Grid Solutions

Multilin G30
Protection for Small to Medium Generators Protection and Control
Combined Generators and Transformers • Generator differential protection including
transformer
The MultilinTM G30 generator protection system provides comprehensive protection for small to medium-
• Restricted ground fault, thermal overload
sized steam, hydraulic and combustion-turbine generators as well as applications that have both the protection, directional, time, instantaneous,
generator and transformer in the same zone of protection. phase, neutral, negative sequence and ground
The G30 is ideal for protecting single and multi-pole generators with single or split-phase winding overcurrent protection
configurations of generators. The G30 includes advanced automation and communication capabilities, • Advanced functionalities such as Loss of
extensive I/O options, and powerful fault recording features that can simplify fault and disturbance excitation, overexcitation, 3rd Harmonic
troubleshooting and minimize generator downtime. neutral undervoltage, Generator unbalance,
reverse and low forward power and
accidental energization
Key Benefits
• Protection and control functionality in one
• Advanced automation capabilities for providing customized protection and control solutions box, reducing the number of devices
• Combined generator and transformer protection solution extending asset life • High density inputs/outputs to support the
• An integrated large, full color display, provides real-time visualization and control of the protected bay, control of many switchyard assets – all from
via a bay mimic as well as annunciator functionality and graphical visualization of phasors one powerful device
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and • Integrated large, full color display, for real-time
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869 or IEC 61850-9-2 Hardfiber) ensures visualization and control of the protected bay
interoperability, device managing optimization and reduced cost of ownership
• Routable GOOSE (R-GOOSE) enables GOOSE messages going beyond the substation, which enables
wide area protection and control applications
Advanced Communications
• 3 independent Ethernet ports for simultaneous
• Increased network availability via failover time reduced to zero through IEC® 62439-3 “PRP” support
& dedicated network connections with
• Supports latest edition of waveform capture (COMTRADE 2013) simplifying fault records management IEEE 1588 support
• IEC 61850-9-2LE/IEC 61869 networked or
Applications IEC61850-9-2 Hardfiber process bus support
• Small to medium-sized generators typically driven by steam, gas or hydraulic turbines
• Pumped storage generators Cyber Security
• Combined generator and transformer in the zone of protection • CyberSentry™ provides high-end cyber security
• Distributed Generator (DG) interconnect protection as per IEEE® 1547 aligned to industry standards and services
(NERC® CIP, AAA, Radius, RBAC, Syslog)

Monitoring & Metering


• Advanced recording capabilities with high-
capacity event recorder, configurable and
extended waveform capture and data logger
• Metering: current, voltage, power, energy,
frequency, and harmonics
G30 Generator Protection System

Protection and Control additional interposing CTs to account for the Overexcitation Inhibit
difference in parameters measured by the relay.
As part of the UR family of Protection & Control An increase in transformer voltage or decrease
Advanced CT saturation and failure detection
devices, the Multilin G30 offers a high degree in system frequency may result in overexcitation
algorithms maintain immunity to high current
of modularity in its design and functionality, of the transformer. It is often desirable to
AC and low current DC saturation conditions
providing superior performance while meeting prevent operation of the percent differential
that may occur due to external disturbances,
the toughest requirements of the marketplace. element in these cases. Therefore a fifth
such as transformer inrush or near generator
Advanced protection and control features of this harmonic inhibit is integrated into a percent
faults, without sacrificing speed or sensitivity.
relay includes: differential function to protect for overexcitation
conditions resulting from an increased
2nd Harmonic Inrush Inhibit
Generator/Transformer Differential V/Hz ratio. The overexcitation inhibit works on a
The G30 utilizes a 2nd harmonic inrush inhibit function per-phase basis and is user-definable.
High-speed percent differential protection
to block the G30 from tripping under transformer
is provided for detecting and clearing both
inrush conditions that can otherwise cause the
generator stator and transformer winding
differential element to maloperate. This element can
faults that occur in the zone of protection of
be configured to include the energization of different
a single generator. The differential protection
types of transformers by using either a traditional
element has built-in phase compensation and
or adaptive mode of 2nd harmonic restraint.
magnitude compensation characteristics that
The adaptive 2nd harmonic restraint maintains
allow for dealing with the inherent offset that
protection dependability and speed on internal faults
occurs with CTs located on different windings
while ensuring security during inrush conditions even
of the transformer. These compensation
with weak second harmonics.
characteristics eliminate the need for installing

Functional Block Diagram


PTs Located on Transformer HV Side

CLOSE 25
TRIP
24 27P 59P 59_2 59N 81O 81U 81R

32 40 50/27 49 50P 50N 51PV 51N 46 67P 67_2 67N

87G

METERING
87GT

50G 51G
27TN 27X 59X

G30 Generator Protection System

ANSI® Device Numbers & Functions


DEVICE DEVICE DEVICE
FUNCTION FUNCTION FUNCTION
NUMBER NUMBER NUMBER
24 Volts Per Hertz 50N Neutral Instantaneous Overcurrent 59_2 Negative Sequence Overvoltage
25 Synchronism Check 50P Phase Instantaneous Overcurrent 67_2 Negative Sequence Directional Overcurrent
27P Phase Undervoltage 50SP Split Phase Instantaneous Overcurrent 67N Neutral Directional Overcurrent
27TN Third Harmonic Neutral Undervoltage 50/27 Accidental Energization 67P Phase Directional Overcurrent
27X Auxiliary Undervoltage 51G Ground Time Overcurrent 81O Overfrequency
32 Directional Power 51N Neutral Time Overcurrent 81R Rate of Change of Frequency
40 Loss of Excitation 51PV Phase Time Overcurrent with Voltage Restraint 81U Underfrequency
46 Generator Unbalance 59N Neutral Overvoltage 87GT Generator/Transformer Differential
49 Thermal Overload 59P Phase Overvoltage 87G Restricted Ground Fault
50G Ground Instantaneous Overcurrent 59X Auxiliary Overvoltage

2 GEGridSolutions.com
G30 Generator Protection System

2nd Harmonic Blocking Characteristic Loss of Excitation


Generator loss of excitation protection
is provided via two negative offset mho
characteristics as per IEEE C37.102. Independent
pickup time delay settings and blocking input
provide security for blown VT fuses and power
swing conditions.

Frequency Rate of Change


The four available frequency rate of change
(df/dt) elements can be used to provide
protection against system disturbances
through load shedding and to provide anti-
islanding protection. These elements monitor
the speed by which the frequency changes in
The adaptive 2nd harmonic inhibit function will stop blocking the differential element as soon as the 2nd any direction, through voltage, current , and
harmonic level drops below the pickup level if the angle of the 2nd harmonic to fundamental ratio is close
frequency supervision.
to 0° or 180° (Point A). If the angle of the 2nd harmonic to fundamental ratio is close to 90°or 270°, this is
an indication that the transformer is an inrush condition, even if the magnitude drops below the pickup
level. The adaptive 2nd harmonic inhibit function will continue to block the differential element for an Pump Storage Generator
extended period of time (Point B).
The G30 provides six elements to monitor
differences in voltage magnitudes, phase
angles, and frequencies taking the CB closing
Split-Phase Protection pickup of the main stator differential element.
time into account to perform synchronism
The low-impedance RGF protection provided
Split-phase protection is provided for sensitive checks across breakers. The G30 can be used in
by the G30 uses an optimized adaptive restraint
detection for inter-turn faults and can be run in conjunction with an external synchronizer as an
signal that provides security for external fault
conjunction with the primary stator differential independent check of the synchronizer prior to
conditions that may cause CT saturation while
protection. Independent settings are provided closing the generator breaker.
still maintaining sensitivity for internal faults.
on a per-phase basis and a single-slope bias
characteristic is used to allow operation on Synchronism Check
Sensitive Directional Power
machines with a section of winding bypassed.
The G30 provides four elements to monitor
Two separate directional power elements are
differences in voltage magnitudes, phase angles,
Restricted Ground Fault (RGF) provided to detect reverse and low forward power
and frequencies to perform synchronism checks
conditions that are often needed for ensuring
Restricted ground fault protection (also known across breakers (up to four). The G30 can be used
power only flows in one direction through the
as zero-sequence differential) extends protection in conjunction with an external synchronizer as
breaker. Each element responds to either reverse
coverage to the neutral point of the stator an independent check of the synchronizer prior
or low forward power flow and can be used to
winding, where fault currents may be below the to closing the generator breaker.
provide independent alarm and trip settings.

IEC 61869 and 61850-9-2LE Process Bus


Three UR process bus modules enable
No Transformer
communicating to Merging Units “MU” that
comply to either IEC 61869 standard or
CLOSE IEC 61850-9-2LE technical report. MUs connect
25
TRIP
to the primary asset and translate analog signals
24 27P 59P 59_2 59N 81O 81U 81R and digital status/commands to standard sample
values “SV” data and GOOSE messages.

32 40 50/27 49 50P 50N 51P 51N 46 67P 67_2 67N Flexibility for connecting to different network size
and topology is granted through 100Mbps and/or
1Gbps Ethernet port support, plus IEC 62439 PRP
or HSR standard redundancy, plus Star, Ring and
Point-to-point network support.
METERING
87S For time synchronization purposes, this Process
bus module can become an IEEE 1588 slave
87G 50G 51G clock (61850-9-3 profile) or a 1588 Grand Master
27TN 27X 59X clock which removes the need of external time
sources connected to the process bus network.
G30 Generator Protection System

GEGridSolutions.com 3
G30 Generator Protection System

Customers who may not be using GE MU Topologies:


devices, could use MU from other vendors. PRP Start Station Bus
Interoperability with MU from other vendors is Hot-Stanby
expected when they comply to the mentioned
standards.

IEC 61850-9-2 HardFiber Process Bus Integrated Station and


Process bus (available)
The IEC 61850 Process Bus module is designed
to interface with the Multilin HardFiber System,
allowing bi-directional IEC 61850 fiber optic
communications. The HardFiber System is Topologies: Process Bus:
designed to integrate seamlessly with existing HSR ring -9-2LE or 61869* SV
UR applications, including protection functions, PRP start IEEE 1588 Grand Master or
P-2-P Process Bus slave 61850-9-1 GOOSE
FlexLogic™, metering and communications.

The Multilin HardFiber System offers the


following benefits:

• Communicates using open standard Mergin units


IEC 61850 messaging
• Drastically reduces P&C design, installation
and testing labor by eliminating individual Conventional or
copper terminations Optical CT/VTs

• Integrates with existing G30’s by replacing


traditional CT/VT inputs with the IEC 61850
Process Bus module • Multiple CT/VT configurations allow for • Oscillography
• Does not introduce new cyber security concerns the implementation of many differential - Supports IEEE C37.111-1999/2013,
schemes, including concurrent split-phase and IEC 60255-24 Ed 2.0 COMTRADE standard
Visit the HardFiber System product page on the
differential protection - 64 digital & up to 40 analog channels
GE Grid Solutions web site for more details.
• Flexible, modular high density I/O covering - Events up to 45s in length
a broad range of input signals and tripping • Data Logger and Disturbance Recording
Advanced Automation schemes - 16 channels up to 1 sample/cycle/channel
The G30 incorporates advanced automation • Up to 80 digital inputs and up to 56 digital • Fault Reports
features including powerful FlexLogic outputs are available - Powerful summary report of pre-fault and
programmable logic, communication, and SCADA • Types of digital outputs include trip-rated Form-A fault values
capabilities that far surpass what is found in the and Solid State Relay (SSR) mechanically The very high sampling rates and large amounts
average generator relay. The G30 integrates latching, and of storage space available for data recording in
seamlessly with other UR relays for complete Form-C outputs the G30 can eliminate the need for installing
system protection, including the unit and auxiliary
• RTDs and DCmA inputs are available to monitor costly stand-alone recording equipment.
transformers, and balance of plant protection.
equipment parameters such as temperature
and pressure Advanced Device Health Diagnostics
FlexLogic
The G30 performs comprehensive device health
FlexLogic is the powerful UR-platform
programming logic engine that provides the
Monitoring and Metering diagnostic tests at startup and continuously
during run-time to test its own major functions
ability to create customized protection and The G30 includes high accuracy metering and and critical hardware. These diagnostic tests
control schemes, minimizing the need and recording for all AC signals. Voltage, current, monitor for conditions that could impact security
associated costs of auxiliary components and and power metering are built into the relay as a and availability of protection, and present
wiring. With 1024 lines of FlexLogic, the G30 can standard feature. Current and voltage parameters device status via SCADA communications
be programmed to provide the required tripping are available as total RMS magnitude, and as and front panel display. Providing continuous
logic along with custom scheme logic for fundamental frequency magnitude and angle. monitoring and early detection of possible
generator breaker control (including interlocking issues help improve system uptime.
with external synchronizers), transfer tripping Fault and Disturbance Recording
• Comprehensive device health diagnostic
schemes for remote breakers and dynamic The advanced disturbance and event recording performed at startup
setting group changes. features within the G30 can significantly reduce
• Monitors the CT/VT input circuitry to validate
the time needed for postmortem analysis
Scalable Hardware the integrity of all signals
of power system events and the creation of
The G30 is available with a multitude of I/O regulatory reports. Recording functions include: • Input, outputs, trip circuits and analog
configurations to suit the most demanding channels are continuously monitored for
• Sequence of Event (SOE) accuracy and performance
application needs. The expandable modular design
- 1024 time stamped events
allows for easy configuration and future upgrades.

4 GEGridSolutions.com
G30 Generator Protection System

Cyber Security - CyberSentry UR Communications Interoperability with Embedded


IEC 61850 Ed. 1 and Ed. 2
CyberSentry UR enabled UR devices deliver full The G30 provides advanced commun-ications
cyber security features that help customers to technologies for remote data and engineering The new IEC 61850 implementation in the UR
comply with NERC CIP and NIST® IR 7628 cyber access, making it the easiest and most flexible Family positions GE as an industry leader in this
security requirements. This software option generator protection relay to use and integrate standard.
delivers the following core features: into new and existing infrastructures. Direct
• Implements, user selectable, Ed. 1 and Ed. 2
support for fiber optic Ethernet provides
of the standard across the entire UR Family
AAA Server Support (Radius/LDAP) high-bandwidth communications allowing
for low-latency controls and high-speed • Provides full relay setting management via
Enables integration with centrally managed standard SCL files (ICD, CID and IID)
file transfers of relay fault and event record
authentication and accounting of all user
information. The available three independent • Enables automated relay setting
activities and uses modern industry best
Ethernet ports, redundant Ethernet option management using 3rd party tools through
practices and standards that meet and exceed
and the embedded managed Ethernet switch standard file transfer services (MMS and SFTP)
NERC CIP requirements for authentication and
provide the means to create fault tolerant
password management. • Increases the number of Logical Devices and
communication architectures in an easy,
data mapped to them, GOOSE messages
cost-effective manner without the need for
Role Based Access Control (RBAC) from up to 64 remote devices, and reports
intermediary communication hardware.
to support different organizational needs for
Efficiently administrate users and roles within
The G30 supports the most popular industry data transfer and reduce dependency on
UR devices. The new and advanced access
standard protocols enabling easy, direct generic logical nodes
functions allow users to configure up to five
integration into DCS and SCADA systems. • Configures GE Systems based on IEC 61850
roles for up to eight configurable users with
independent passwords. The standard “Remote • IEC 61850 Ed. 1 and Ed. 2 Station Bus, using universal 3rd party tools
Authentication Dial In User Service” (Radius) is IEC 61850-2-2LE / IEC 61869 networked or • R-GOOSE enable customer to send GOOSE
used for authentication. IEC 61850-9-2 HardFiber Process Bus, and messages beyond the substation, which
IEC 61850-90-5 PMU over GOOSE support enables WAPC and more cost effective
Event Recorder (Syslog for SEM) • DNP 3.0 (serial & TCP/IP) communication architectures for wide area
Capture all cyber security related events within applications
• Ethernet Global Data (EGD)
a SOE element (login, logout, invalid password
• IEC 60870-5-103 and IEC 60870-5-104 Direct I/O Messaging
attempts, remote/local access, user in session,
settings change, FW update, etc), and then • Modbus RTU, Modbus TCP/IP Direct I/O allows for the sharing of high-speed
serve and classify data by security level using • HTTP, TFTP, SFTP and MMS file transfer digital information between multiple UR
standard Syslog data format. This will enable relays via direct back-to-back connections or
• IEEE1588 and redundant SNTP for time
integration with established SEM (Security Event multiplexed through a standard DS0 multiplexer
synchronization
Management) systems. channel bank. Regardless of the connection
• PRP as per IEC 62439-3 method, direct I/O provides continuous real-time
• Supports Routable GOOSE (R-GOOSE) channel monitoring that supplies diagnostics
information on channel health.

Power System Troubleshooting

The G30 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

GEGridSolutions.com 5
G30 Generator Protection System

Direct I/O provides superior relay-to-relay Multi-Language modem connections, or offline by creating
communications that can be used in advanced setting files to be sent to devices at a later time.
UR devices support multiple languages: English,
interlocking, generation rejection and other
French, Russian, Chinese, Turkish, German, Included in Launchpad is a document archiving
special protection schemes.
Polish and Japanese. These language options and management system that ensures critical
• Communication with up to 16 UR relays are available on the front panel, in the EnerVista documentation is up-to-date and available when
in single or redundant rings rather than setup software, and in the product manuals. needed. Documents made available include:
simplistic point-to-point configurations Easily switch between English and an additional
• Manuals
• Connect to standard DS0 channel banks language on the local displays without
uploading new firmware. • Application Notes
through standard RS422, G.703 or IEEE
C37.94 interfaces or via direct fiber optic • Guideform Specifications
connections
EnerVista Software • Brochures
• Built-in continuous loop and channel • Wiring Diagrams
The EnerVista suite is an industry-leading set
monitoring provides real-time diagnostics
of software programs that simplifies every • FAQs
of your communication channels with no
aspect of using the G30 relay. The EnerVista • Service Bulletins
external or handheld tester required
suite provides all the tools to monitor the status
LAN Redundancy of your generator, maintain your relay, and Viewpoint Monitoring
integrate information measured by the G30 into Viewpoint Monitoring is a simple-to-use and
Substation LAN redundancy has been
DCS or SCADA monitoring systems. Convenient full-featured monitoring and data recording
traditionally accomplished by reconfiguring
COMTRADE and SOE viewers are an integral part software package for small systems. Viewpoint
the active network topology in case of failure.
of the UR setup software included with every UR Monitoring provides a complete HMI package
Regardless of the type of LAN architecture (tree,
relay, to carry out postmortem event analysis to with the following functionality:
mesh, etc), reconfiguring the active LAN requires
ensure proper protection system operation.
time to switchover, during which the LAN is • Plug & Play Device Monitoring
unavailable. UR devices deliver redundancy as EnerVista Launchpad
• System Single-Line Monitoring & Control
specified by PRP-IEC 62439-3, which eliminates
EnerVista Launchpad is a powerful software
the dependency on LAN reconfiguration and the • Annunciator Alarm Screens
package that provides users with all of
associated switchover time. The UR becomes a • Trending Reports
the setup and support tools needed for
dual attached node that transmits data packets
configuring and maintaining Multilin products. • Automatic Event Retrieval
over both main and redundant networks
The setup software within Launchpad allows • Automatic Waveform Retrieval
simultaneously, so in case of failure, one of the
for the configuration of devices in real-time
data packets will reach the receiving device with
by communicating using serial, Ethernet , or
no time delay.

Providing Traceability and Regulatory


Audit Tracking
The G30 tracks and records information about
configuration changes that have been made to
the relay, providing a method to audit system
security and engineering processes.

6 GEGridSolutions.com
G30 Generator Protection System

Viewpoint UR Engineer Viewpoint Maintenance EnerVista Integrator


Viewpoint UR Engineer is a set of powerful tools Viewpoint Maintenance provides tools that EnerVista Integrator is a toolkit that allows
that allows you to configure and test GE relays will create reports on the operating status of seamless integration of Multilin devices into
at a system level in an easy-to-use graphical the relay, simplify the steps to download fault new or existing automation systems. Included in
drag-and-drop environment . Viewpoint UR and event data, and reduce the work required EnerVista Integrator is:
Engineer provides the following configuration for cyber security compliance audits. Tools
• OPC/DDE Server
and commissioning utilities: available in Viewpoint Maintenance include:
• Multilin Drivers
• Graphical Logic Designer • Settings Security Audit Report
• Automatic Event Retrieval
• Graphical System Designer • Device Health Report
• Automatic Waveform Retrieval
• Graphical Logic Monitor • Single-Click Fault Data Retrieval
• Graphical System Monitor

User Interface
The G30 front panel provides extensive local LED indicators 7” large color graphic HMI
HMI capabilities. The local display is used for
monitoring, status messaging, fault diagnosis, 8 user
and device configuration. User-configurable programmable
messages that combine text with live data can be pushbuttons
displayed when user-defined conditions are met.

A 7” color, graphic HMI is optionally available that


allows users to have customizable bay diagrams
with local monitoring of status, values and control
functionality. The alarm annunciator panel
provides the configuration of up to 96 signals 10 side screen
(alarms and status) with full text description. pushbuttons

GEGridSolutions.com 7
G30 Generator Protection System

Typical Wiring
ALTERNATE

A A

52 B B

C C

NOTE:

R
M1a

M2a

M3a

M4a
M1b

M2b

M3b

M4b
M1c

M2c

M3c

M4c

F1a
F1b

F2a

F2b

F3a

F3b

F4a

F4b

F5a

F6a

F7a

F8a

F5a

F6a

F7a
F1c

F2c

F3c

F4c

F5c

F6c

F7c

F8c

F5c

F6c

F7c
VB

VC
VA
VB

VC

VX
VA
IG

IG1
IC
IA

IB

IC1
IA1

IB1

VB

VC
IG5

VA
IC5
IA5

IG
IB5

IG1
IC
IA

IB

IC1
IA1

IB1

VB

VC
IG5

VA

VX
IC5
IA5

IB5
H5a 6G I H1a TC 1
H5c H1
V
H1b
H6a H1c
H6c I H2a
H5b H2
V
H2b
H2c
H7a I H3a
H7c TC 2
H3
V
H3b
H8a
H3c
H8c I H4a
H7b
H4
V
H4b
H8b SURGE H4c

B1b
CRITICAL
1

B1a FAILURE

DC
B2b
B3a G30 GENERATOR MANAGEMENT RELAY
B3b OUTPUT
B5b HI
CONTROL
B6b LO
POWER
B6a
RS-232
B8a SURGE (front)
B8b FILTER
DB-9

* Fibre
Optic
Tx1 10BaseFL
NORMAL
Rx1
UR COMPUTER
Tx2 10BaseFL COM
ALTERNATE 1 1 8
Rx2 1
TXD 2 2 3 RXD
Shielded 10BaseT RXD 3 3 2 TXD
Remote 4 4 20
Device D1a
RS485 SGND 5 5 7 SGND
D2a
D3a com 6 6 6
D4b 7 7 4
D4a IRIG-B 8 8 5
Input 9 9 22
Co-axial BNC

IRIG-B
Co-axial BNC Output CONNECTOR
CONNECTOR

830744A2.CDR

minimum
X W V U T S R P N M L K J H G F D B
GROUND 8 6 8 9 1
PROVIDED
BUS
CT Inputs/ VT/CT CPU Power
outputs Supply

G30-H00-HCH-F8F-H6G-M8H-PXX-UXX-WXX

8 GEGridSolutions.com
Ordering
G30 - * 00 - H * * - F ** - H ** - M ** - P ** - U ** - W/X ** For Full Sized Horizontal Mount
Base Unit G30 Base Unit
CPU E RS485 + RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-453
Software Options1 00 No Software Options
01 Ethernet Global Data (EGD)
03 IEC 61850
04 Ethernet Global Data (EGD) + IEC 61850
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry. Req UR FW 7.xx or higher
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Environment Coating
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Environment Coating
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel3
O Enhanced Polish Front Panel with User-Programmable Pushbuttons3
Z Enhanced Japanese Front Panel3
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons3
Power Supply2 H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive ground 8CT w/ enhanced diagnostic
IEC 61850 Process Bus4, 5 81 8 Port IEC 61850 Process Bus Module
85 -9-2LE & 61869 Process Bus, 2 x 1000BaseF
86 -9-2LE & 61869 Process Bus, 4 x 1000BaseF + 4 x 100BaseFx
87 -9-2LE & 61869 Process Bus, 4 x 100BaseFx
Digital I/O XX XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
6W 6W 6W 6W 6W 6W 30 Contact Inputs - Pin Terminals3
6X 6X 6X 6X 6X 6X 18 Form-A (No Monitoring) Outputs - Pin Terminals3
Transducer I/O 5C 5C 5C 5C 5C 5C 8 RTD Inputs
5E 5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7R G.703, 1 Channels
7S G.703, 2 Channels
7T RS422, 1 Channels
7W RS422, 2 Channels
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2A C37.94SM, 1300nm singlemode, ELED, 1 Channel singlemode
2B C37.94SM, 1300nm singlemode, ELED, 2 Channel singlemode
Ordering Note:
 .To view all the options available for G30, please visit GE’s On-Line Store at http://store.
1
gedigitalenergy.com/viewprod.asp?model=G30
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same GEGridSolutions.com
type. Maximum 2 per chassis
3. Option available soon IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
4. Process bus module requires empty slots next to it. trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
5. Conventional DSP and Process Bus modules cannot run simultaneously Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.

GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.

Copyright 2018, General Electric Company. All Rights Reserved.


12757J(EN)
English
181218