You are on page 1of 5

SEWA Regulations for Electrical Connection

5-8-1 The cross sectional area of the protective conductor shall not be less than the appropriate value
Shown in table 5.8.A in this case checking of compliance with clause 5.7 is not necessary

If the application of this table produces non standard size conductor having the nearest standard
Cross sectional areas are to be used.

Table 5.8.A

Cross sectional area of phase Minimum cross sectional area of the


Conductors of the installation Corresponding protective conductor
S (mm2 ) SP (mm2 )

S≤ 16 S

16 < S ≤ 35 16

S> 35 S/2

The value in table 5.8.A is valid only if the protective conductor is made of the same metal as the phase conductor. if this is not so
the cross sectional area of the protective conductor is to be determined in a manner which produces a conductance equivalent to
that which results from the application of table 5.8.A .

The cross sectional area of every productive conductor which doesn’t form part of the supply cable or cable enclosure shall be in
any case not less than
a) 2.5 mm2 if mechanical protection is provided
b) 4.0 mm2 if mechanical protection is not provided.

Page 61
SEWA Regulations for Electrical Connection

5.9.1 Types of protective conductor


Deleted

5-9-2 Protective Conductors may comprise:-


• Conductors in multi core cables
• Fixed bare or insulated conductors
• Insulated or bare conductors in common enclosure
• Metal covering ,for example , the sheaths and armouring of certain cables
• Metal conduits or other metal enclosures for conductors
• Certain extraneous conductor parts.

5-9-3 Where the installation contains enclosures or frames of factory Built assemblies or metal enclosed bus bar trunking
system (busway) the metal enclosure or frame may be used as protective conductors if they simultaneously satisfy
the following three requirement:

1. Their electrical continuity shall be achieved in such manner as to ensure protection against mechanical or
electromechanical deterioration

2. Their conductance shall be at least equal to that resulting from the application of clause 543

3. They shall permit the connection of the protective conductors at every predetermined tap-off point.

5.9.4 The metallic covering including sheaths (bare or insulated) of certain wiring in particular the sheaths of
Mineral –insulated cables, and certain metallic conduits and trunking for electrical purpose (types under consideration)
may be used as protective conductor for the corresponding circuits if they satisfy
Both purpose shall not be used as a protective conductor.

Page 62
SEWA Regulations for Electrical Connection

5-9-5 Extraneous conductive parts may be used as protective conductor if they satisfy all the following four
Requirement.

1. Their electrical continuity shall be assured, either by construction or by suitable connection, in such a way as to be

protected against mechanical, chemical or electromechanical deterioration.

2. Their conductance shall be at least equal to that resulting from the application of the clause 543

3. Unless compensatory measures are provided, precautions shall be taken against their removal
4. They have been considered for such a use and, if necessary , suitably adapted .

The use of metallic water pipe is permitted provided the consent of a person or body responsible for the water

system is obtained. Gas pipe shall not be used as protective conductor.

5-9-6 Extraneous conductive parts shall not be used as PEN conductors.

5-9-7 Preservation of electrical continuity of protective conductors.

5-9-8 Protective conductors shall be suitably protected against mechanical and chemical deterioration and
Electrodynamics forces.

5-9-9 Joints of protective conductors shall be accessible for inspection and testing except in compound-filled
Or encapsulated join

5-9-10 No switching device shall be inserted in the protective conductor , but joints which can be disconnected
For test purpose by use of a tool may be provided.

Page 63
SEWA Regulations for Electrical Connection
5-9-11 Where electrical monitoring of earth-continuity is used the operating coils shall not be inserted in
Protective conductors.

5-9-12 exposed conductive parts of apparatus shall not be used to form part of the protective conductor for
Other equipment except as allowed by sub-clause 5.9.5.

5.10 Earthing and protective conductors for fault –voltage –operated protective devices.

5-10-1 An auxiliary earth electrode shall be provided electrically independent of all other earthed metal for
Example, Constructional metalwork, pipes, or metal-sheathed cable .This requirement is considered to be fulfilled

If the auxiliary earth electrode is installed at a specified distance from all other earthed metal (value of distance

Under consideration).

5-10-2 The earthing conductor leading to the auxiliary earth electrode shall be insulated to avoid contact with
The protective conductor or any of the parts connected there to extraneous conductive parts which are
or may be in contact with them.

Note: this requirement is necessary to prevent the voltage sensitive element being inadvertently bridged.

5-10-3 The protective conductor shall be connected only to the exposed parts of those items of electrical
Equipment whose supply will be interrupted in the event of the protective device operating under fault
Condition.

5-10-4 Excessive earth –leakage current requirements under consideration.

Page 64
SEWA Regulations for Electrical Connection

5-11 Earthing Arrangement for functional purpose

5-11-1 General
Earthing arrangement for functional purpose shall be provided to ensure correct operation of
Equipment to permit reliable and proper functioning of installations
(Further requirement under consideration)

5-11-2 Low noise

5-12 Earthing arrangement for combined protective and functional purposes

5-12-1 General
Where earthing for combined protective and functional purpose is required, the requirements for
Protective measures shall prevail.

5-12-2 PEN conductor

5-12-3 In TN system, for cables in fixed installations having a cross-sectional area not less than 10mm
In copper or 16mm in aluminum, a single conductor may serve both as protective conductor
And neutral conductor, provided that the part of the installation concerned is not protected
By residual current-operated device.

However the minimum cross-sectional area of a PEN conductor may be 4mm provided that the cable
Is of a concentric type conforming to IEC standard and that duplicated continuity connections exist at
all joints and terminations in the runs of the concentric conductor.

Page 65

You might also like