1Ph-2W Energy Meter

Double Current Element


Meter
What does it mean ?
This is the inside of the meter
Case of two meters in a premises with
independent wirings
Consumer 1

Phase

Supply No problems!!

Neutral

Consumer 2
Case of two meters in a premises with
common neutral wiring
Consumer 1

Phase

Supply This represents the common neutral

Neutral

Consumer 2
… and the Consumer 1 removes his
neutral
Consumer 1

Phase

Supply

Neutral

Consumer 2
The neutral current of Consumer 2 becomes sum of currents of both the consumers
The one who tampers doesn’t loose.
Consumer 1

Phase

Supply The looser is the one who doesn’t


tamper!!

Neutral

Consumer 2
The internal logic of the meter causes doubled recording of energy for Consumer 2