MGE Galaxy 6000

TM TM

“High availability, High performance”

250/300/400/500/600 kVA

>
Performance 3 Phase Power
Protection with high active power
to Meet the Unique Requirements
of very Large Datacenters,
Buildings and Mission Critical
Environment

> Flexible and very adaptable


> Strong electrical features
> Parallel capable Output
Synchronization to External Source
> High availability architectures
component
> Large tactile color display
Dedicated system for large data
centers and ultra sensitive high
power demand processes
DATA CENTERS AND PROCESS INDUSTRY
TELECOMMUNICATIONS
Easy to upgrade Operation under all
Flexibility for upgrade without any risk is a conditions
major requirement for strategic data centers,
Manufacturing conditions often create a
second only to power availability and
very harsh environment for equipment.
quality.
Dust, damp, vibration, large temperature
Most data centers start with a requirement
variations - processes must be able to
for a few hundred kVA which increases to
operate without failure despite such
several MVA as the data centre becomes
conditions.
populated. The power uplift is without loss
MGETM GalaxyTM 6000 has been designed
of continuity and planned when required.
to be robust, mechanically as well as
Various paralleling options of the MGETM
electrically, and is ideally suited for
GalaxyTM 6000 can provide ideal solution to
providing an uninterruptible power supply.
match this need.
> High overload
In conjunction with Static Transfer Switches
> Stable output voltage even during load
(STS),MGETM GalaxyTM 6000 UPSs can
transients.
supply power to two or three separate
> High ingress protection, strong, reinforced
circuits for double or triple input power
enclosure, dust filters.
supply units that are regularly used in data
> Compatible with wide range of open lead
centers.
acid, sealed lead acid and nickel cadmium
type batteries.
APC by Schneider design office
Green Data Centers and dedicated engineering division
The compact MGETM GalaxyTM 6000 has are able to modify standard
high efficiency, input harmonic reduction products or customize them
and improved Power Factor which makes it for particular requirements:
ideal for organizations committed to Green > anti-vibration mountings for maritime
Data Centre design. applications
> custom paint and markings.

Meets Data Center TIA 942


and TIER IV requirements*
The data centre world is becoming more
uniform and standardized. MGE offers
solutions based on MGETM GalaxyTM 6000
UPSs, UPSILON Static Transfer Switches
and expert design and installation services
to meet TIA 942 and the TIER IV
requirements defined by the Uptime
Institute.
Power quality and availability
assured continuity of service
Data communication is part of everyday DigiBat and Battery
operation in data centers,
telecommunications and manufacturing Monitoring: for digital
processes. battery management
In these particularly critical domains, a DigiBat uses the operating power level,
power cut may cause very serious temperature, age and type of battery
operating losses and risks for staff and parameters to adjust the battery charging
equipment as well as the image voltage for the operating conditions and
of the company. continuously calculates:
APC by Schneider Electric has designed its > the real backup time available
high power range to supply high quality > the remaining lifetime.
power 24 hours a day for all operating
conditions and applications. Digibat also:
> Tests the battery system automatically (at
High quality supply to intervals that can be set), without affecting
the battery capacity
applications > Raises an alarm if the batteries are low.
The on-line double conversion and variable
frequency switching enable the MGETM The optional B2000 and Cellwatch battery
GalaxyTM 6000 to supply high power quality monitoring systems monitor the battery
with: systems 24 hours a day and provide
> very low output distortion: THDU <3% predictive fault alarms for each battery
> stable output voltage even on during load block:
transients. > continuous voltage and internal resistance
Advantages: measurement for each block
> optimum operation of the equipment > identification of faulty blocks (trend
> longer life expectancy curves)
> protection of capital investment > possibility of replacing individual
> fault tolerant blocks.

Redundant architectures
The Uptime Institute recommends that, from
TIER II upwards, equipment should be
provided with multiple power sources.
For Tier III and IV, redundant power
distribution must be provided.
> Paralleled MGETM GalaxyTM 6000s provide
source redundancy.
> UPSILON Static Transfer Switches
provide redundant power distribution.

Batteries always available


Batteries ensure service continuity. APC by Advantages:
Schneider Electric takes particular care in > ensures that the battery is available
managing batteries > maximizes the lifetime, reduces
to ensure that they are always ready for monitoring and maintenance costs.
demanded duty.
Flexibility : for upgrading
without limits
MGETM GalaxyTM 6000 provides high power Advanced monitoring: wide
quality with different types of battery,
architectures and options and its great variety of protocols
modularity allows applications to be UPS monitoring is essential for managing
upgraded more or less without any risk to an installation and for making decisions if a
the load. problem should arise.
Local
The optional "Vision" display combines:
> functionality (mimic of the whole
Easy upgrading: more installation, measurements, trending,
power, greater redundancy statistics)
MGETM GalaxyTM 6000 can be installed > ease of use (large high definition color
singly or in parallel or with a common touch screen).
bypass and can therefore meet all needs to: Advantages:
> improve the power availability > rapid learning
> increase the power rating as the site > reduced risk of error, easy to monitor and
develops. control for effective, safe operation.
MGETM GalaxyTM 6000 UPSs can be Remote
synchronized with any other external power MGETM GalaxyTM 9000 incorporates all the
source (transformers, generator sets, UPSs, communications facilities that have
etc) and can supply power to Static Transfer been developed by APC to:
Switches (STS) to guarantee maximum > monitor the operation of the UPS and its
power availability. environment
> automatically shutdown the operating
systems of the servers supported by the
UPS
> supervise a group of UPSs.
Using:
> simple programmable relay
contacts
> J-Bus and Mod-Bus protocols to
communicate with a building management
system
> Ethernet 10/100 using HTTPS (Secure
Socket Layer) for monitoring via Internet.
Advantages:
> clean shutdown of servers to protect data
> real-time information about the UPS
status
> can be used with any network
management system.
Minimum total cost of
ownership
High efficiency:
reduced running costs
At 250 or 600 kVA, one of the key criteria of
the total cost of ownership is
the efficiency of the UPS system. The
smallest increase in efficiency
can provide significant savings in operating
costs.

The MGETM GalaxyTM 6000 has variable


frequency switching to give an
efficiency of 95%, even at 50% load.
Advantages:
> Savings in power consumption
> Reduction in size of air-conditioning
and ventilation systems

Reduction in size of mains


input equipment
The harmonic filters on the input to the
UPSs minimizes harmonic currents and
improves the power factor:
Advantages:
> Reduces the size of the circuit protection
devices on the UPS supply
> Reduces the cross-section of UPS supply
cables
> Can save up to 20% on the sizing of the
electrical infrastructure
The most comprehensive range of
services
Commissioning Maintenance contracts
Schneider Electric Critical Power and Cooling A maintenance contract on your UPS ensures a
Services provides commissioning service smooth running system allowing you to focus on
for all new equipment with support to meet your core business. A maintenance partnership with
your specific requirements. the company that manufacturers and installs your
UPS systems provides continuity and service levels
no one else can meet. APC by Schneider is pleased
to offer the industry's most comprehensive, efficient
Teleservice monitoring services and cost effective maintenance programs designed
Continuous monitoring, providing necessary in an á la carte fashion to tailor the program to your
alerts at the customers' sites and for the service specific needs.
centers, with powerful diagnostics: the availability While you can custom build a maintenance program
of the installation is monitored by the largest specific to your site, APC has devised 3 basic
network of experts. packages that cover a majority of the needs of our
customers. However, even these three packages
can be customized to your precise specifications
Managing an installation calls for and budget. For example, additional services such
as preventative maintenance visits, site inspections
Upgradeability and remote monitoring can be added to each
package so you get precisely the level of service
To be sure of benefiting from the management of an
you need.
installation, Schneider Electric Critical Power and
Cooling Services provides solutions for upgrading: • ULTRA :
• technical upgrading APC by Schneider’s most complete service
• upgrading battery functions package, Ultimate Agreements offer 7 x 24 back-up
• site audits, studies and analysis of the UPS featuring 30 minute call back time on all service
environment requests and on site arrival within four hours of your
call (not available in all areas). All parts,
• harmonic audits replacement spare parts, labor, and travel expenses
• upgrading the UPS function using Swap-Pac for associated with the call are included with Ultimate
adapting and anticipating changes in Agreements.
customers' requirements as well as providing
environmental end of life cycle management. • PREMIER :
For a superior level of coverage, Premier Service is
available Monday through Friday, from 8:00AM -
5:00PM, local time, perfect for most businesses.
This program guarantees a maximum 30-minute
callback time, with on-site arrival of your APC by
schneider engineer on the next business day or
sooner. All parts, replacement spare parts, labor,
and travel expenses associated with visiting your
site are included in this complete package.

• SELECT :
For a moderate level of coverage, Select Service
offers a discount on parts and labor associated with
corrective maintenance, 30-minutes maximum
callback time, and next business day or sooner on-
site arrival time. Parts, labor and travel expenses
associated with corrective maintenance are billed
separately at discounted time and material rates.
Technical characteristics
Rated power (kVA/KW) 250/200 300/240 400/320 500/400 600/480
Normal AC supply input
Input voltage range 323 V to 470 V
Normal and backup supplies Separate or Common
Frequency 50 or 60 Hz +/- 10%
THDI (with filter) < 4 % with harmonic filter
Input power factor > 0,95 with harmonic filter
AC bypass input
Input voltage range 320V to 470V +/- 3% three phase + neutral
Frequency 50 or 60 Hz +/- 10%
Output
Output voltage 380/400/415 v +/- 3% three phase + neutral
Voltage regulation +/- 1%
Frequency 50 or 60 Hz
Overload 165%(0) 1 minute, 125% 10 minutes
Output voltage total harmonic distortion THDU < 3%
Max. load crest factor 3:1
Variation of voltage with 100% load step ± 5%
Batteries
Backup time 8-10-15-20-30-60 minutes, others on request
Type Sealed / open lead acid, nickel cadmium
Environmental conditions
Storage temperature -20°C to +45°C dry
Operating temperature up to 40°C (1)
Noise 68 dBA 69 dBA 72 dBA
Operating altitude (without derating) < 1000 m
Parallel operation
Integrated parallel up to 4
With Static Switch Cubicle up to 6
Standards
Performance and safety IEC/EN 62040-1, IEC/EN60950
Performance and design IEC/EN 62040-3
Design and manufacture ISO 14001, ISO 9001, IEC 60146
EMC immunity IEC61000-4
EMC emissions IEC 62040-2 C3
Approvals TÜV - LCIE - CEM - CE Mark
Dimensions and weight (height 1900 mm(2) ; depth : 840 mm)
UPS without batteries
Width (mm) 1600 3600
Weight (kg) 1650 1650 2030 2070 3500
Battery cubicle ( depth = 840 mm and height = 1900 mm)
10-minute autonomy , Width (mm) 2500 2950 3750 (3) (3)
Weight (kg) 3450 4450 5740 (3) (3)
30-minute autonomy , Width (mm) 4600 6700 8400 (3) (3)
Weight (kg) 6840 8690 11200 (3) (3)
Static bypass cubicle ( depth = 840 mm and height = 1900 mm)
Nominal power output (kVA) 800 1200 2000 3200 4800
Width (mm) 1000 1600 2500 Contact us for details
Weight (kg) 500 1000 1200 Contact us for details
0: 150% from 400 kVA. 1: For 8 hours. 35°C continuous. N.B. There is a risk of premature battery ageing above 25°C. 2: 2000 mm for 500 kVA.
3: Site type installation recommended, contact us for details. * Contact us for rating 500 kVA.