Professional Documents
Culture Documents
3
terminal
1MRK 504 013-BEN
Page 1
Issued May 2001
Changed since March 2001
Data subject to change without notice
(SE960158)
Features • Multiple function transformer protection ter- - Overexcitation restraint with 5th har-
minal in a compact design monic
• Numerical microprocessor design with - Internal CT ratio and vector group adap-
advanced facilities tation
• Suitable for power transformers, generator- - Settable zero sequence current elimina-
transformer blocks and reactors tion
• Variants: • Three-phase time overcurrent protection
with inverse and definite time characteris-
- Two-winding transformer application
tics. Three protection modules are avail-
- Three-winding transformer application able. Each of them can be configured to
- Both with multi-breaker arrangement any side of the transformer. Directionality
connections possibilities as option
Features (cont’d) • Single or three-phase definite time under- • Disturbance recording and data storage for
voltage protection for selectable trans- presentation on PC
former sides. Three protection modules are
• Front mounted menu driven display with
available
key pad and front port connector for PC
• Overexcitation protection based on V/Hz
• Remote data communication with 2 ports
measurement with IEEE inverse time or
for station control and station monitoring
transformer adapted characteristic
systems
• Thermal overload protection
• Available for 19 inch rack mounting in a
• Voltage regulation for single transformer or panel, surface or flush mounting
parallel transformers with on load tap
• Hardware options:
changer
- Up to four input/output modules for
• Programmable logic with inputs and out- binary inputs and output contacts, and
puts, And-, Or-gates, SR-gates, timers and mA analog inputs
trip logic for trip and/or indication of exter-
nal protection features (Buchholz, tempera- - One or two analog input modules
ture, etc.) - Separate Combitest test switch for reli-
• Display of service values able and safe testing
Application The numerical transformer terminal RET 521 The RET 521 includes setting adaptation to
is designed for fast and selective protection power transformer rating and instrument
and control of two- and three-winding trans- transformer ratios to allow protection settings
formers, auto-transformers, generator-trans- in percent (%), of the power transformer rat-
former blocks and shunt reactors. ing, thus facilitating the protection settings to
an optimum.
The RET 521 has low requirements on the
main Current Transformers and no interpos- The RET 521 can be supplied for 2-winding
ing CTs are necessary. applications or 3-winding applications as
indicated below in Fig. 1.
Flexibility is provided to cover for different
applications in form of transformer size, vec-
tor groups, system neutral earthing and exten- 2-winding applications
sion of protection functions according to the
user’s preference. The selection of function- 2-winding power trans-
ality from the modular hardware and software former
is made according to the requirements for
selectivity and reliability in accordance to the 2-winding power trans-
user’s preference. Big and important trans- former with unconnected
formers such as generator-transformer blocks delta tertiary winding
or large network transformers can use two
RET 521 and include the modular protection 2-winding power trans-
software selectively to obtain redundancy. former with 2 circuit
breakers on one side
Smaller transformers and shunt reactors can
include the modular software in one RET 521
and can also use the programmable logic to 2-winding power trans-
provide trip or indication for external protec- former with 2 circuit
tions (e.g. Buchholz). Thus providing a very breakers and 2 CT-sets
on both sides
compact design for protection and control.
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 3
Comm.
Application (cont’d) Restricted earth fault protection, REF Single-/Three-phase time undervoltage
Three units of restricted earth fault protec- protection, TUV
tions can be included in RET 521. REF is an Three units of single-/three-phase time under-
instantaneous earth current differential pro- voltage protections can be included. The und-
tection for solidly or low impedance earthed ervoltage protection can be applied on any
systems. It can be applied for each low transformer side, if VT inputs are provided. It
impedance earthed transformer winding. The has got parallel outputs for both single-phase
protection is a stabilised low impedance type measurement and three-phase measurement.
and is unaffected by inrush currents or exter- The undervoltage protection is recommended
nal faults. The protection is also stabilised as backup for sustained system undervolt-
against CT saturation. A directional feature is ages. The undervoltage protection is provided
included in the protection. with two settable voltage levels, and both lev-
els are provided with independent time delay.
Service values for differential current and
bias current are available. Service value for lowest voltage is available.
Earth fault time current protection, TEF Neutral time voltage protection, TOV
Three units of earth fault time current protec- The above described single-/three-phase
tions can be included. They can be applied for overvoltage protection is designed to be suit-
each transformer winding. The earth fault able also as neutral overvoltage protection.
protection is recommended as a backup pro- The overvoltage protection measures the fun-
tection for transformer faults or network damental frequency component and is there-
faults. The earth fault protection is provided fore insensitive for 3rd and higher harmonics.
with two settable current levels. The lower When used as a neutral overvoltage protec-
level can be selected with independent or tion it is typically connected to a VT in the
inverse time characteristic, and the higher neutral of the transformer or to an open delta
level can be selected with independent char- connection of the secondary of a three-phase
acteristic only. Both levels can also be pro- set of VTs. As a neutral overvoltage protec-
vided with a 2nd harmonic restraint for inrush tion it is normally used in high impedance
currents. The earth fault protection can be earthed systems, and is given a longer time
connected to a neutral CT or to summated delay than the feeder earth fault protections.
phase currents. The earth fault protection can
be added with a directional feature using 3Uo Thermal overload protection, THOL
polarising by selection at ordering. At too low The three-phase thermal overload protection
polarising voltage the directional earth fault can be included in RET 521 and protects the
function will be blocked. transformer windings against thermal
stresses. The thermal protection can be
Service values for residual current and resid- applied to one selected transformer winding.
ual voltage are available. The thermal protection is provided with two
different thermal constants. The thermal pro-
Single-/Three-phase time overvoltage pro- tection is provided with two independently
tection, TOV set levels for alarm and tripping.
Six units of single-/three-phase time overvolt-
age protections can be included. The over- Service value for measured current, thermal
voltage protection can be applied on any status, time-to-trip and time-to-reset of lock-
transformer side, if VT inputs are provided. It out are available.
has got parallel outputs for both single-phase
measurement and three-phase measurement. Overexcitation protection (V/Hz), OVEX
The overvoltage protection is recommended The overexcitation protection can be included
as backup for sustained system overvoltages. in RET 521 and can be configured to any side
The overvoltage protection is provided with of the power transformer. However the side
two settable voltage levels, and both levels with the voltage regulation taps shall be
are provided with independent time delay. avoided. The overexcitation protection can be
The low stage can alternatively have an configured to either three-phase to earth volt-
inverse time delay. ages or to one phase-to-phase voltage. The
overexcitation protection is based on voltage/
Service value for highest voltage is available. frequency (V/Hz) measurement. The IEEE
trip time inverse characteristic can be set to
follow the transformer characteristic and a
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 5
cooling time memory is included. The trip the terminals controlling a group of parallel
time characteristic is also provided with defi- transformers. Another feature is that a hot
nite minimum and maximum times. stand-by transformer also can be automati-
cally controlled and be prepared to momen-
As an alternative a transformer adapted time tarily be switched into a parallel group.
delay characteristic can be used for close
adaptation to the transformer capability char- The voltage control function for parallel
acteristic. transformers also includes the single trans-
former control module with the same func-
Separate trip and alarm outputs are included. tionality as described in previous point.
Service values for relative excitation status Service values as above but also for circulat-
voltage/frequency, thermal status and time- ing current and mean values of bus voltages
to-trip are available. and settings in a parallel group are available.
Application (cont’d) • Alternative 2 is primarily used for two onds. There is a possibility to enter one to
winding power transformers with both four complete groups of settings. It is then an
sides low ohmic earthed easy operation to switch between these
• Alternative 3 is primarily used for two groups locally or by external control.
winding power transformers with multi-
Settings can be changed from the front
breaker system on one side.
Human-Machine-Interface (HMI), or by a
• Alternative 4 is primarily used for three portable personal computer (PC), with a
winding power transformers with possi- parameter setting program (PST) included in
bility for multi-breaker system on one side. CAP 535, connected to a fibre-optic connec-
• Alternative 5 is primarily used for three tor socket at the front, or from another loca-
winding power transformers with multi- tion over a data communication system.
breaker systems on two sides as in the
Indications, events and service values
example shown in fig 4 on pages 20 and
21. Operation indications and time-tagged events
are available by the front HMI and a con-
• Alternative 6 is primarily used for three nected PC, or from another location over a
winding power transformers with a protec- data communication system. Actual input
tion system not using more than 9 currents quantity values, load, differential current and
and 1 voltage (only one analog input mod- other service values can also be read from the
ule used). terminal.
Design The physical design of terminal RET 521 is Behind the front there is an interconnection
in line with the products in the RE. 500- board, a motherboard, to which printed board
series. It is housed in painted sheet steel assemblies (PBAs) are plugged in from the
enclosure suitable for different mounting by rear side. The input module for analog AC
use of particular mounting accessories. Wire quantities is fixed mounted and the connec-
connections are made at the rear side at termi- tion terminal for these circuits are also fixed
nals of compression type tightened by a mounted. The connection terminals for the
screw. Fibre optic wires for data communica- DC contact circuits are of the multipole
tion are also connected at the rear side. On the detachable type so as to facilitate disconnec-
front is a HMI-panel and socket with an optic tion for exchange of PBAs.
interface to a specific cable for a portable PC.
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 7
The following modules can be included in the contacts. 10 BOs are each made by one
RET521 terminal: printed circuit board type of relay (PCB
mounted relay) which has one normally
• Analog input module with galvanic sepa- open contact. 2 BOs have also got one reed
ration and adaptation of the AC signals. To relay in parallel with the standard relay to
suit different applications there are three be used for fast signalling with one nor-
variants with different number of current mally open contact.
and voltage signals. The analog input mod-
• Another possibility of binary in/out inter-
ule also contains an analog to digital con-
face is to use a separate binary input mod-
verter (A/D-converter) which provides the ule, BIM, with 16 binary inputs and a
necessary conversion and some filtering.
separate binary output module, BOM, with
• Processor modules with data processing 24 output relay contacts. The BIs an BOs
for the protection as well as other func- are essentially of similar design as for the
tions and communication. As an option combined module, IOM.
two communication interfaces can be • Additional binary in/out modules of the
added for connection to a station monitor-
three above types are available if needed.
ing system (SMS) including a remotely
located PC and a station control system • A mA-analog input board with 6 channels
(SCS). 0-20 mA (4-20 mA) is also available.
• Power supply module with DC/DC con- • Front HMI panel. There are three light-
verter for the electronic circuits. emitting diodes (LEDs), one LCD display
with 4 lines times 16 characters and there
• One choice of binary in/out interface is a is a six button key pad and a fibre-optic
combined binary input/output module,
connector socket, for connection to the
IOM, with 8 binary inputs and 12 output
serial port of a portable PC by means of a
relay contacts. The BIs have isolation by special interface cable.
optocouplers and are intended for external
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 8
Technical data
Table 1: Energising quantities, rated values and limits
Quantity Rated value Nominal range Operative range
Current Ir = 1 A or 5 A (0,2-30) x Ir (0,03 - 100 x Ir)
Burden < 0,25 VA at Ir (0,2-4) x Ir continu- 100 x Ir for 1 s*
ously
AC voltage Ph-Ph** Ur = 100/110/115/120 V 80-120% of Ur 1,5 x Ur continuously
Burden < 0,2 VA at Ur 2,5 x Ur for 10 s
Frequency fr = 50/60 Hz ±2,5 Hz ±5 Hz
Frequency with increased
range fr = 50/60 Hz (0,7-1,2) x fr Hz (0,65-1,25) x fr Hz
Auxiliary DC voltage EL EL = 110/125 V ±20% ±20%
EL = 220/250 V ±20% ±20%
Power consumption
Basic terminal (2 AIM, < 35 W
1 BOM, 1 BIM, 1 IOM and
1 MIM) and no activated
relay outputs
Auxiliary DC power in-rush 110 VDC, <15 A, 0,1 ms
220 VDC, <30 A, 0,1 ms
Binary input (8) /output (12)
module
DC voltage RL RL = 24/30 V ±20% ±20%
RL = 48/60 V ±20% ±20%
URL = 110/125 V ±20% ±20%
RL = 220/250 V ±20% ±20%
power consumption
each I/O board ≤1W
each output relay ≤ 0,15 W
RL = 24/30 V max. 0,05 W/input
RL = 48/60 V max. 0,1 W/input
RL = 110/125 V max. 0,2 W/input
RL = 220/250 V max. 0,4 W/input
Binary input(16) module
DC voltage RL = 24/30 V ±20% ±20%
RL = 48/60 V ±20% ±20%
RL = 110/125 V ±20% ±20%
RL = 220/250 V ±20% ±20%
power consumption
each I/O board ≤0,5 W
RL = 24/30 V max. 0,05 W/input
RL = 48/60 V max. 0,1 W/input
RL = 110/125 V max. 0,2 W/input
RL = 220/250 V max. 0,4 W/input
Binary output (24/12)
module
power consumption
each output board ≤1W
each output relay ≤ 0,25 W
mA input module
input range ±20 mA
input resistance Rin = 194 ohm
power consumption
each mA module ≤4 W
each mA input channel ≤0,1W
Ambient temperature 20°C -5°C to +55°C
Ripple in dc auxiliary voltage max. 2% max. 12% Full wave rectified
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 9
Table 6: CE-mark
Test Type test values Reference standards
Immunity EN 50082-2
Emissivity EN 50081-2
Low voltage directive EN 50178
Table 29: Additional voltage control parameters for parallel power transformers
Parallel operation OperatonPAR Off/On
Parallel transformer reactance reduced to
secondary side (for each transformer T x) Tx Xr2 0,1-20,0 ohm
Parallel control compensation factor Comp 0-2000%
Operation circulation current block function OperationCC Off/On
Circulating current block limit (primary value) CircCurrLimit 0,0-20000,0 A
Circulating current delay time tCircCurrent 1- 300 s
Operation common setpoint for parallell op OperUsetPar Off/On
Operation simultaneous tapping prohibited OperSimtap Off/On
Operation homing function OperHoming Off/On
VTmismatch VTmismatch 0,5-10,0 %
VTmismatch time tVTmismatch 1,0-10,0 s
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 19
Terminal
diagrams
P8 P3
X81:TX P8 SLM
#
1a) X82:RX SERIIAL CH INTERFACE
FIBRE X31:
X83:TX 1A 1
OPTIC
2) X84:RX LON CH INTERFACE 5A 2
AI 1(I)
TX 3
1A 4
1b) HMI HMI 5A 5
AI 2(I)
RX 6 • • •
• • •
1A 7
P14 AI 3(I) 5A 8
9
1A 10
X141:1 INTERNAL FAIL 5A 11
NO AI 4(I)
X141:3 12
3) NC
X141:2 1A 13
•
5A 14
•
AI 5(I)
+ - 15
X141:4
+ 1A 16
4) X141:5 5A 17
- AI 6(I)
18
P12 1A 19
AI 7(I) 5A 20
X121:7
+ 21
5) MI.11 22
X121:8
-
X121:9 AI 8(U)
24
MI.12 25
X121:10
AI 9(U) • • •
X121:11
27 • • •
MI.13 28
X121:12
X121:13 AI 10(U)
30
MI.14
X121:14
X121:15
MI.15
X121:16
X121:17
MI.16
X121:18
RET 521
P9
X91:1 PROTECTION, CONTROL &
+ MONITORING FUNCTIONS
6) X91:2 BI.01
-
X91:3
+
7) X91:4 BI.02
-
X91:5
+ TOC (HV) 3I>
8) X91:6 BI.03
- 1a) SERIAL CHANNEL BUS (SPA), BACK
X91:7 REF (HV) Id
+
9) X91:8 BI.04 1b) SERIAL CHANNEL BUS (SPA), FRONT WITH
-
X91:9 TEF (HV) I SPECIAL INTERFACE CABLE
+
10) X91:10 BI.05
- 2) LON BUS
X91:11 DIFP 3Id/I
+
11) X91:12 BI.06 3) INTERNAL FAIL / LOSS OF AUXILARY VOLT-
-
X91:13 AGE
+ TOC (LV) 3I>→
12) X91:14 BI.07
- 4) AUXILIARY DC VOLTAGE, EL
X91:15 TOV (residual) U
+
13) X91:16 BI.08 5) OLTC POSITION TRANSDUCER SIGNAL
-
TOV (LV) 3U>
BO.01 6) RESET
X92:2
14) BO.02 TUV (LV) 3U<
X92:3 7) WINDING TEMP TRIP
X92:4 BO.03 THOL I 8) OIL TEMP TRIP
X92:5 BO.04
BO.05 OVEX U>/f 9) BUCHHOLZ ALARM
X92:6
X92:9 BO.06 10) PRESSURE ALARM
15) VCTR U><
X92:8 11) WINDING TEMP ALARM
X92:11 BO.07
16)
DRP 12) TRANSFORMER DISCONNECTED
X92:12 BO.08 (disturb report)
17) BO.09 13) TAP CHANGER IN PROGRESS
X92:13
X92:14 BO.10
14) TRIP HV CIRCUIT BREAKER
X92:16 *) BO.11
15) TRIP LV CIRCUIT BREAKER
18) *) BO.12
X92:18
19) 16) TAP CHANGER RAISE
17) TAP CHANGER LOWER
X92:17
X92:15
X92:10
X92:7
X92:1
1b) AI 3(I) 5A 8
HMI HMI
RX 9
1A 10
AI 4(I) 5A 11
P14 12
1A 13
AI 5(I) 5A 14
X141:1 INTERNAL FAIL 15
NO
X141:3 1A 16
3) NC
X141:2 AI 6(I) 5A 17
- 18
+
X141:4 1A 19
+ 5A 20
4) X141:5 AI 7(I)
- 21
1A 22
P12 AI 8(I) 5A 23
X121:7 24
+ 25
MI.11
•
5)
•
X121:8 AI 9(U)
-
X121:9 27
28
MI.12
• • •
X121:10
• • •
AI 10(U)
•
•
X121:11 30
MI.13
X121:12 P7 X71:
X121:13 1A 1
MI.14 AI 1(I) 5A 2
X121:14 # 3
X121:15 1A 4
MI.15 AI 2(I) 5A 5
X121:16
Transformer protection terminal
6
X121:17 1A 7
MI.16 AI 3(I) 5A 8
X121:18 9
1A 10
AI 4(I) 5A 11
12
1A 13
AI 5(I) 5A 14
15
1A 16
RET 521 AI 6(I) 5A 17
18
1A 19
5A 20 • • • • • •
AI 7(I) • • • • • •
21
1A 22
AI 8(I) 5A
24
1A 25
AI 9(I) 5A
27
28
AI 10(U)
30
Page 20
1MRK 504 013-BEN
RET 521*2.3
P9
X91:1 1a) SERIAL CHANNEL BUS (SPA), BACK
+
6) X91:2 BI.01 1b) SERIAL CHANNEL BUS (SPA), FRONT
-
X91:3 PROTECTION, CONTROL & WITH SPECIAL INTERFACE CABLE
+
7) X91:4 BI.02 MONITORING FUNCTIONS
-
+ X91:5 2) LON BUS
8) X91:6 BI.03
- 3) INTERNAL FAIL / LOSS OF AUXILIARY VOLT-
X91:7
+ RET 521 AGE
9) X91:8 BI.04
- TOC (HV) 3I> 4) AUXILIARY DC VOLTAGE, EL
+ X91:9
10) X91:10 BI.05
- REF (HV) Id 5) OLTC POSITION TRANSDUCER SIGNAL
X91:11
+ (ONLY IF BINARY INPUT NOT USED)
11) X91:12 BI.06 TEF (HV) I
-
+ X91:13 6) RESET
12) X91:14 BI.07
-
X91:15 DIFP 3Id/I 7) WINDING TEMP TRIP
+
13) X91:16 BI.08
Fig. 4
- 8) OIL TEMP TRIP
X92:1 TOC (MV) 3I>
+
14) X92:2 BI.09 9) EXTERNAL DISTURBANCE RECORDER START
-
X92:3 REF (MV) Id
+ X92:4
15) BI.10 10) OIL TEMP ALARM
- X92:5 TEF (MV) I
+ 11) BUCHHOLZ ALARM
16) X92:6 BI.11
- TOV (MV) U>
X92:7 12) PRESSURE ALARM
+ X92:8
17) BI.12
- TUV (MV) U<
X92:9 13) TRANSFORMER DISCONNECTED
+
18) X92:10 BI.13
- 14) TAP CHANGER IN PROGRESS
X92:11
+ X92:12 TOC (LV) 3I>
19) BI.14 15) TAP CHANGER POSITION BIT 1
- X92:13
+ TOV (LV) U
20) X92:14 BI.15 16) TAP CHANGER POSITION BIT 2
-
X92:15
+ 17) TAP CHANGER POSITION BIT 3
21) X92:16 BI.16 THOL I
-
18) TAP CHANGER POSITION BIT 4
P10 OVEX U>/f
19) TAP CHANGER POSITION BIT 5
X101:1 BO.01
22) BO.02 20) TAP CHANGER POSITION BIT 6
22) X101:3 VCTR U><
X101:4 BO.03
22) BO.04 21) TAP CHANGER PARITY BIT
22) X101:6
X101:7 BO.05 DRP 22) TRIP HV CIRCUIT BREAKERS
23) BO.06 (disturb report)
Transformer protection terminal
23) X101:9
X101:10 BO.07 23) TRIP MV CIRCUIT BREAKERS
23) BO.08
23) X101:12 24) TRIP LV CIRCUIT BREAKER
X101:13 BO.09
24) BO.10
24) X101:15 25) RET TRIP LOCKOUT
X101:16 BO.11
25) BO.12 26) OVERLOAD ALARM 1
26) X101:18
X102:1 BO.13
27) BO.14 27) OVERLOAD ALARM 2
28) X102:3
X102:4 BO.15
29) 28) OVEREXCITATION ALARM
X102:6 BO.16
30) BO.17
X102:7 29) EXTERNAL DISTURBANCE RECORDER
31) BO.18
32) X102:9 START
X102:10 BO.19
33) BO.20 30) OIL TEMP ALARM
34) X102:12
X102:13 BO.21
35) BO.22 31) BUCHHOLZ ALARM
36) X102:15
X102:16 BO.23 32) PRESSURE ALARM
37) BO.24
38) X102:18
33) TRANSFORMER DISCONNECTED
X102:17
X102:14
X102:11
X102:8
X102:5
X102:2
X101:17
X101:14
X101:11
X101:8
X101:5
X101:2
36) TAP CHANGER HUNTING
37) TAP CHANGER RAISE
38) TAP CHANGER LOWER
RET 521*2.3
Page 21
1MRK 504 013-BEN
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 22
Ordering RET 521 are intended for two-winding transformer or three-winding transformer applications.
The analog transformer input modules type AIM can be configured to the application with
maximum 10 input transformers for each analog input module, maximum 2 analog input mod-
ules can be included. The basic versions occupy 3/4 of a 6U 19 inch rack. Totally 4 rack posi-
tions are intended for I/O boards in the 3/4 rack. One optional test switch type RTXP 24 can be
fitted in the same 19 inch rack together with the protection terminal. If two test switches are
needed the second one has to be placed in an other rack.
The base terminal contains hardware always needed and some basic software functions. The
hardware in the terminal will be customised by additional choices according to the alternatives
below.
Protection and control functions can be added to the terminal while observing the need and lim-
itations for the number of input transformers and also the need and limitations for the number
of I/O boards.
Custom logic programming (40 AND, 40 OR, 20 inverters, 25 timers, 20 pulse timers, 10 SR-
gates and 3 MOVE blocks)
Binary converter
Basic data:
Nominal frequency: 50/60 Hz
Rated VT input voltage 100/√3, 110/√3, 115/√3, 120/√3, 100, 110, 115, 120 V
(across each individual
input)
Rated CT input current 1/5 A
Auxiliary dc voltage EL 110-250 V
*) Needs only to be filled in when no transformer differential protection is ordered in next table
If transformer differential protection is ordered in next table the type of transformer terminal
will automatically be chosen from that information.
Ordering (cont’d)
Earth fault time current protection Available options
Max three options totally and only one per Non-Directional Directional
TEFx can be chosen
First earth fault time current protection, 1MRK 001 538-LA 1MRK 001 538-PA
TEF1
Second earth fault time current protection, 1MRK 001 538-MA 1MRK 001 538-RA
TEF2
Third earth fault time current protection, 1MRK 001 538-NA 1MRK 001 538-SA
TEF3
If the hardware required is different from the alternatives in the table below no example config-
uration is downloaded but the user can easily change one of the example configurations in CAP
or built his own configuration to fit his application. The hardware configuration is always
downloaded in the delivered terminal.
If the user require to have a specific configuration made and downloaded in the delivered ter-
minal by ABB this can be ordered as well.
Example 1 P3 P9 2 windings
Select with “X” mark in tables below the required type of module per slot location
(cont’d)
Binary Input/Output & Available options for Input/Output Module
mA module BIM BOM IOM MIM
1MRK000508-xx 1MRK000614-AB 1MRK000173-xx 1MRK000284-AA
Input/Output Module 1
(Located in Slot P9)
Input/Output Module 2
(Located in Slot P10)
Input/Output Module 3
(Located in Slot P11)
Input/Output Module 4
(Located in Slot P12)
BIM = 16 Optocoupler Inputs. Please specify rated voltage of optocoupler inputs below
BOM = 24 Contact Outputs
IOM = 12 Contact Outputs and 8 Optocoupler Inputs. Please specify rated voltage of optoc. inputs below
MIM = 6 analog (i.e. mA) inputs, always located in Slot P12
Please specify with “X” mark rated voltage for optocoupler inputs only for slots in which you
have chosen BIM or IOM type of module
Available rated Voltages for Optocoupler Inputs on BIM & IOM Modules
24/30 V dc 48/60 V dc 110/125 V dc 220/250 V dc
for BIM xx =DB for BIM xx =AB for BIM xx =BB for BIM xx = CB
for IOM xx =GB for IOM xx =AC for IOM xx =BC for IOM xx = CC
Input/Output Module 1
(Located in Slot P9)
Input/Output Module 2
(Located in Slot P10)
Input/Output Module 3
(Located in Slot P11)
Input/Output Module 4
(Located in Slot P12)
Mechanical options:
Test switch
COMBITEST test switch module RTXP 1MRK 000 371-EA
Current circuits connected for rated current 1A 5A
NOTE!
The test switches have internal star point connection of three-phase CT groups
Each analogue input module AIM is connected to its own test switch module so two test switches are
needed if two analogue input modules are used.
The first test switch module RTXP 24 will be mounted with the transformer protection terminal in
RHGS 6 case with window door forming a full 19 inch case.
The second test switch module RTXP 24 (if needed) will be mounted in a separate RHGS 6 case with
window door.
Test switch module RTXP24 for AIM2 mounted in RHGS6 Case 1MRK 000 371-EB
Rated current (1 or 5 A) to be specified for the connection between test switch and terminal.
The terminal is reconnectable and can at any time be altered between 1 or 5 A, but the terminal will be
delivered with all current channels connected to either 1 A or to 5 A.
Mounting details
Mounting details with IP40 degree of protection from the front for protection terminal case and if needed the
extra test switch case for a second test switch module:
Protection Second test
terminal switch case
Manuals
One copy of the Application manual, the Installation and Commissioning manual, the Operator´s manual and
the Technical reference manual are always included for each terminal.
Rule: Specify the number of extra manual requested.
Installation and commissioning manual Quantity: 1MRK 504 017-UEN
Operator´s manual Quantity: 1MRK 504 015-UEN
Technical reference manual Quantity: 1MRK 504 016-UEN
Application manual Quantity: 1MRK 504 021-UEN
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 28
Related
documents
Technical Overview brochure
CAP 535*1.1 1MRK 511 086-BEN
For our reference and statistics we would be pleased if we are provided with the following application data:
Sample Numerical transformer terminal type RET tections, three-phase under- and over-voltage
Specification 521 with continuous selfmonitoring and ana- protections and neutral voltage protections
logue/digital conversion of all input quanti- shall be available for selectable windings. A
ties. The terminal shall be suitable for thermal overload protection and an overexci-
protection, control and monitoring of two- or tation protection shall be included.
three-winding transformers, auto-transform-
ers, reactors, and generator-transformer block Voltage regulation for single transformer or
units and also for applications with multi- parallel transformers with On-Load-Tap-
breaker arrangements. The numerical trans- Changer shall be included in the numerical
former terminal shall be designed to operate transformer terminal.
correctly over a wide frequency range to
accommodate for system frequency varia- The terminal shall be provided with a pro-
tions and block generator start-up. grammable logic for trip and indications and
configuration of the included protection, con-
The differential protection function shall be trol and monitoring functions, and the basic
provided with 2nd harmonic restraint to avoid structure shall be modular for binary inputs
tripping at magnetizing inrush and 5th har- and binary outputs to facilitate user adapta-
monic restraint to avoid tripping at overexci- tion. A mA transducer input module shall be
tation. Recovery inrush and CT saturation possible to add.
shall not influence the differential function.
The differential protection shall have a setta- The terminal shall be provided with a front
ble restraint characteristic and be provided mounted menu driven human-machine-inter-
with an adaptive differential feature for multi- face and a front port optical connector for a
breaker arrangements. The differential pro- personal computer. Service value display of
tection shall be stable in case of high through- voltage, currents, frequency, event recording
faults also in multi-breaker arrangements. with 150 events and 10 recordings, and dis-
Tap-changer position indication must be used turbance recording with 10 analogue signals
to provide maximum sensitivity for the differ- and 48 digital signals for 40 s, and local data
ential protection. A high-set unrestrained dif- storage shall be included. Communication
ferential current protection shall be included. with the terminal shall be provided with two
ports for LON and SPA in the rear for station
Three-phase time overcurrent protections, control and station monitoring purpose.
restricted earth-fault protections, second har-
monic restrained time earth-fault current pro-