP, AAA, Radius, RBAC, Syslog)
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869* or IEC 61850-9-2 Hardfiber) ensures
interoperability, device managing optimization and reduced cost of ownership
Advanced Communications
• 3 independent Ethernet ports for simultaneous
• Routable GOOSE (R-GOOSE) enables customer to send GOOSE messages beyond the substation, which
enables WAPC and more cost effective communication architectures for wide area applications & dedicated network connections with
IEEE 1588 support
• Increased network availability via failover time reduced to zero through IEC® 62439-3 “PRP” support
• IEC 61850-9-2LE/IEC 61869* networked or
• Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE standard IEC61850-9-2 Hardfiber process bus support
• Direct I/O for secure, high-speed exchange
Applications URs for DTT & pilot-aided schemes
• Transformer asset monitoring using hottest spot, loss-of-life and aging factor
• Applicable for transformers with up to six windings in a ring bus or breaker-and-a-half configuration Monitoring & Metering
• Reliable and secure protection for three-phase transformers, autotransformers, reactors, split phase • P&M class synchrophasors of voltage, current,
and phase angle regulating transformers and sequence components
• Stand-alone or component in automated substation control system • Advanced recording capabilities with high-
capacity event recorder, configurable and
extended waveform capture and data logger
T60 Transformer Protection System

Protection and Control T60 - Protection, Metering, Monitoring and Control

The T60 transformer protection system is a


comprehensive three-phase transformer relay
designed to protect medium and large power
transformers.
As part of the Universal Relay (UR) Family, the
T60 provides superior protection and control
that includes:

Percent Differential Protection


The T60 provides enhanced security by including
both restrained and unrestrained (instantaneous)
differential protection. The percent differential
element is based on a configurable dual-
breakpoint/dual-slope differential restraint
characteristic with inrush and overexcitation
inhibits. The maximum winding current is used
as a restraining signal for better through fault
stability under CT saturation conditions.

Advanced CT saturation and failure detection


algorithms maintain immunity to high current The T60 is the single point for protection, control, metering, and monitoring in one integrated device
that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
AC and low current DC saturation conditions
Monitoring as shown.

Functional Block Diagram

Voltage

second
source

828786A1.CDR
59X
from

59X
49
TYPICAL CONFIGURATION (the AC signal path is configurable)

27X
50BF-2
50P-2

51P-2

Amps

81O
2nd and 5th
harmonics

TM
49

Harmonic
Calculate

restraint

FlexElement
3

81U
Calculate

Block
Winding 2

87RGF-2
50G-2

51G-2

67N-2

51N-2

50N-2
Amps

3I_0

Metering + PMU

27P
operate amps

T60 Transformer Protection System


Calculate

50/87
Amps

87T

24
Winding 1

Calculate
87RGF-1

51N-1

50N-1
50G-1

51G-1

67N-1
Amps

3I_0

Transducer Input

59P
Calculate
restraint

Amps
amps

59N
3

50BF-1
50P-1

51P-1

Amps

67_2
50_2

51_2

21G

21P
67P
32

68

78

49

59_2
3V_0

ANSI Device Numbers & Functions


®

DEVICE DEVICE DEVICE


FUNCTION FUNCTION FUNCTION
NUMBER NUMBER NUMBER
21G Ground distance 50N Neutral instantaneous overcurrent 67N Neutral directional overcurrent
21P Phase distance 50P Phase instantaneous overcurrent 67P Phase directional overcurrent
24 Volts per hertz 50_2 Negative-sequence instantaneous overcurrent 67_2 Negative-sequence directional overcurrent
25 Synchrocheck 51G Ground time overcurrent 68 Power swing blocking
27P Phase undervoltage 51N Neutral time overcurrent 78 Out-of-step tripping
27X Auxiliary undervoltage 51P Phase time overcurrent 81O Overfrequency
32 Sensitive directional power 51_2 Negative-sequence time overcurrent 81R Rate of change frequency
49 Thermal overload protection 59N Neutral overvoltage 81U Underfrequency
50/87 Instantaneous differential overcurrent 59P Phase overvoltage 87RGF Restricted ground fault
50BF Breaker failure 59X Auxiliary overvoltage 87T Transformer differential
50G Ground instantaneous overcurrent 59_2 Negative-sequence overvoltage 87TF Inter-turn transformer protection

2 GEGridSolutions.com
T60 Transformer Protection System

Differential vs. Restraint Characteristic while exceeding the settable pickup level, an elements under heavy resistive loading
(ld vs.lr) operand is asserted, which can be used to block conditions.
Differential such sensitive elements.
Current (Id) Slope 2 Overcurrent Functions
Overexcitation Inhibit T60 provides thermal overload, time and
Break Point 2 An increase in transformer voltage or decrease instantaneous overcurrent elements for
Transition Region in system frequency may result in overexcitation phase, neutral, ground, phase and neutral
of the transformer. It is often desirable to prevent directional. The neutral directional overcurrent
operation of the percent differential element in element supports enhanced dual polarization
Break 1 these cases, therefore a fifth harmonic inhibit is modes which can be configured to prioritize
Slope 1 integrated into the percent differential element on voltage or current polarization. All of them
to cater to overexcitation conditions, resulting can run in parallel with primary differential
from an increased V/Hz ratio. protection or can be programmed to provide
Restraint Current (Ir)
primary protection under conditions when other
The settings for the dual-slope, dual-breakpoint
characteristic provides higher flexibility for Unrestrained Differential protection elements are blocked.
shaping up the characteristic and achieving An unrestrained differential element is provided
better sensitivity and security.
for fast tripping on heavy internal faults to User-Definable Protection Functions
limit catastrophic damage to the transformer Sixteen user-definable protection functions
and minimize risks to the remainder of the (FlexElements) can be programmed to respond
that may occur due to external disturbances,
power system. to any quantity measured or computed by the
such as transformer inrush or near generator
relay (phase, ground and sequence current and
faults, without sacrificing speed or sensitivity.
Restricted Ground Fault (RGF) voltage power, frequency, power factor, etc.)
Inter-turn fault detection RGF (also known as zero-sequence differential) These elements respond to variations in its input
extends protection coverage to the neutral signal. Applications could include: overvoltage,
This element is a complement to the percent
point of wye-connected windings where overpower, low power factor, temperature
differential function. It detects interturn
fault currents may be below the pickup of the differential, and more.
fault conditions using voltage compensated
main transformer differential elements. The
differential currents. The voltage-based
compensation term cancels out steady state
low-impedance RGF protection provided in IEC 61869* and 61850-9-2LE
the T60 uses an optimized adaptive restraint
differential current of each phase. The resulting
signal that provides security for external fault
Process Bus
compensated differential current is sensitive
conditions that may cause CT saturation while Three UR process bus modules enable
enough to pick up turn-to-turn faults.
still maintaining sensitivity for internal faults. communicating to Merging Units “MU” that
comply to either IEC 61869 standard or
Inrush Inhibit
Distance Protection IEC 61850-9-2LE technical report. MUs connect
The 2nd harmonic inhibit function is selectable to the primary asset and translate analog signals
Separate high-speed phase and ground
in order to cover the energization of different and digital status/commands to standard
distance elements are provided in T60 as a
types of transformers and can be set to either sample values “SV” data and GOOSE messages.
backup protection. T60 comes with five phase
traditional or adaptive mode. The adaptive
and ground distance quad and mho distance Flexibility for connecting to different network size
mode maximizes dependability on internal faults
elements. The phase distance elements come and topology is granted through 100Mbps and/
and ensures security during inrush conditions
with built-in in-zone transformer compensation. or 1Gbps Ethernet port support, plus IEC 62439
even with weak second harmonics. It reduces
The T60 also provides a load encroachment PRP or HSR standard redundancy, plus Star, Ring
the sensitivity of magnitude comparison by
element , which supervises the distance and Point-to-point network support.
biasing towards security, based on an angular
relationship. Dependability is maintained by
applying the restraint signal only for a period of
time, dependent on the magnitude ratio.

Harmonic/Inrush detection
A separate Harmonic detection element
monitors the selected 2nd to 5th harmonic
or Total Harmonics Distortion (THD), which is
present in the phase currents. The relay provides
six identical Harmonic Detection elements.

During transformer energization or motor starts,


the inrush current present in phase currents
can impact some sensitive elements, such as
negative sequence overcurrent . Therefore,
the ratio of the second harmonic to the Faults close to the neutral point of a wye-connected winding does not generate adequate fault current for
elements to detect. Restricted ground fault protection provides sensitive ground fault detection for low-
fundamental magnitude per phase is monitored, magnitude fault currents.

GEGridSolutions.com 3
T60 Transformer Protection System

For time synchronization purposes, this Process


bus module can become an IEEE 1588 slave Topologies:
PRP Start Station Bus
clock (61850-9-3 profile) or a 1588 Grand Master
clock which removes the need of external time Hot-Stanby
sources connected to the process bus network.

Customers who may not be using GE MU


devices, could use MU from other vendors. Integrated Station and
Interoperability with MU from other vendors is Process bus (available)
expected when they comply to the mentioned
standards.
Topologies: Process Bus:
HSR ring IEC 61850-9-2LE or 61869* SV
IEC 61850-9-2 HardFiber PRP start IEEE 1588 Grand Master or
Process Bus P-2-P Process Bus slave 61850-9-1 GOOSE
The IEC 61850 Process Bus module is designed
to interface with the Multilin HardFiber System,
allowing bi-directional IEC 61850 fiber optic
communications. The HardFiber System is Merging units
designed to integrate seamlessly with existing
UR applications, including protection functions,
FlexLogic™ metering and communications. Conventional or
Optical CT/VTs
The Multilin HardFiber System offers the
following benefits:

• Communicates using open standard CB closing time into account to perform FlexLogic
IEC 61850 messaging synchronism checks across breakers (up to six).
FlexLogic is the powerful UR-platform
• Drastically reduces P&C design, installation The T60 can be used in conjunction with an
programming logic engine that provides the
and testing labor by eliminating individual external synchronizer as an independent check
ability to create customized protection and
copper terminations of the synchronizer prior to closing the breaker.
control schemes, minimizing the need and
• Integrates with existing T60’s by replacing associated costs of auxiliary components and
traditional CT/VT inputs with the IEC 61850 Advanced Automation wiring. With 1024 lines of FlexLogic, the T60 can
Process Bus module be programmed to provide the required tripping
The T60 incorporates advanced automation
• Does not introduce new cyber security concerns logic along with custom scheme logic for line
features including powerful FlexLogic
phase comparison (including interlocking
Visit the HardFiber System product page on the programmable logic, communication, and
with external synchronizers), transfer tripping
GE Grid Solutions web site for more details. SCADA capabilities that far surpass what is
schemes for remote breakers and dynamic
found in the average transformer relay. The T60
Synchronism Check setting group changes.
integrates seamlessly with other UR relays for
The T60 provides six elements (as standard) complete system protection.
Scalable Hardware
to monitor differences in voltage magnitudes,
The T60 is available with a multitude of I/O
phase angles, and frequencies taking the
configurations to suit the most demanding
application needs. The expandable modular
design allows for easy configuration and future
upgrades.

• Multiple CT/VT configurations allow for


the implementation of many differential
schemes, including concurrent split-phase
and differential protection
• Types of digital outputs include trip-
rated Form-A and Solid State Relay (SSR)
mechanically latching, and
Form-C outputs
• RTDs and DCmA inputs are available to
monitor equipment parameters such as
temperature and pressure

Multi-breaker application example.

4 GEGridSolutions.com
T60 Transformer Protection System

Monitoring and Metering • Fault Reports • Comprehensive device health diagnostic


- Powerful summary report of pre-fault and performed at startup
The T60 includes high accuracy metering
fault values • Monitors the CT/VT input circuitry to validate
and recording for all AC signals. Voltage,
• Extensive breaker info (continuous coil monitor, the integrity of all signals
current , and power metering are built into
the relay as a standard feature. Current and arcing current, operating time, operation • Inputs, outputs, trip circuits and analog
counter for asset management) channels are continuously monitored for
voltage parameters are available as total RMS
magnitude, and as fundamental frequency The very high sampling rates and large amount accuracy and performance
magnitude and angle. For power quality of storage space available for data recording
in the T60 can eliminate the need for installing Advanced Asset Monitoring
applcations, harmonic measurements (up to the
25th) for voltage and current are available. costly stand-alone recording equipment. The T60 has advanced functions that raise
an alarm or trip the scheme when an internal
T60 can monitor, calculate and log hottest- Temperature Monitoring – RTD Module condition in the power transformer or breaker
spot temperature, aging factor and loss-of-life Option 5C could lead to a fault . These functions are
data over a long period. This data, combined conditions of:
The T60 RTD option provides 8 programmable
with economic analysis, allows criteria to be
RTD inputs per module that are used for • Hottest-spot temperature: element provides
developed regarding the best time at which to
temperature monitoring. Each RTD input has a mechanism for detecting abnormal
replace a power transformer due to load growth,
2 operational levels: alarm and trip. The T60 winding hottest-spot temperatures inside the
i.e. to minimize the cost without significantly
supports RTD trip voting and provides open RTD transformer.
increasing the risk.
failure alarming. Alternatively, a remote RTD
• Aging factor: the aging factor element
Fault and Disturbance Recording module “RRTD”, which supports 12 RTD inputs, detects transformer aging in per-unit normal
can also be used with the T60 for temperature insulation aging.
The advanced disturbance and event recording
monitoring. The RRTD provides cost savings
features within the T60 can significantly reduce • Loss of Life: The Loss of Life element detects the
when compared with traditional RTD wiring.
the time needed for postmortem analysis accumulated total consumed transformer life.
of power system events and the creation of Advanced Device Health Diagnostics • Breaker arcing current: This element
regulatory reports. Recording functions include: calculates an estimate of the per-phase
The T60 performs comprehensive device health
deterioration on the breaker contacts by
• Sequence of Event (SOE) 1024 time stamped diagnostic at startup and continuously during
measuring and integrating the current
events run-time to test its own major functions and
(squared) passing through the breaker
• Oscillography critical hardware. These diagnostic tests monitor
contacts as an arc.
- Supports IEEE C37.111-1999/2013, for conditions that could impact security and
availability of protection, and present device These elements allow the user to optimize
IEC 60255-24 Ed 2.0 COMTRADE standard
status via SCADA communications and front maintenance routines on the power transformer
- 128 digital & up to 56 analog channels
- Events with up to 45s length panel display. Providing continuous monitoring and breakers.

• Data Logger and Disturbance Recording and early detection of possible issues help
-1
 6 channels up to 1 sample/cycle/channel improve system uptime.

Power System Troubleshooting

Record the operation of the internal T60 Analyze transformer faults using both analog and
elements and external connected devices with digital power system quantities that are measured
1ms time-stamped accuracy to identify the and recorded up to a rate of 64 samples per cycle. Visualization of differential characteristics allows for
Sequence of Operation of station devices during setting verification and operation troubleshooting.
transformer faults and disturbances.

GEGridSolutions.com 5
T60 Transformer Protection System

Cyber Security – CyberSentry UR • IEC 61850 Ed. 1 and Ed. 2 Station Bus, interlocking, generation rejection and other
IEC 61850-2-2LE / IEC 61869* networked or special protection schemes.
CyberSentry UR enabled UR devices deliver full IEC 61850-9-2 HardFiber Process Bus, and
cyber security features that help customers to • Communication with up to 16 UR relays
IEC 61850-90-5 PMU over GOOSE support
comply with NERC CIP and NIST® IR 7628 cyber in single or redundant rings rather than
• DNP 3.0 (serial & TCP/IP) simplistic point-to-point configurations
security requirements.
• Ethernet Global Data (EGD) • Connect to standard DS0 channel banks
This software option delivers the following core
• IEC 60870-5-103 and IEC 60870-5-104 through standard RS422, G.703 or IEEE
features:
C37.94 interfaces or via direct fiber optic
• Modbus RTU, Modbus TCP/IP
connections
AAA Server Support (Radius/LDAP) • HTTP, TFTP, SFTP and MMS file transfer
• Built-in continuous loop and channel
Enables integration with centrally managed • IEEE 1588 and redundant SNTP for time monitoring provides real-time diagnostics
authentication and accounting of all user synchronization of your communication channels with no
activities and uses modern industry best
• PRP as per IEC 62439-3 external or handheld tester required
practices and standards that meet and exceed
NERC CIP requirements for authentication and • Supports Routable GOOSE (R-GOOSE) LAN Redundancy
password management.
Interoperability with Embedded Substation LAN redundancy has been traditionally

Role Based Access Control (RBAC) IEC 61850 Ed. 1 and Ed. 2 accomplished by reconfiguring the active network
topology in case of failure. Regardless of the type
The new IEC 61850 implementation in the UR
Efficiently administrate users and roles within of LAN architecture (tree, mesh, etc), reconfiguring
Family positions GE as an industry leader in this
UR devices. The new and advanced access the active LAN requires time to switchover, during
standard.
functions allow users to configure up to five which the LAN is unavailable. UR devices deliver
roles for up to eight configurable users with • Implements, user selectable, Ed. 1 and Ed. 2 redundancy as specified by PRP-IEC 62439-3,
independent passwords. The standard “Remote of the standard across the entire UR Family which eliminates the dependency on LAN
Authentication Dial In User Service” (Radius) is • Provides full relay setting management via reconfiguration and the associated switchover
used for authentication. standard SCL files (ICD, CID and IID) time. The UR becomes a dual attached node
• Enables automated relay setting that transmits data packets over both main and
Event Recorder (Syslog for SEM) redundant networks simultaneously, so in case
management using 3rd party tools through
Capture all cyber security related events within standard file transfer services (MMS and SFTP) of failure, one of the data packets will reach the
a SOE element (login, logout, invalid password receiving device with no time delay.
• Increases the number of Logical Devices and
attempts, remote/local access, user in session,
data mapped to them, GOOSE messages
settings change, FW update, etc), and then Multi-Language
from up to 64 remote devices, and reports
serve and classify data by security level using UR devices support multiple languages: English,
to support different organizational needs for
standard Syslog data format. This will enable data transfer and reduce dependency on French, Russian, Chinese, Turkish, German,
integration with established SEM (Security Event generic logical nodes Polish and Japanese. These language options
Management) systems. are available on the front panel, in the EnerVista
• Configures GE Systems based on IEC 61850
using universal 3rd party tools setup software, and in the product manuals.
Communications • Multicast IEEE C37.118 synchrophasor
Easily switch between English and an additional
language on the local displays without
The T60 provides advanced commun-ications data between PMU and PDC devices using
uploading new firmware.
technologies for remote data and engineering IEC 91850-90-5
access, making it the most advanced and • R-GOOSE enable customer to send GOOSE
flexible transformer protection relay to use and messages beyond the substation, which EnerVista Software
integrate into new and existing infrastructures. enables WAPC and more cost effective The EnerVista suite is an industry-leading set
Direct support for fiber optic Ethernet provides communication architectures for wide area of software programs that simplifies every
high-bandwidth communications allowing applications aspect of using the T60 relay. The EnerVista
for low-latency controls and high-speed suite provides all the tools to monitor the status
file transfers of relay fault and event record Direct I/O Messaging
of the transformer, maintain the relay, and
information. The available three independent Direct I/O allows for the sharing of high-speed integrate information measured by the T60 into
Ethernet ports, redundant Ethernet option digital information between multiple UR DCS or SCADA monitoring systems. Convenient
and the embedded managed Ethernet switch relays via direct back-to-back connections or COMTRADE and SOE viewers are an integral part
provide the means to create fault tolerant multiplexed through a standard DS0 multiplexer of the UR setup software included with every UR
communication architectures in an easy, channel bank. Regardless of the connection relay, to carry out postmortem event analysis
cost-effective manner without the need for method, direct I/O provides continuous real-time and ensure proper protection system operation.
intermediary communication hardware. The T60 channel monitoring that supplies diagnostics
supports the most popular industry standard information on channel health. EnerVista Launchpad
protocols enabling easy, direct integration into
Direct I/O provides superior relay-to-relay EnerVista Launchpad is a powerful software
DCS and SCADA systems.
communications that can be used in advanced package that provides users with all of the setup

6 GEGridSolutions.com
T60 Transformer Protection System

and support tools needed for configuring and with the following functionality: will create reports on the operating status of
maintaining Multilin products. The setup software the relay, simplify the steps to download fault
• Plug-&-Play Device Monitoring
within Launchpad allows for the configuration and event data, and reduce the work required
of devices in real-time by communicating • System Single-Line Monitoring & Control for cyber security compliance audits. Tools
using serial, Ethernet, or modem connections, • Annunciator Alarm Screens available in Viewpoint Maintenance include:
or offline by creating setting files to be sent to • Trending Reports • Settings Security Audit Report
devices at a later time. Included in Launchpad is
• Automatic Event Retrieval • Device Health Report
a document archiving and management system
that ensures critical documentation is up-to- • Automatic Waveform Retrieval • Single-Click Fault Data Retrieval
date and available when needed. Documents
Viewpoint UR Engineer EnerVista Integrator
made available include:
Viewpoint UR Engineer is a set of powerful tools EnerVista Integrator is a toolkit that allows
• Manuals
that allows you to configure and test GE relays seamless integration of Multilin devices into
• Application Notes & Support Documents at a system level in an easy-to-use graphical new or existing automation systems. Included in
• Guideform Specifications drag-and-drop environment . Viewpoint UR EnerVista Integrator:
Engineer provides the following configuration
• Brochures • OPC/DDE Server
and commissioning utilities:
• Wiring Diagrams • Multilin Drivers
• Graphical Logic Designer
• FAQ’s
• Graphical System Designer • Automatic Event Retrieval
• Service Bulletins
• Graphical Logic Monitor • Automatic Waveform Retrieval
Viewpoint Monitoring • Graphical System Monitor
Viewpoint Monitoring is a simple-to-use and • IEC 61850 Configurator
full-featured monitoring and data recording
software package for small systems. Viewpoint Viewpoint Maintenance
Monitoring provides a complete HMI package Viewpoint Maintenance provides tools that

User Interface LED indicators 7” large color graphic HMI


The T60 front panel provides extensive local HMI capabilities.
The local display is used for monitoring, status messaging, fault 8 user
diagnosis, and device configuration. User-configurable messages programmable
pushbuttons
that combine text with live data can be displayed when user-
defined conditions are met.

A 7” color, graphic HMI is optionally available that allows users to


have customizable bay diagrams with local monitoring of status,
values and control functionality. The alarm annunciator panel
provides the configuration of up to 96 signals (alarms and status)
with full text description. 10 side screen
pushbuttons

GEGridSolutions.com 7
8
TYPICAL CONFIGURATION
Typical Wiring

THE AC SIGNAL PATH IS CONFIGURABLE


OPEN DELTA
VT CONNECTION (ABC)
(5 amp CTs)
A A
B B
C C

WINDING 1
WINDING 2
(5 amp CTs)
T60 Transformer Protection System

A
B
C

WINDING 3

F7c
F8a
F1a
F2a
F3a

F5c
F6c
F5c
F6c
F8c
F1c
F2c
F3c
F4c
M1c
M2c
M3c
M4c
M5c
M6c
M7c
M8c

F1b
F2b
F4b
M1b
M2b
M3b
M4b
M5b
M8b

F3b

F5a
F6a
F7a
F5a
F6a
F7a
M3a
M4a
M5a
M6a

M2a

F4a

F7c
M6b
M7b

M1a
M7a
M8a

VX

VA
VA

VC
VC

VB
VB
IA
IB
IC
IA
IA

IB
IB

IC
IC

IG
IG
IG

VX

VA
VA

VC
VC

VB
VB
IA1
IG1

IA5
IG5

IB1
IC1

IB5
IA1
IA1

IC5
IG1
IG1

IA5
IA5

IG5
IG5

IB1
IB1

IC1
IC1

IB5
IB5

IC5
IC5

VOLTAGE INPUTS VOLTAGE INPUTS CURRENT INPUTS CURRENT INPUTS


VOLTAGE AND

8F / 8G 8H/ 8J

H7a CONTACT INPUT H7a DIGITAL INPUTS/OUTPUTS 6H I H1a TC 1


H7c CONTACT INPUT H7c 1 H1b
CURRENT SUPERVISION

V
H8a CONTACT INPUT H8a H1c
H8c CONTACT INPUT H8c I H2a
H7b COMMON H7b 2 H2b
V
H2c
H8b SURGE
I H3a
3 H3b
V TC 2
B1b H3c

1
CRITICAL

( DC ONLY )
B1a FAILURE
I H4a
B2b 4 H4b
V
B3a 48 VDC H4c
VOLTAGE SUPERVISION

B3b OUTPUT I H5a


DC
B5a MED 5 H5b

GEGridSolutions.com
V
B5b HI CONTROL H5c
AC or DC B6b LO POWER T60 TRANSFORMER PROTECTION SYSTEM I H6a
B6a 6 H6b
V
B8a SURGE H6c T60 COMPUTER

POWER SUPPLY
B8b FILTER
1 1 8
TXD 2 2 3 RXD
RXD 3 3 2 TXD
4 4 20
Fibre Tx1 100BaseFX

T
* Optic PORT 1 SGND 5 5 7 SGND
Rx1
6 6 6
Tx2 100BaseFX CONTACT INPUTS/OUTPUTS 6D 7 7 4
Rx2 PORT 2
8 8 5
Shielded Tx3 100BaseFX 9 9 22
Ground at Rx3 PORT 3 CONTACT INPUTS/OUTPUTS
twisted pairs 6C
UR
Device D1a
RS485 9 PIN 25 PIN
P1
P2
P3
P4
P5
P6
P7
P8

D2a
SURGE

COM 2 CONNECTOR CONNECTOR


D3a com

COMMON U1b
COMMON U3b
COMMON U5b
COMMON U7b

D4b RS-232

CONTACT INPUT U1c


CONTACT INPUT U2c
CONTACT INPUT U3c
CONTACT INPUT U4c
CONTACT INPUT U5c
CONTACT INPUT U6c
CONTACT INPUT U7c
CONTACT INPUT U8c

CONTACT INPUT U1a


CONTACT INPUT U2a
CONTACT INPUT U3a
CONTACT INPUT U4a
CONTACT INPUT U5a
CONTACT INPUT U6a
CONTACT INPUT U7a
CONTACT INPUT U8a

D4a IRIG-B
DB-9
Input
Co-axial BNC (front)

CPU
PERSONAL
COMPUTER
P1c
P2c
P3c
P4c
P5c
P6c
P7c
P8c

P1b
P2b
P3b
P4b
P5b
P6b
P7b
P8b

P1a
P2a
P3a
P4a
P5a
P6a
P7a
P8a

U1c
U2c
U3c
U4c
U5c
U6c
U7c
U8c

U1b
U3b
U5b
U7b
U8b

U1a
U2a
U3a
U4a
U5a
U6a
U7a
U8a

828782A4.CDR
MODULE ARRANGEMENT
X W V U T S R P N M L K J H G F D B
6 6 6 6 8 9 1
Inputs/ Inputs/
outputs outputs CT Inputs/ CT/VT CPU Power
No. 10AWG * * outputs supply
minimum This diagram is based on the following order code:
GROUND BUS (Rear view) T60-T00-HCL-F8F-H6H-M8H-P6C-U6D-WXX
CONTACTS SHOWN * Optional
WITH NO This diagram provides an example of how the device
MODULES MUST BE CONTROL POWER
GROUNDED IF
is wired, not specifically how to wire the device. Please
TERMINAL IS refer to the Instruction Manual for additional details on
PROVIDED wiring based on various configurations.

Copyright GE Multilin Inc. All rights reserved.


Ordering
T60 - * 00 - H * * - F ** - H ** - M ** -P ** - U ** - W/X ** For Full Sized Horizontal Mount
Base Unit T60 Base Unit
CPU E RS485 + RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-455
Software Options1, 3 & 4 00 No Software Options
01 Ethernet Global Data (EGD)
03 IEC 61850
04 Ethernet Global Data (EGD) + IEC 61850
06 PMU
07 IEC 61850 + PMU
10 Synchrocheck
11 Synchrocheck + IEC 61850
23 5 windings (No Breaker Failure) + EGD + IEC 61850
33 PMU + Synchrocheck
34 PMU + IEC 61850 + Synchrocheck
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry. Req UR FW 7.xx or higher
M0 IEC 61850 + PMU + 61850-90-5
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel5
O Enhanced Polish Front Panel with User-Programmable Pushbuttons5
Z Enhanced Japanese Front Panel5
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons5
Power Supply H 125 / 250 V AC/DC
2

H RH 125/250 V AC/DC with redundant 125/250 V AC/DC


L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
IEC 61850 Process Bus6, 7 81 8 Port IEC 61850 Process Bus Module
85 -9-2LE & 61869* Process Bus, 2 x 1000BaseF
86 -9-2LE & 61869* Process Bus, 4 x 1000BaseF + 4 x 100BaseFx
87 -9-2LE & 61869* Process Bus, 4 x 100BaseFx
Digital I/O XX XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
6W 6W 6W 6W 6W 6W 30 Contact Inputs - Pin Terminals5
6X 6X 6X 6X 6X 6X 18 Form-A (No Monitoring) Outputs - Pin Terminals5
Transducer I/O 5A 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5C 5C 5C 5C 5C 5C 8 RTD Inputs
5E 5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2B C37.94SM, 1300nm singlemode, ELED, 2 Channel singlemode
Ordering Notes:
1. To view all the options available for T60, please visit GE’s On-Line Store
http://store.gedigitalenergy.com/viewprod.asp?model=T60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type. Maximum 2 per chassis.
GEGridSolutions.com
3. All “5 windings (No breaker Failure)” options become “6 windings w/breaker failure” when FW v7xx is chosen. IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
4. Synchro-Check elements (25) are part of the standard features. Applies to FW version 7.4 and above trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
5. Option available soon Schneider Automation.NERC is a registered trademark of North American Electric Reliability Council.
6. Process bus module requires empty slots next to it.
NIST is a registered trademark of the National Institute of Standards and Technology.
7. Conventional DSP and
Footnote: * Upcoming release Process Bus modules cannot run simultaneously GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
Electric Company. GE reserves the right to make changes to specifications of products described at
any time without notice and without obligation to notify any person of such changes.

Copyright 2020, General Electric Company. GEA-12650N(EN)