You are on page 1of 29

Transformer protection RET 521*2.

3
terminal
1MRK 504 013-BEN
Page 1
Issued May 2001
Changed since March 2001
Data subject to change without notice

(SE960158)

Features • Multiple function transformer protection ter- - Overexcitation restraint with 5th har-
minal in a compact design monic
• Numerical microprocessor design with - Internal CT ratio and vector group adap-
advanced facilities tation
• Suitable for power transformers, generator- - Settable zero sequence current elimina-
transformer blocks and reactors tion
• Variants: • Three-phase time overcurrent protection
with inverse and definite time characteris-
- Two-winding transformer application
tics. Three protection modules are avail-
- Three-winding transformer application able. Each of them can be configured to
- Both with multi-breaker arrangement any side of the transformer. Directionality
connections possibilities as option

• No interposing Current Transformers • Restricted earth fault protection for each


required transformer winding, based on the low
impedance principle and also provided with
• Application flexibility through generous set- a directional feature
ting and configuration facilities
• Earth fault time current protection with
• Extended frequency range by frequency inverse and definite time characteristics.
tracking and filter adaptation Three protection modules are available.
• Function modular and type tested software Each of them can be configured to any side
of the transformer. 2nd harmonic restrain-
• Transformer differential protection ing can be chosen if required. Directionality
- for two- and three-winding transformers as option
with 2, 3 or more CT groups
• Single or three-phase definite time or
- Through-fault stability by settable cur- inverse time overvoltage protection for
rent bias characteristics selectable transformer sides. This overvolt-
age protection is also suitable to apply as
- Enhanced through-fault stability for
neutral voltage protection. Six protection
multi-breaker arrangements
modules are available
- Inrush restraint with two selectable com-
binations of waveform and 2nd har-
monic methods. Settable crossblocking
between phases
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 2

Features (cont’d) • Single or three-phase definite time under- • Disturbance recording and data storage for
voltage protection for selectable trans- presentation on PC
former sides. Three protection modules are
• Front mounted menu driven display with
available
key pad and front port connector for PC
• Overexcitation protection based on V/Hz
• Remote data communication with 2 ports
measurement with IEEE inverse time or
for station control and station monitoring
transformer adapted characteristic
systems
• Thermal overload protection
• Available for 19 inch rack mounting in a
• Voltage regulation for single transformer or panel, surface or flush mounting
parallel transformers with on load tap
• Hardware options:
changer
- Up to four input/output modules for
• Programmable logic with inputs and out- binary inputs and output contacts, and
puts, And-, Or-gates, SR-gates, timers and mA analog inputs
trip logic for trip and/or indication of exter-
nal protection features (Buchholz, tempera- - One or two analog input modules
ture, etc.) - Separate Combitest test switch for reli-
• Display of service values able and safe testing

• Display of event records - On/Off switch for dc supply

• Continuous selfmonitoring and diagnostics - Mounting details for IP 40 and IP 54

Application The numerical transformer terminal RET 521 The RET 521 includes setting adaptation to
is designed for fast and selective protection power transformer rating and instrument
and control of two- and three-winding trans- transformer ratios to allow protection settings
formers, auto-transformers, generator-trans- in percent (%), of the power transformer rat-
former blocks and shunt reactors. ing, thus facilitating the protection settings to
an optimum.
The RET 521 has low requirements on the
main Current Transformers and no interpos- The RET 521 can be supplied for 2-winding
ing CTs are necessary. applications or 3-winding applications as
indicated below in Fig. 1.
Flexibility is provided to cover for different
applications in form of transformer size, vec-
tor groups, system neutral earthing and exten- 2-winding applications
sion of protection functions according to the
user’s preference. The selection of function- 2-winding power trans-
ality from the modular hardware and software former
is made according to the requirements for
selectivity and reliability in accordance to the 2-winding power trans-
user’s preference. Big and important trans- former with unconnected
formers such as generator-transformer blocks delta tertiary winding
or large network transformers can use two
RET 521 and include the modular protection 2-winding power trans-
software selectively to obtain redundancy. former with 2 circuit
breakers on one side
Smaller transformers and shunt reactors can
include the modular software in one RET 521
and can also use the programmable logic to 2-winding power trans-
provide trip or indication for external protec- former with 2 circuit
tions (e.g. Buchholz). Thus providing a very breakers and 2 CT-sets
on both sides
compact design for protection and control.
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 3

521 suitable for multibreaker arrangements.


3-winding applications The setting facilities cover for application of
the differential protection to power trans-
formers with or without tap changer, a shunt
reactor or a local feeder within the station,
3-winding power trans- and for multi-breaker arrangements. An adap-
former with all three tive differential feature is included for
windings connected through-faults. By introducing the tap
changer position to RET 521, the differential
protection pick-up can be set to optimum sen-
sitivity covering low level internal fault cur-
rents.
3-winding power trans-
former with 2 circuit
breakers and 2 CT-sets
Stabilisation is included to avoid differential
on one side protection tripping for inrush currents and for
overexcitation. Stabilisation is also included
for system recovery inrush and CT saturation
for external faults. Crossblocking between
3-winding power trans- phases is normally used, but the option can be
former with 2 circuit turned off.
breakers and 2 CT-sets
on 2 out of 3 sides A fast high set unrestrained differential cur-
rent protection is also included for high speed
Fig. 1 CT group arrangement for differential tripping at high internal fault currents.
protection and other protections
Service values for differential currents, bias
current and tap position are available.

Three-phase time overcurrent protection,


3I> TOC TOC
3Id/I DIFP Three units of three-phase overcurrent protec-
Id REF tions can be included. Each of them can be
configured to any side of the transformer. The
overcurrent protection is recommended as a
U TOV backup protection for transformer faults or
network faults. The overcurrent protection is
3I> TOC
Overtemp. provided with two settable current levels. The
etc.
Logic
lower level can be selected with independent
or inverse time characteristic, and the higher
I/O
level can be selected with independent char-
(96000026)

Comm.

Trip acteristic only. Both levels have separate


blocking inputs. The higher level of the over-
current protection can be used as a blocking
type of busbar protection for the low voltage
Fig. 2 An application example side with a short time delay. Low voltage side
distribution feeder protection start functions
are then connected to this blocking input.
Transformer differential protection, DIFP The three-phase overcurrent protection can be
The differential protection function is one of added with directional features individually
the most important function for fast and for each stage using healthy phase polarising
selective protection of transformers. The RET by selection at ordering. At too low polarising
521 is provided with internal settable adapta- voltage the overcurrent function can be
tion for CT ratio matching and vector groups, blocked or made non directional indepen-
which allows connection directly to Y-con- dently on both levels.
nected main CTs. Zero sequence current
elimination is made internally, but the option Service value for highest current is available.
can be turned off. All current inputs are pro-
vided with restraint features, making the RET
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 4

Application (cont’d) Restricted earth fault protection, REF Single-/Three-phase time undervoltage
Three units of restricted earth fault protec- protection, TUV
tions can be included in RET 521. REF is an Three units of single-/three-phase time under-
instantaneous earth current differential pro- voltage protections can be included. The und-
tection for solidly or low impedance earthed ervoltage protection can be applied on any
systems. It can be applied for each low transformer side, if VT inputs are provided. It
impedance earthed transformer winding. The has got parallel outputs for both single-phase
protection is a stabilised low impedance type measurement and three-phase measurement.
and is unaffected by inrush currents or exter- The undervoltage protection is recommended
nal faults. The protection is also stabilised as backup for sustained system undervolt-
against CT saturation. A directional feature is ages. The undervoltage protection is provided
included in the protection. with two settable voltage levels, and both lev-
els are provided with independent time delay.
Service values for differential current and
bias current are available. Service value for lowest voltage is available.

Earth fault time current protection, TEF Neutral time voltage protection, TOV
Three units of earth fault time current protec- The above described single-/three-phase
tions can be included. They can be applied for overvoltage protection is designed to be suit-
each transformer winding. The earth fault able also as neutral overvoltage protection.
protection is recommended as a backup pro- The overvoltage protection measures the fun-
tection for transformer faults or network damental frequency component and is there-
faults. The earth fault protection is provided fore insensitive for 3rd and higher harmonics.
with two settable current levels. The lower When used as a neutral overvoltage protec-
level can be selected with independent or tion it is typically connected to a VT in the
inverse time characteristic, and the higher neutral of the transformer or to an open delta
level can be selected with independent char- connection of the secondary of a three-phase
acteristic only. Both levels can also be pro- set of VTs. As a neutral overvoltage protec-
vided with a 2nd harmonic restraint for inrush tion it is normally used in high impedance
currents. The earth fault protection can be earthed systems, and is given a longer time
connected to a neutral CT or to summated delay than the feeder earth fault protections.
phase currents. The earth fault protection can
be added with a directional feature using 3Uo Thermal overload protection, THOL
polarising by selection at ordering. At too low The three-phase thermal overload protection
polarising voltage the directional earth fault can be included in RET 521 and protects the
function will be blocked. transformer windings against thermal
stresses. The thermal protection can be
Service values for residual current and resid- applied to one selected transformer winding.
ual voltage are available. The thermal protection is provided with two
different thermal constants. The thermal pro-
Single-/Three-phase time overvoltage pro- tection is provided with two independently
tection, TOV set levels for alarm and tripping.
Six units of single-/three-phase time overvolt-
age protections can be included. The over- Service value for measured current, thermal
voltage protection can be applied on any status, time-to-trip and time-to-reset of lock-
transformer side, if VT inputs are provided. It out are available.
has got parallel outputs for both single-phase
measurement and three-phase measurement. Overexcitation protection (V/Hz), OVEX
The overvoltage protection is recommended The overexcitation protection can be included
as backup for sustained system overvoltages. in RET 521 and can be configured to any side
The overvoltage protection is provided with of the power transformer. However the side
two settable voltage levels, and both levels with the voltage regulation taps shall be
are provided with independent time delay. avoided. The overexcitation protection can be
The low stage can alternatively have an configured to either three-phase to earth volt-
inverse time delay. ages or to one phase-to-phase voltage. The
overexcitation protection is based on voltage/
Service value for highest voltage is available. frequency (V/Hz) measurement. The IEEE
trip time inverse characteristic can be set to
follow the transformer characteristic and a
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 5

cooling time memory is included. The trip the terminals controlling a group of parallel
time characteristic is also provided with defi- transformers. Another feature is that a hot
nite minimum and maximum times. stand-by transformer also can be automati-
cally controlled and be prepared to momen-
As an alternative a transformer adapted time tarily be switched into a parallel group.
delay characteristic can be used for close
adaptation to the transformer capability char- The voltage control function for parallel
acteristic. transformers also includes the single trans-
former control module with the same func-
Separate trip and alarm outputs are included. tionality as described in previous point.

Service values for relative excitation status Service values as above but also for circulat-
voltage/frequency, thermal status and time- ing current and mean values of bus voltages
to-trip are available. and settings in a parallel group are available.

Voltage control for single transformer, Input trip matrix


VCTR External contacts, e.g. from transformer over-
The voltage control function can be included temperature devices and Buchholz gas detec-
in RET 521 and is used to maintain a constant tor, can be connected via Binary Inputs.
user preset voltage at the low voltage side of Logic can be arranged for alarm, event log-
the transformer, i.e. at the busbar or at the ging and tripping. For redundancy reasons it
feeder ends. Constant voltage is obtained by is recommended to route tripping from the
controlling the tap changer position by raise Buchholz or overpressure device in parallel to
and lower commands. The delay for the regu- RET 521.
lating command can be of inverse or indepen-
dent type. Blocking is included for Tripping matrix
overcurrent and undervoltage, power system The tripping commands are configured to trip
emergencies and tap changer end positions. logic blocks, which then are configured to the
Line drop compensation is included. A load tripping output relays. Each trip logic block
shedding based on voltage reduction is also has 16 inputs to an or gate. Up to 12 trip logic
included. Number of tap changer operations blocks can be used.
can be recorded for determining the service
intervals. Remote or local command possibil- Additional logic
ities are included. Alarms from the tap Additional logic elements in the form of 40
changer auxiliary equipment (binary con- AND-gates, 40 OR-gates, 20 inverters, 25
tacts) can be connected to the voltage control timers, 20 pulse elements and 10 SR-gates are
function. The tap changer position can be available and can be combined by the user to
monitored by mA-input or by binary inputs to suit particular requirements.
the voltage control function.
Optional BI/BO modules can be added to get
Service values for busbar voltage, compen- more BI and BO interfaces, while observing
sated voltage, actual set voltage, load voltage that the maximum number of board places is
adjustment, tap changer position, contact life four.
calculation and no of operation counter are
available Configuration
Six example configurations for the connec-
Voltage control for parallel transformer, tion of the analog inputs, the binary inputs/
VCTR outputs, the logical circuits and the protection
The voltage control function for parallel modules, the control modules and the moni-
transformers can be included in RET 521 and toring modules are available and used as
is used to maintain a constant user preset shown in table 30 on page 25. These configu-
voltage at the low voltage side of up to four rations are often covering more functionality
parallel operating transformers, i.e. at the than needed but can easily be changed from a
busbar or at the feeder ends. The voltage reg- connected PC with the CAP 535 configura-
ulation is based on minimising the circulating tion and programming tool package.
current method. LON communication is used
between terminals to get information about • Alternative 1 is primarily used for two
adjacent transformer currents, voltages and winding power transformers with one side
settings. The regulation can be made to use high ohmic earthed as in the example
the mean value of the voltages and settings of shown in fig 3 on page 19.
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 6

Application (cont’d) • Alternative 2 is primarily used for two onds. There is a possibility to enter one to
winding power transformers with both four complete groups of settings. It is then an
sides low ohmic earthed easy operation to switch between these
• Alternative 3 is primarily used for two groups locally or by external control.
winding power transformers with multi-
Settings can be changed from the front
breaker system on one side.
Human-Machine-Interface (HMI), or by a
• Alternative 4 is primarily used for three portable personal computer (PC), with a
winding power transformers with possi- parameter setting program (PST) included in
bility for multi-breaker system on one side. CAP 535, connected to a fibre-optic connec-
• Alternative 5 is primarily used for three tor socket at the front, or from another loca-
winding power transformers with multi- tion over a data communication system.
breaker systems on two sides as in the
Indications, events and service values
example shown in fig 4 on pages 20 and
21. Operation indications and time-tagged events
are available by the front HMI and a con-
• Alternative 6 is primarily used for three nected PC, or from another location over a
winding power transformers with a protec- data communication system. Actual input
tion system not using more than 9 currents quantity values, load, differential current and
and 1 voltage (only one analog input mod- other service values can also be read from the
ule used). terminal.

Parameter settings Disturbance recording


RET 521 has wide setting facilities to ensure Sampled data from a disturbance, like a trip-
application flexibility. Factory default set- ping operation, can be stored and made avail-
tings are chosen to indicate typical setting able for oscillographic presentation and
values or choices. The settings are organised evaluation on a front connected PC or from
as general settings and settings for each sepa- another location over a data communication
rate function. system, to which the disturbance files are
transferred. This function stores continu-
The main data (ratings) of the protected trans- ously sampled data in a cyclic buffer. At
former and ratios of the instrument transform- selectable trigger conditions the data are
ers are entered in the terminal setting and stored, so that both prefault and fault data are
configuration menus. Most of the setting saved.
parameters of the particular functions can
then be made as per unit (p.u.) or percent (%) Data communication
values related to the power transformer rat- Two remote communication ports for SPA
ing. For some protections there also exist a and LON can be included. They enable co-
possibility to define the rated value in the set- operation with a station monitoring system
ting menu to another value than the power (SMS) including a remotely located PC, and a
transformer rating. Most timers are set in sec- station control system (SCS).

Design The physical design of terminal RET 521 is Behind the front there is an interconnection
in line with the products in the RE. 500- board, a motherboard, to which printed board
series. It is housed in painted sheet steel assemblies (PBAs) are plugged in from the
enclosure suitable for different mounting by rear side. The input module for analog AC
use of particular mounting accessories. Wire quantities is fixed mounted and the connec-
connections are made at the rear side at termi- tion terminal for these circuits are also fixed
nals of compression type tightened by a mounted. The connection terminals for the
screw. Fibre optic wires for data communica- DC contact circuits are of the multipole
tion are also connected at the rear side. On the detachable type so as to facilitate disconnec-
front is a HMI-panel and socket with an optic tion for exchange of PBAs.
interface to a specific cable for a portable PC.
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 7

The following modules can be included in the contacts. 10 BOs are each made by one
RET521 terminal: printed circuit board type of relay (PCB
mounted relay) which has one normally
• Analog input module with galvanic sepa- open contact. 2 BOs have also got one reed
ration and adaptation of the AC signals. To relay in parallel with the standard relay to
suit different applications there are three be used for fast signalling with one nor-
variants with different number of current mally open contact.
and voltage signals. The analog input mod-
• Another possibility of binary in/out inter-
ule also contains an analog to digital con-
face is to use a separate binary input mod-
verter (A/D-converter) which provides the ule, BIM, with 16 binary inputs and a
necessary conversion and some filtering.
separate binary output module, BOM, with
• Processor modules with data processing 24 output relay contacts. The BIs an BOs
for the protection as well as other func- are essentially of similar design as for the
tions and communication. As an option combined module, IOM.
two communication interfaces can be • Additional binary in/out modules of the
added for connection to a station monitor-
three above types are available if needed.
ing system (SMS) including a remotely
located PC and a station control system • A mA-analog input board with 6 channels
(SCS). 0-20 mA (4-20 mA) is also available.
• Power supply module with DC/DC con- • Front HMI panel. There are three light-
verter for the electronic circuits. emitting diodes (LEDs), one LCD display
with 4 lines times 16 characters and there
• One choice of binary in/out interface is a is a six button key pad and a fibre-optic
combined binary input/output module,
connector socket, for connection to the
IOM, with 8 binary inputs and 12 output
serial port of a portable PC by means of a
relay contacts. The BIs have isolation by special interface cable.
optocouplers and are intended for external
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 8

Technical data
Table 1: Energising quantities, rated values and limits
Quantity Rated value Nominal range Operative range
Current Ir = 1 A or 5 A (0,2-30) x Ir (0,03 - 100 x Ir)
Burden < 0,25 VA at Ir (0,2-4) x Ir continu- 100 x Ir for 1 s*
ously
AC voltage Ph-Ph** Ur = 100/110/115/120 V 80-120% of Ur 1,5 x Ur continuously
Burden < 0,2 VA at Ur 2,5 x Ur for 10 s
Frequency fr = 50/60 Hz ±2,5 Hz ±5 Hz
Frequency with increased
range fr = 50/60 Hz (0,7-1,2) x fr Hz (0,65-1,25) x fr Hz
Auxiliary DC voltage EL EL = 110/125 V ±20% ±20%
EL = 220/250 V ±20% ±20%
Power consumption
Basic terminal (2 AIM, < 35 W
1 BOM, 1 BIM, 1 IOM and
1 MIM) and no activated
relay outputs
Auxiliary DC power in-rush 110 VDC, <15 A, 0,1 ms
220 VDC, <30 A, 0,1 ms
Binary input (8) /output (12)
module
DC voltage RL RL = 24/30 V ±20% ±20%
RL = 48/60 V ±20% ±20%
URL = 110/125 V ±20% ±20%
RL = 220/250 V ±20% ±20%
power consumption
each I/O board ≤1W
each output relay ≤ 0,15 W
RL = 24/30 V max. 0,05 W/input
RL = 48/60 V max. 0,1 W/input
RL = 110/125 V max. 0,2 W/input
RL = 220/250 V max. 0,4 W/input
Binary input(16) module
DC voltage RL = 24/30 V ±20% ±20%
RL = 48/60 V ±20% ±20%
RL = 110/125 V ±20% ±20%
RL = 220/250 V ±20% ±20%
power consumption
each I/O board ≤0,5 W
RL = 24/30 V max. 0,05 W/input
RL = 48/60 V max. 0,1 W/input
RL = 110/125 V max. 0,2 W/input
RL = 220/250 V max. 0,4 W/input
Binary output (24/12)
module
power consumption
each output board ≤1W
each output relay ≤ 0,25 W
mA input module
input range ±20 mA
input resistance Rin = 194 ohm

power consumption
each mA module ≤4 W
each mA input channel ≤0,1W
Ambient temperature 20°C -5°C to +55°C
Ripple in dc auxiliary voltage max. 2% max. 12% Full wave rectified
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 9

Table 1: Energising quantities, rated values and limits


Quantity Rated value Nominal range Operative range
Relative humidity 10-90% 10-90% 0-95%
* Max 350 A for 1 s when COMBIFLEX test switch is used
** Ph-ph voltage may also be directly connected across the analog voltage inputs

Table 2: Influencing factors, Permissible influence


Dependence on Within nominal range Within operative range
Ambient temperature 0,01%/1°C Correct function
Frequency dependence (without fr ± 2,5 Hz for 50 Hz ± 3,0 %
extended frequency range) fr ± 2,5 Hz for 60 Hz
Frequency dependence (with (0,7-1,2) x fr ± 2,0 %
extended frequency range)
Harmonic frequency dependence 2:nd 3:rd and 5:th harmonic of ± 1,0 %
(10, 20 and 50% content) fr
Ripple in auxiliary DC voltage negligible Correct function
Interruption in auxiliary DC voltage
without resetting < 50 ms < 50 ms
no unwanted function 0-∞ 0-∞

Table 3: Electromagnetic compatibility (EMC), immunity tests


Test Type test values Reference standards
1 MHz burst disturbance 2,5 kV IEC 60255-22-1, Class III
Electrostatic discharge
Direct application 8 kV, air discharge IEC 60255-22-2, Class III
6 kV, contact discharge
Indirect application 6 kV, contact discharge IEC 61000-4-2, Class III
Fast transient disturbance 4 kV IEC 60255-22-4, Class IV
Surge immunity test 1-2 kV, 1,2/50 µs, high energy IEC 61000-4-5, Class III
Radiated electromagnetic field 10 V/m, 26-1000 MHz IEC 61000-4-3, level 3
disturbance
Radiated electromagnetic field 10 V/m, 900 MHz ENV 50204
disturbance GSM
Conducted electromagnetic field 10 V/m, 0,15-80 MHz IEC 61000-4-6, level 3
disturbance

Table 4: Electromagnetic compatibility (EMC), emission tests


Test Type test values Reference standards
Electromagnetic emission radiated 30-1000 MHz, class A EN 55011
Electromagnetic emission conducted 0,15 - 30 MHz, class A EN 55081-2
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 10

Technical data (cont’d)

Table 5: Insulation tests


Test Type test values Reference standards
Dielectric test 2,0 kV ac 1 min IEC 60255-5
Impulse voltage test 5 kV, 1,2/50 µs, 0,5 J IEC 60255-5
Insulation resistance > 100 Mohm at 500 V dc IEC 60255-5

Table 6: CE-mark
Test Type test values Reference standards
Immunity EN 50082-2
Emissivity EN 50081-2
Low voltage directive EN 50178

Table 7: Mechanical tests


Test Type test values Reference standards
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3

Table 8: Contact data (reference standard: IEC 60255)


Fast signal relays
Function or quantity Trip- and signal relays (parallel reed relay)
Max. system voltage 250 V ac, dc 250 V ac, dc
Test voltage across open contact,
1 min 1,0 kV rms 800 V, dc
Current carrying capacity
continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load
with L/R > 10 ms
0,2 s 30 A 0,4 A
1,0 s 10 A 0,4 A
Breaking capacity for ac, cosϕ > 0,4 250 V/8,0 A 250 V/8,0 A
Breaking capacity for dc 48 V/1 A 48 V/1 A
with L/R < 40 ms 110 V/0,4 A 110 V/0,4 A
220 V/0,2 A 220 V/0,2 A
250 V/0,15 A 250 V/0,15 A
Maximum capacitive load 10 nF
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 11

Table 9: Connection system


Maximum Maximum load Maximum load
Connector type Rated voltage square area continuous 1s
Voltage connectors 250 V AC 2,5 mm2 10 A 30 A
2 x 1 mm2
Current connectors 250 V AC 4 mm2 20 A 500 A
Fiber connectors Glass: Bayonet ST
Plastic: Snap in Simplex Latching

Table 10: Additional general data


Weight approximate 10 kg
Dimensions
Width 336 mm (3/4 of 19”)
Height 6U = 267 mm
Depth 245 mm
Water and dust protection level Front IP 40 ( IP 54 with sealing strip )
Sides IP 30
Back IP 20
Storage temperature -40°C to +70°C

Table 11: Front communication


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 baude
Slave number 1 to 899
Connectors special electric/optic cable

Table 12: Serial communication (SPA)


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 baude
Slave number 1 to 899
Connectors and optical fibres glass or plastic

Table 13: Serial communication (LON)


Function Value
Protocol LON
Communication speed 1,25 Mbit/s
Connectors and optical fibres glass or plastic
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 12

Technical data (cont’d)

Table 14: Event recording


Function Value
Time tagging resolution 1 ms
Event buffering capacity
Max. number of events/
disturbance report 150
Max. number of disturbance reports 10
Time tagging error with synchronisation
using LON and minute pulse ± 1 ms typical

Time tagging error without synchronisation ± 10ms/hour

Table 15: Service values for input quantities


Function Nominal range
Frequency (0,7 -1,2) x fr acc ± 2 mHz at three phase connection
acc ± 50 mHz at single phase connection
Current (0,1 - 4,0) x Ir
Voltage (0,1 - 1,5) x Ur
Angles 0,0 - 359,9 degrees

Table 16: Disturbance recorder


Function Setting range
Number of binary inputs 0-48
Number of analog inputs 0-10
Sampling rate 1 kHz or 1,2 kHz for 50 and 60 Hz respectively
Recording bandwidth (5-500) Hz or (6-600) Hz fixed
Over triggering (0,00-50,00) x rated value (Ur or Ir)
Under triggering (0,00-2,00) x rated value (Ur or Ir)
Pre-fault time (50-300) ms in steps of 10 ms
Post fault time (100-3000) ms in steps of 100 ms
Limit time (500-4000) ms in steps of 100 ms
Number of recorded disturbances Max. 10 disturbances
Function Value
Voltage channels
dynamic range (0,01-2,0) x Ur at 100 V sec.
resolution 0,1% of Ur
accuracy at rated frequency fr
U<Ur ≤1% of Ur
U>Ur ≤1% of U
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 13

Table 16: Disturbance recorder


Current channels
dynamic range
without DC offset (0,01-85) x Ir
with full DC offset (0,01-40) x Ir
resolution ≤0,5% of Ir
accuracy at rated frequency fr
I<Ir ≤1% of Ir
I>Ir ≤1% of I (current value)
Total recording time with 10 analog and
48 digital signals recorder maximum 40 s
Built-in calendar For 30 years including leap years

Table 17: Transformer (object) data


Quantity Parameter Value or Range
Rated power 2 winding Sr 0,1-9999,9 MVA
Rated power 3 winding primary wind Sr1 0,1-9999,9 MVA
Rated power 3 winding secondary wind Sr2 0,1-9999,9 MVA
Rated power 3 winding tertiary wind Sr3 0,1-9999,9 MVA
Rated current primary winding in A Ir1 1-99999 A
Rated current secondary winding in A Ir2 1-99999 A
Rated current tertiary winding in A Ir3 1-99999 A
Rated voltage primary winding in kV Ur1 1,0-999,9 kV
Rated voltage secondary winding in kV Ur2 1,0-999,9 kV
Rated voltage tertiary winding in kV Ur3 1,0-999,9 kV
Vector group compensation VectorGrp2WV 1-24
(For different groups, Yy0, Yd1, Dy11.. etc.)
Vector group compensation VectorGrp3WV 1-288
(For different groups, Yy0d1.. etc.)

Table 18: Transformer terminal configuration


Quantity Parameter Value or Range
Used input tap for CT on AIM card in A InputCTTap Input 1A / Input 5A
Rated CT primary current in A CTprim 1-99999
Rated CT secondary current in A CTsec 1-5 (step 1)
Current transformer earthing, Towards power CTstarpoint ToObject, FromObject
transformer/Towards bus
Rated VT primary voltage in kV VTprim 0,1-999,9
Rated VT secondary voltage in V VTsec 1-999

Table 19: Transformer differential protection


Function Parameter Value or Range
Current bias CharactNo Selectable characteristics
Inrush Stabilisation setting StabByOption Wave form and second
harmonic selections
Inrush restraint I2/I1ratio 10-25%
Overexcitation restraint I5/I1ratio 10-50%
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 14

Technical data (cont’d) Table 19: Transformer differential protection


Function Parameter Value or Range
Basic diff. current, % of object Ir Idmin 10-50%
High, non-restraint diff. current, % of object Ir Idunre 500-2500%
Zero Sequence Current Subtraction ZSCSub Off/On
Operation crossblocking CrossBlock Off/On
Number of taps NoOfTaps 1 - 64
Rated tap RatedTap 1 - 64
Voltage for minimum tap (tap1) in kV MinTapVoltage 0,1 - 999,9
Voltage for maximum tap in kV MaxTapVoltage 0,1 - 999,9
Operate time
at diff. current I = 2 x Ir 33 ms, typically
at diff. current I = 10 x Ir 30 ms, typically
at diff. current I = 2 x Idunre 20 ms, typically
Reset time Typical 15 ms

Table 20: Three-phase time overcurrent protection


Function Parameter Value or Range
Level 1
Operate current, % of object Ir or
user defined Ir IsetLow 10-500%
Time characteristics CurveType DEF, NI, VI, EI, LI
Definite time setting tDefLow 0,03- 240,00 s
Inverse time characteristics Acc. to IEC 60255-3
t=(k × T)/[(I/Is1)e -1] Normal inverse, Type A
Is1 = IsetLow Very inverse, Type B
Extremely inverse, Type C
Long time inverse
Time multiplier k 0,05-1,10
Definite minimum time tMin 0,05-1,00 s
High set current, % of object Ir or
user defined Ir IsetHigh 10-2000%
Time setting tDefHigh 0,03-5,00 s
Selection of nondirectional, forward or DirectionLow NonDir, Forward, Reverse
reverse direction for lowset
Selection of nondirectional forward or reverse DirectionHigh NonDir, Forward, Reverse
direction for highset
Relay Characteristic Angle in degrees rca -50 to -20 degrees
Relay Operate Angle in degrees roa ±60 to ±90 degrees
Resetting ratio > 0,95
Operate time
IEC curves Class 5 and -0/+40 ms
Definite time setting ±0,5% of setting -0/+40 ms
Reset time Typical 35 ms
Transient overreach for DC offset L/R<100ms < 10%
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 15

Table 21: Restricted earth-fault protection


Function Parameter Value or Range
Basic diff. current, % of object Ir Idmin 5-50%
Directional rca (fixed) 180°
characteristic roa ±60° to ±90°
Operate time at 2 × Id 30 ms, typically
Reset time Typical 25 ms

Table 22: Earth-fault time current protection


Function Parameter Value or Range
Level 1
Operate current, % of object Ir or
user defined Ir IsetLow 3-500%
Time characteristics CurveType Definite (independent)
Inverse (dependent)
Definite time setting tDefLow 0,03-240,00 s
Inverse time characteristics Acc. to IEC 60255-3
t=(k × T)/[(I/Is1)e -1] Normal inverse, Type A
Is1 = IsetLow Very inverse, Type B
Extremely inverse, Type C
Long time inverse
Time multiplier k 0,05-1,10
Definite minimum time tMin 0,05-1,00 s
Logarithmic inverse (RXIDG)
t= 5,8-1,35 × ln(I/Ib)
Ib = IsetLow
Min current Istart x IsetLow Istart 1,0 -4,0
Definite min. time tLog 0,03-10,00 s
High set current, % of object Ir or
user defined Ir IsetHigh 20-2000%
Time setting tDefHigh 0,03-10,00 s
2nd harmonic restrain 2harLow Off/On
2harHigh Off/On
Second to first harmonic ratio I2/I1ratio 10-25%
Relay characteristic angle in degrees rca 0 to 90 degrees
Relay operate angle in degrees roa ±60 to ±90 degrees
Selection of nondirectional, forward or DirectionLow NonDir, Forward, Reverse
reverse direction for lowset
Selection of nondirectional forward or reverse DirectionHigh NonDir, Forward, Reverse
direction for highset
Resetting ratio > 0,95
Operate time
IEC curves Class 5 and -0/+40ms
Definite time setting ±0,5% of setting -0/+40ms
Reset time Typical 35 ms
Transient overreach for DC offset L/R<100ms < 10%
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 16

Technical data (cont’d)

Table 23: Single-/Three-phase time overvoltage protection


Function Parameter Value or Range
Operate voltage, % of object Ur UsetLow 5,0-200,0%
Time characteristics CurveType Definite (Independent)
Very Inverse (Dependent)
Definite time setting tDefLow 0,03-120,00 s
Inverse time characteristic Very Inverse
t=(k × T)/[(U/Us1)e -1]
Us1 = UsetLow
Time multiplier k 0,05-1,10
Definite minimum time tMin 0,05-1,00 s
High set voltage, % of object Ur UsetHigh 5,0-200,0%
Time setting tDefHigh 0,03-60,00 s
Resetting ratio > 0,99
Operate time
IEC curves Class 5 and -0/+40ms
Definite time setting ±0,5% of setting -0/+40ms
Reset time Typical 35 ms

Table 24: Single-/Three-phase time undervoltage protection


Function Parameter Value or Range
Operate voltage, % of object Ur UsetLow 5,0-130,0%
UsetHigh 5,0-130,0%
Time setting tDefLow 0,03-120,00 s
tDefHigh 0,03-120,00 s
Resetting ratio < 1,01
Operate time
Definite time setting ±0,5% of setting -0/+40 ms
Reset time Typical 35 ms

Table 25: Neutral time voltage protection


Function Parameter Value or Range
The Time Overvoltage Protection is used for this application

Table 26: Thermal overload protection


Function Parameter Value or Range
Normal base current, in % of object Ir lb1 30-250%
Based current used with true COOLING input lb2 30-250%
signal, in % of Ir
Thermal overload steady state trip current Itr 50-250%
in % of Ibx
Initial heat content in % of heat content trip Thetalnit 0-95%
value (Itr)2
Normal time constant, in min, used with lb1 TimeConstant1 1-500 min
Time constant, in min, used with lb2 TimeConstant2 1-500 min
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 17

Table 26: Thermal overload protection


Function Parameter Value or Range
1:st alarm level, in % of heat content trip Alarm1 50-99%
value (Itr)2
2:nd alarm level, in % of heat content trip Alarm2 50-99%
value (Itr)2
Reset level for lock-out, in % of heat content ResetLockOut 10-95%
trip value (Itr)2
Operate time ±5% of set time

Table 27: Overexcitation protection


Function Parameter Value or Range
Emax continous no-load Emaxcont 1,00-1,50 p.u.
Emax when time according to Emax 1,20-1,80 p.u.
delay tMin takes over
Minimum time delay when over tMin 0,50-30,00 s
excitation >Emax
Maximum time delay for over excitation tMax 10-120 min
IEEE time characteristics
t=(k × 0.18)/[M -1]2
M = overexcitation

Time multiplier for inverse time functions k 1-60


Transformer cooling time constant Tcool 1-120 min
Time delay for alarm tAlarm 0-120 s
Time value in sec. for Time 1 t1 0-7200 s
Time value in sec. for Time 2 t2 0-7200 s
Time value in sec. for Time 3 t3 0-7200 s
Time value in sec. for Time 4 t4 0-7200 s
Time value in sec. for Time 5 t5 0-7200 s
Time value in sec. for Time 6 t6 0-7200 s
Operate time ±5% of setting -0/+40 ms

Table 28: Voltage control function


Function Parameter Value or Range
Voltage control set voltage, % of Ur2* Uset 85,0-120,0%
acc < 0,5 % of Ur
Set voltage deadband, % of Ur2 Udeadband 0,5-9,0%
Set inner deadband, % of Ur2 UdeadbandInner 0,1-9,0 %
Upper limit busbar voltage Umax 100-130%
acc < 0,5 % of Ur
Lower limit busbar voltage Umin 70-95%
acc < 0,5 % of Ur
Fast step down function activation FSDMode Off, Auto, AutoMan
Time characteristic for Time 1 t1Use Const
(first command) Inverse
Time delay for first command t1 1-300 s
Time characteristic for Time 2 t2Use Const
(consecutive command) Inverse
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 18

Technical data (cont’d) Table 28: Voltage control function


Function Parameter Value or Range
Time delay for consecutive command t2 1-300 s
Minimum operating time in sec tMin 1,0-30,0 s
Operation line voltage drop compensation OperationLDC Off/On
Regulation for capacitive load OperCapaLDC Off/On
Line resistance, primary values Rline 0,0-150,0 ohm
Line reactance, primary values Xline -150,0 to 150,0 ohm
Constant load voltage adjust factor 1 LVAConst1 -9,0 to 9,0%
Constant load voltage adjust factor 2 LVAConst2 -9,0 to 9,0%
Constant load voltage adjust factor 3 LVAConst3 -9,0 to 9,0%
Constant load voltage adjust factor 4 LVAConst4 -9,0 to 9,0%
Load current dependent automatic voltage VRAuto -4,0 to 0,0%
reduction factor
Undervoltage blocking, % of Ur2 Ublock 50-90%
Operation OLTC reversed action blocking OperationRA Off/On
Power system emergency blocking time tRevAct 30-360 s
Tap changer low limit position LowVoltTap 1-64
Tap changer high limit position HighVoltTap 1-64
Overcurrent blocking, % of object Ir1 Iblock 0-250%
Output pulse duration tPulseDur 0,5-5,0 s
Tap changer constant timeout time tTCTimeout 1-60 s
Hunting detection alarm, max operation/day DayHuntDetect 0-100
Hunting detection alarm, max operation/hour HourHuntDetect 0-30
Time sliding window hunting detection tHuntDetect 1-120 min
Hunting detection alarm, max operation/wind NoOpindow 0-30
Contact life counter factor CLFactor 1,0 -3,0
Initial value tap changer life counter InitCLCounter 0-9999999
External MMI operation priority mode ExtMMIPrio Priority/No Priority
Total block of the voltage control function TotalBlock Off/On
Automatic mode block of the voltage control AutoBlock Off/On
*) Rated secondary side power transformer voltage set in menu Transformer data

Table 29: Additional voltage control parameters for parallel power transformers
Parallel operation OperatonPAR Off/On
Parallel transformer reactance reduced to
secondary side (for each transformer T x) Tx Xr2 0,1-20,0 ohm
Parallel control compensation factor Comp 0-2000%
Operation circulation current block function OperationCC Off/On
Circulating current block limit (primary value) CircCurrLimit 0,0-20000,0 A
Circulating current delay time tCircCurrent 1- 300 s
Operation common setpoint for parallell op OperUsetPar Off/On
Operation simultaneous tapping prohibited OperSimtap Off/On
Operation homing function OperHoming Off/On
VTmismatch VTmismatch 0,5-10,0 %
VTmismatch time tVTmismatch 1,0-10,0 s
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 19

Terminal
diagrams
P8 P3

X81:TX P8 SLM
#
1a) X82:RX SERIIAL CH INTERFACE
FIBRE X31:
X83:TX 1A 1
OPTIC
2) X84:RX LON CH INTERFACE 5A 2
AI 1(I)
TX 3
1A 4
1b) HMI HMI 5A 5
AI 2(I)
RX 6 • • •
• • •
1A 7
P14 AI 3(I) 5A 8
9
1A 10
X141:1 INTERNAL FAIL 5A 11
NO AI 4(I)
X141:3 12
3) NC
X141:2 1A 13


5A 14


AI 5(I)
+ - 15
X141:4
+ 1A 16
4) X141:5 5A 17
- AI 6(I)
18
P12 1A 19
AI 7(I) 5A 20
X121:7
+ 21
5) MI.11 22
X121:8
-
X121:9 AI 8(U)
24
MI.12 25
X121:10
AI 9(U) • • •
X121:11
27 • • •
MI.13 28
X121:12
X121:13 AI 10(U)
30
MI.14
X121:14
X121:15
MI.15
X121:16
X121:17
MI.16
X121:18
RET 521
P9
X91:1 PROTECTION, CONTROL &
+ MONITORING FUNCTIONS
6) X91:2 BI.01
-
X91:3
+
7) X91:4 BI.02
-
X91:5
+ TOC (HV) 3I>
8) X91:6 BI.03
- 1a) SERIAL CHANNEL BUS (SPA), BACK
X91:7 REF (HV) Id
+
9) X91:8 BI.04 1b) SERIAL CHANNEL BUS (SPA), FRONT WITH
-
X91:9 TEF (HV) I SPECIAL INTERFACE CABLE
+
10) X91:10 BI.05
- 2) LON BUS
X91:11 DIFP 3Id/I
+
11) X91:12 BI.06 3) INTERNAL FAIL / LOSS OF AUXILARY VOLT-
-
X91:13 AGE
+ TOC (LV) 3I>→
12) X91:14 BI.07
- 4) AUXILIARY DC VOLTAGE, EL
X91:15 TOV (residual) U
+
13) X91:16 BI.08 5) OLTC POSITION TRANSDUCER SIGNAL
-
TOV (LV) 3U>
BO.01 6) RESET
X92:2
14) BO.02 TUV (LV) 3U<
X92:3 7) WINDING TEMP TRIP
X92:4 BO.03 THOL I 8) OIL TEMP TRIP
X92:5 BO.04
BO.05 OVEX U>/f 9) BUCHHOLZ ALARM
X92:6
X92:9 BO.06 10) PRESSURE ALARM
15) VCTR U><
X92:8 11) WINDING TEMP ALARM
X92:11 BO.07
16)
DRP 12) TRANSFORMER DISCONNECTED
X92:12 BO.08 (disturb report)
17) BO.09 13) TAP CHANGER IN PROGRESS
X92:13
X92:14 BO.10
14) TRIP HV CIRCUIT BREAKER
X92:16 *) BO.11
15) TRIP LV CIRCUIT BREAKER
18) *) BO.12
X92:18
19) 16) TAP CHANGER RAISE
17) TAP CHANGER LOWER
X92:17
X92:15
X92:10
X92:7
X92:1

*) REED CONTACTS 18) SIGNAL (TRIP HV)


19) SIGNAL (TRIP LV)

Fig. 3 2 Winding Transformer Protection Terminal Diagram acc to configuration alternative 1


P8 P3 X31:
1A 1
X81:TX P8 SLM
AI 1(I) 5A 2
1a) X82:RX SERIAL CH INTERFACE
# 3
FIBRE 1A 4
X83:TX
OPTIC AI 2(I) 5A 5
2) X84:RX LON CH INTERFACE
6 • • • • • •
TX 1A 7 • • • • • •

1b) AI 3(I) 5A 8
HMI HMI
RX 9
1A 10
AI 4(I) 5A 11
P14 12
1A 13
AI 5(I) 5A 14
X141:1 INTERNAL FAIL 15
NO
X141:3 1A 16
3) NC
X141:2 AI 6(I) 5A 17
- 18
+
X141:4 1A 19
+ 5A 20
4) X141:5 AI 7(I)
- 21
1A 22
P12 AI 8(I) 5A 23
X121:7 24
+ 25
MI.11


5)


X121:8 AI 9(U)
-
X121:9 27
28
MI.12
• • •

X121:10
• • •

AI 10(U)



X121:11 30
MI.13
X121:12 P7 X71:
X121:13 1A 1
MI.14 AI 1(I) 5A 2
X121:14 # 3
X121:15 1A 4
MI.15 AI 2(I) 5A 5
X121:16
Transformer protection terminal

6
X121:17 1A 7
MI.16 AI 3(I) 5A 8
X121:18 9
1A 10
AI 4(I) 5A 11
12
1A 13
AI 5(I) 5A 14
15
1A 16
RET 521 AI 6(I) 5A 17
18
1A 19
5A 20 • • • • • •
AI 7(I) • • • • • •
21
1A 22
AI 8(I) 5A
24
1A 25
AI 9(I) 5A
27
28
AI 10(U)
30
Page 20
1MRK 504 013-BEN
RET 521*2.3
P9
X91:1 1a) SERIAL CHANNEL BUS (SPA), BACK
+
6) X91:2 BI.01 1b) SERIAL CHANNEL BUS (SPA), FRONT
-
X91:3 PROTECTION, CONTROL & WITH SPECIAL INTERFACE CABLE
+
7) X91:4 BI.02 MONITORING FUNCTIONS
-
+ X91:5 2) LON BUS
8) X91:6 BI.03
- 3) INTERNAL FAIL / LOSS OF AUXILIARY VOLT-
X91:7
+ RET 521 AGE
9) X91:8 BI.04
- TOC (HV) 3I> 4) AUXILIARY DC VOLTAGE, EL
+ X91:9
10) X91:10 BI.05
- REF (HV) Id 5) OLTC POSITION TRANSDUCER SIGNAL
X91:11
+ (ONLY IF BINARY INPUT NOT USED)
11) X91:12 BI.06 TEF (HV) I
-
+ X91:13 6) RESET
12) X91:14 BI.07
-
X91:15 DIFP 3Id/I 7) WINDING TEMP TRIP
+
13) X91:16 BI.08

Fig. 4
- 8) OIL TEMP TRIP
X92:1 TOC (MV) 3I>
+
14) X92:2 BI.09 9) EXTERNAL DISTURBANCE RECORDER START
-
X92:3 REF (MV) Id
+ X92:4
15) BI.10 10) OIL TEMP ALARM
- X92:5 TEF (MV) I
+ 11) BUCHHOLZ ALARM
16) X92:6 BI.11
- TOV (MV) U>
X92:7 12) PRESSURE ALARM
+ X92:8
17) BI.12
- TUV (MV) U<
X92:9 13) TRANSFORMER DISCONNECTED
+
18) X92:10 BI.13
- 14) TAP CHANGER IN PROGRESS
X92:11
+ X92:12 TOC (LV) 3I>
19) BI.14 15) TAP CHANGER POSITION BIT 1
- X92:13
+ TOV (LV) U
20) X92:14 BI.15 16) TAP CHANGER POSITION BIT 2
-
X92:15
+ 17) TAP CHANGER POSITION BIT 3
21) X92:16 BI.16 THOL I
-
18) TAP CHANGER POSITION BIT 4
P10 OVEX U>/f
19) TAP CHANGER POSITION BIT 5
X101:1 BO.01
22) BO.02 20) TAP CHANGER POSITION BIT 6
22) X101:3 VCTR U><
X101:4 BO.03
22) BO.04 21) TAP CHANGER PARITY BIT
22) X101:6
X101:7 BO.05 DRP 22) TRIP HV CIRCUIT BREAKERS
23) BO.06 (disturb report)
Transformer protection terminal

23) X101:9
X101:10 BO.07 23) TRIP MV CIRCUIT BREAKERS
23) BO.08
23) X101:12 24) TRIP LV CIRCUIT BREAKER
X101:13 BO.09
24) BO.10
24) X101:15 25) RET TRIP LOCKOUT
X101:16 BO.11
25) BO.12 26) OVERLOAD ALARM 1
26) X101:18
X102:1 BO.13
27) BO.14 27) OVERLOAD ALARM 2
28) X102:3
X102:4 BO.15
29) 28) OVEREXCITATION ALARM
X102:6 BO.16
30) BO.17
X102:7 29) EXTERNAL DISTURBANCE RECORDER
31) BO.18
32) X102:9 START
X102:10 BO.19
33) BO.20 30) OIL TEMP ALARM
34) X102:12
X102:13 BO.21
35) BO.22 31) BUCHHOLZ ALARM
36) X102:15
X102:16 BO.23 32) PRESSURE ALARM
37) BO.24
38) X102:18
33) TRANSFORMER DISCONNECTED

3 winding Transformer Terminal Diagram acc to configuration alternative no 5


34) TAP CHANGER AUTOBLOCK
35) TAP CHANGER ERROR

X102:17
X102:14
X102:11
X102:8
X102:5
X102:2
X101:17
X101:14
X101:11
X101:8
X101:5
X101:2
36) TAP CHANGER HUNTING
37) TAP CHANGER RAISE
38) TAP CHANGER LOWER
RET 521*2.3
Page 21
1MRK 504 013-BEN
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 22

Ordering RET 521 are intended for two-winding transformer or three-winding transformer applications.
The analog transformer input modules type AIM can be configured to the application with
maximum 10 input transformers for each analog input module, maximum 2 analog input mod-
ules can be included. The basic versions occupy 3/4 of a 6U 19 inch rack. Totally 4 rack posi-
tions are intended for I/O boards in the 3/4 rack. One optional test switch type RTXP 24 can be
fitted in the same 19 inch rack together with the protection terminal. If two test switches are
needed the second one has to be placed in an other rack.

The base terminal contains hardware always needed and some basic software functions. The
hardware in the terminal will be customised by additional choices according to the alternatives
below.

Protection and control functions can be added to the terminal while observing the need and lim-
itations for the number of input transformers and also the need and limitations for the number
of I/O boards.

Hardware base modules


Casing with connection board and front HMI panel, 3/4 of 6U 19 inch

Numerical module (processor board)

Auxiliary power supply module

Software base functions


Frequency measurement function (FRME)

Service value reading

Event recording and trip value recording (in disturbance report)

Custom logic programming (40 AND, 40 OR, 20 inverters, 25 timers, 20 pulse timers, 10 SR-
gates and 3 MOVE blocks)

Trip logic,12 blocks

Binary converter

Event function (single and double indications)

Command function (single and multiple)


Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 23

Ordering Number: 1MRK 001 530-AC Quantity:

Basic data:
Nominal frequency: 50/60 Hz
Rated VT input voltage 100/√3, 110/√3, 115/√3, 120/√3, 100, 110, 115, 120 V
(across each individual
input)
Rated CT input current 1/5 A
Auxiliary dc voltage EL 110-250 V

Basic data to be specified

RET 521 Protection and control functions

Select with “X” mark required protection and control functions.

Transformer terminal*) Available options


Max one option can be chosen Two winding Three winding
Transformer terminal 1MRK 001 534-SB 1MRK 001 534-TB

*) Needs only to be filled in when no transformer differential protection is ordered in next table
If transformer differential protection is ordered in next table the type of transformer terminal
will automatically be chosen from that information.

Transformer differential protection Available options


Max one option can be chosen Two winding Three winding
Transformer differential protection, DIFP 1MRK 001 534-NC 1MRK 001 534-PC

Three-phase time overcurrent Available options


protection
Max three options totally and only one per Non-Directional Directional
TOCx can be chosen
First time overcurrent protection, TOC1 1MRK 001 538-AA 1MRK 001 538-DA
Second time overcurrent protection, TOC2 1MRK 001 538-BA 1MRK 001 538-EA
Third time overcurrent protection, TOC3 1MRK 001 538-CA 1MRK 001 538-FA

Restricted earth fault protection Available options


First restricted earth fault protection, REF1 1MRK 001 538-GA
Second restricted earth fault protection, REF2 1MRK 001 538-HA
Third restricted earth fault protection, REF3 1MRK 001 538-KA
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 24

Ordering (cont’d)
Earth fault time current protection Available options
Max three options totally and only one per Non-Directional Directional
TEFx can be chosen
First earth fault time current protection, 1MRK 001 538-LA 1MRK 001 538-PA
TEF1
Second earth fault time current protection, 1MRK 001 538-MA 1MRK 001 538-RA
TEF2
Third earth fault time current protection, 1MRK 001 538-NA 1MRK 001 538-SA
TEF3

Thermal overload protection Available options


Thermal overload protection, THOL 1MRK 001 534-GA

Single-/Three-phase overvoltage protection or neutral time voltage Available options


protection
First time overvoltage protection, TOV1 1MRK 001 538-TA
Second time overvoltage protection, TOV2 1MRK 001 538-UA
Third time overvoltage protection, TOV3 1MRK 001 538-VA
Fourth time overvoltage protection, TOV4 1MRK 001 538-XA
Fifth time overvoltage protection, TOV5 1MRK 001 538-YA
Sixth time overvoltage protection, TOV6 1MRK 001 538-ZA

Single-/Three-phase time undervoltage protection Available options


First time undervoltage protection, TUV1 1MRK 001 534-UA
Second time undervoltage protection, TUV2 1MRK 001 534-VA
Third time undervoltage protection, TUV3 1MRK 001 534-XA

Overexcitation protection Available options


Overexcitation protection, OVEX 1MRK 001 534-HC

Voltage control (On-load tap changer Available options


control)
Max one option can be chosen Single Parallel(*)
Voltage control, VCTR 1MRK 001 534-LC 1MRK 001 534-MC
(*) Requires rear LON communication port on the RET terminal

Disturbance recorder Available options


Disturbance recorder DR 1MRK 001 534-KC
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 25

RET 521 Configuration


In the table below the hardware requirements for some general applications have been sug-
gested. If the hardware is ordered according to that table also the corresponding example con-
figuration will be downloaded in the delivered terminal. The six example configurations are
available as templates in the configuration tool. The example configurations often cover more
functionality than required in a specific case. Since all example configurations are available the
necessary changes for a specific application will be easy to implement by using examples from
the other configuration templates. The configuration tool CAP 535 have to be used to do the
changes.

If the hardware required is different from the alternatives in the table below no example config-
uration is downloaded but the user can easily change one of the example configurations in CAP
or built his own configuration to fit his application. The hardware configuration is always
downloaded in the delivered terminal.

If the user require to have a specific configuration made and downloaded in the delivered ter-
minal by ABB this can be ordered as well.

Table 30: Configuration examples


One One
One One mA
Binary Binary In/ Intended
Configura- One AIM Two AIM One AIM One AIM Binary In input
Out Out for
tion 7I+3U in 7I+3U in 8I+2U in 9I+1U in module module
module module transfor-
alternative position positions position position in in
in in mer with
position position
position position

Example 1 P3 P9 2 windings

Example 2 P3 P9 P12 2 windings

Example 3 P3 P9 P10 P12 2 windings

Example 4 P3 and P7 P9 P10 3 windings

Example 5 P3 P7 P9 P10 3 windings

Example 6 P3 P9 P10 P12 3 windings

RET 521 Hardware Components

Select with “X” mark in tables below the required type of module per slot location

Analog Input Module Available options for Analogue Input Module


7I + 3U 8I + 2U 9I + 1U
1MRK 001 162-AA 1MRK 001 162-BA 1MRK 001 162-CA
Analog Input Module 1
(Located in Slot P3)
Analog Input Module 2 (Located
in Slot P7)
7I+3U = Seven CT Inputs and Three VT Inputs
8I+2U = Eight CT Inputs and Two VT Inputs
9I+1U = Nine CT Inputs and One VT Inputs
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 26

(cont’d)
Binary Input/Output & Available options for Input/Output Module
mA module BIM BOM IOM MIM
1MRK000508-xx 1MRK000614-AB 1MRK000173-xx 1MRK000284-AA
Input/Output Module 1
(Located in Slot P9)
Input/Output Module 2
(Located in Slot P10)
Input/Output Module 3
(Located in Slot P11)
Input/Output Module 4
(Located in Slot P12)
BIM = 16 Optocoupler Inputs. Please specify rated voltage of optocoupler inputs below
BOM = 24 Contact Outputs
IOM = 12 Contact Outputs and 8 Optocoupler Inputs. Please specify rated voltage of optoc. inputs below
MIM = 6 analog (i.e. mA) inputs, always located in Slot P12

Please specify with “X” mark rated voltage for optocoupler inputs only for slots in which you
have chosen BIM or IOM type of module
Available rated Voltages for Optocoupler Inputs on BIM & IOM Modules
24/30 V dc 48/60 V dc 110/125 V dc 220/250 V dc
for BIM xx =DB for BIM xx =AB for BIM xx =BB for BIM xx = CB
for IOM xx =GB for IOM xx =AC for IOM xx =BC for IOM xx = CC
Input/Output Module 1
(Located in Slot P9)
Input/Output Module 2
(Located in Slot P10)
Input/Output Module 3
(Located in Slot P11)
Input/Output Module 4
(Located in Slot P12)

Communication ports Available Options


SPA = Plastic SPA = Plastic SPA = Glass
LON = Plastic LON = Glass LON = Glass
1MRK 001 608-AA 1MRK 001 608-BA 1MRK 001 608-CA
Rear communication via SPA &
LON bus
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 27

Mechanical options:
Test switch
COMBITEST test switch module RTXP 1MRK 000 371-EA
Current circuits connected for rated current 1A 5A

On/Off switch for the dc-supply RK 795 017-AA

NOTE!
The test switches have internal star point connection of three-phase CT groups

Each analogue input module AIM is connected to its own test switch module so two test switches are
needed if two analogue input modules are used.
The first test switch module RTXP 24 will be mounted with the transformer protection terminal in
RHGS 6 case with window door forming a full 19 inch case.
The second test switch module RTXP 24 (if needed) will be mounted in a separate RHGS 6 case with
window door.
Test switch module RTXP24 for AIM2 mounted in RHGS6 Case 1MRK 000 371-EB

Rated current (1 or 5 A) to be specified for the connection between test switch and terminal.
The terminal is reconnectable and can at any time be altered between 1 or 5 A, but the terminal will be
delivered with all current channels connected to either 1 A or to 5 A.
Mounting details
Mounting details with IP40 degree of protection from the front for protection terminal case and if needed the
extra test switch case for a second test switch module:
Protection Second test
terminal switch case

19” rack mounting of 3/4 of 19” terminal 1MRK 000 020-BA


casing
19” rack mounting (applicable for terminal 1MRK 000 020-CA
together with test switch)
19” rack mounting for second test switch case 1MRK 000 020-BE
Wall mounting (applicable for terminal and for 1MRK 000 020-DA
test switch)
Flush mounting (applicable for terminal and 1MRK 000 020-Y
for test switch)
Flush mounting with IP54 (applicable 1MKC 980 001-2
for terminal only)

Manuals
One copy of the Application manual, the Installation and Commissioning manual, the Operator´s manual and
the Technical reference manual are always included for each terminal.
Rule: Specify the number of extra manual requested.
Installation and commissioning manual Quantity: 1MRK 504 017-UEN
Operator´s manual Quantity: 1MRK 504 015-UEN
Technical reference manual Quantity: 1MRK 504 016-UEN
Application manual Quantity: 1MRK 504 021-UEN
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 28

Related
documents
Technical Overview brochure
CAP 535*1.1 1MRK 511 086-BEN

For our reference and statistics we would be pleased if we are provided with the following application data:

Country: End user:

Station name: Voltage level: kV


Transformer Rated Power: MVA
Transformer protection terminal RET 521*2.3
1MRK 504 013-BEN
Page 29

Sample Numerical transformer terminal type RET tections, three-phase under- and over-voltage
Specification 521 with continuous selfmonitoring and ana- protections and neutral voltage protections
logue/digital conversion of all input quanti- shall be available for selectable windings. A
ties. The terminal shall be suitable for thermal overload protection and an overexci-
protection, control and monitoring of two- or tation protection shall be included.
three-winding transformers, auto-transform-
ers, reactors, and generator-transformer block Voltage regulation for single transformer or
units and also for applications with multi- parallel transformers with On-Load-Tap-
breaker arrangements. The numerical trans- Changer shall be included in the numerical
former terminal shall be designed to operate transformer terminal.
correctly over a wide frequency range to
accommodate for system frequency varia- The terminal shall be provided with a pro-
tions and block generator start-up. grammable logic for trip and indications and
configuration of the included protection, con-
The differential protection function shall be trol and monitoring functions, and the basic
provided with 2nd harmonic restraint to avoid structure shall be modular for binary inputs
tripping at magnetizing inrush and 5th har- and binary outputs to facilitate user adapta-
monic restraint to avoid tripping at overexci- tion. A mA transducer input module shall be
tation. Recovery inrush and CT saturation possible to add.
shall not influence the differential function.
The differential protection shall have a setta- The terminal shall be provided with a front
ble restraint characteristic and be provided mounted menu driven human-machine-inter-
with an adaptive differential feature for multi- face and a front port optical connector for a
breaker arrangements. The differential pro- personal computer. Service value display of
tection shall be stable in case of high through- voltage, currents, frequency, event recording
faults also in multi-breaker arrangements. with 150 events and 10 recordings, and dis-
Tap-changer position indication must be used turbance recording with 10 analogue signals
to provide maximum sensitivity for the differ- and 48 digital signals for 40 s, and local data
ential protection. A high-set unrestrained dif- storage shall be included. Communication
ferential current protection shall be included. with the terminal shall be provided with two
ports for LON and SPA in the rear for station
Three-phase time overcurrent protections, control and station monitoring purpose.
restricted earth-fault protections, second har-
monic restrained time earth-fault current pro-

References Series RE 500


mechanical packaging and connection 1MRK 510 010-BEN

COMBITEST Test system 1MRK 512 001-BEN

Auxiliary relays 1MRK 508 015-BEN

Manufacturer ABB Automation Products AB


Substation Automation Division
SE-721 59 Västerås
Sweden
Tel: +46 (0) 21 34 20 00
Fax: +46 (0) 21 14 69 18

You might also like