U4 Motoring 17.8.2022 p243 Event
U4 Motoring 17.8.2022 p243 Event
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:29
Easergy Studio
Page: 2
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:30
Easergy Studio
Page: 3
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:30
Easergy Studio
Page: 4
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:30
Easergy Studio
Page: 5
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:31
IA Differential: 0 A
IB Differential: 0 A
IC Differential: 0 A
VN1 Measured: 0 V
VN Derived: 21.19 V
IN Measured: 0 A
I Sensitive: 0 A
I2: 835.7 A
V2: 125.7 V
3 Phase Watts: -1.551MW
3 Phase VArs: -13.49MVAr
3Ph Power Factor: -100.0e-3
Wednesday 17 August 2022 02:27:06.375 : Output Contacts1
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:00 Row:21
Event type: Device output changed state
Event Value: 1100000000000000000000
0 R1 186A TRIP: OFF
1 R2 186B TRIP: OFF
2 R3 ANY TRIP: OFF
3 R4 186C TRIP: OFF
4 R5 O/V to AVR CO: OFF
5 R6 V/Hz>1 -SCADA: OFF
6 R7 V/Hz>2 -SCADA: OFF
7 R8 286A TRIP: OFF
8 R9 286B TRIP: OFF
9 R10 286C TRIP: OFF
10 R11 SPARE: OFF
11 R12 SPARE: OFF
12 R13 SPARE: OFF
13 R14 SPARE: OFF
14 R15 SPARE: OFF
15 R16 SPARE: OFF
16 R17 SPARE: OFF
17 R18 SPARE: OFF
18 R19 SPARE: OFF
19 R20 SPARE: OFF
20 R21 SPARE: ON
21 R22 SPARE: ON
Wednesday 17 August 2022 02:27:06.375 : Any Trip OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:33
Event type: Standard Event
Event Value: 00000000000000000000000000100000
Wednesday 17 August 2022 02:27:06.370 : Output Contacts1
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:00 Row:21
Easergy Studio
Page: 6
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:31
Easergy Studio
Page: 7
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:31
Easergy Studio
Page: 8
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:32
Easergy Studio
Page: 9
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:32
Easergy Studio
Page: 10
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:32
Easergy Studio
Page: 11
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:33
Easergy Studio
Page: 12
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:33
0 Start A: OFF
1 Start B: OFF
2 Start C: OFF
3 Start N: OFF
4 Trip A: OFF
5 Trip B: OFF
6 Trip C: OFF
7 Trip N: OFF
Start Elements1: 00000000000000000000000000001111
0 General Start: ON
1 Start Power 1: ON
2 Start Power 2: ON
3 Start FFail1: ON
4 Start FFail2: OFF
5 Start V Dep O/C: OFF
6 Start I>1: OFF
7 Start I>2: OFF
8 Start I>3: OFF
9 Start I>4: OFF
10 Start IN>1: OFF
11 Start IN>2: OFF
12 Not Used: OFF
13 Not Used: OFF
14 Start ISEF>1: OFF
15 Start ISEF>2: OFF
16 Not Used: OFF
17 Not Used: OFF
18 Start NVD VN>1: OFF
19 Start NVD VN>2: OFF
20 Start 100%StEF3H: OFF
21 Start Sen Power1: OFF
22 Start Sen Power2: OFF
23 Start z PSlip Z1: OFF
24 Start z PSlip Z2: OFF
25 Start Z<1: OFF
26 Start Z<2: OFF
27 Not Used: OFF
28 Not Used: OFF
29 Not Used: OFF
30 Not Used: OFF
31 Not Used: OFF
Start Elements2: 00000000000000000000000000
0 Start V<1: OFF
1 Start V<2: OFF
2 Start V< A/AB: OFF
3 Start V< B/BC: OFF
4 Start V< C/CA: OFF
5 Start V>1: OFF
6 Start V>2: OFF
7 Start V> A/AB: OFF
8 Start V> B/BC: OFF
9 Start V> C/CA: OFF
10 Start F<1: OFF
Easergy Studio
Page: 13
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:33
Easergy Studio
Page: 14
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:34
Easergy Studio
Page: 15
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:34
Easergy Studio
Page: 16
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:34
V2: 16.57 V
3 Phase Watts: 482.9kW
3 Phase VArs: 19.46MVAr
3Ph Power Factor: 24.77e-3
Wednesday 17 August 2022 02:26:47.835 : Power1 Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00100000000000000000000000000000
Wednesday 17 August 2022 02:26:47.831 : PSlipz BlindStrt OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3C
Event type: Standard Event
Event Value: 00000000010000000000000000000000
Wednesday 17 August 2022 02:26:47.825 : Power1 Start ON
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00110000000000000000000000000000
Wednesday 17 August 2022 02:26:47.806 : Any Start ON
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3A
Event type: Standard Event
Event Value: 00000000000000000000000000111001
Wednesday 17 August 2022 02:26:47.806 : Power2 Start ON
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00100000000000000000000000000000
Wednesday 17 August 2022 02:26:47.801 : Output Contacts1
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:00 Row:21
Event type: Device output changed state
Event Value: 1100000000000000000000
0 R1 186A TRIP: OFF
1 R2 186B TRIP: OFF
2 R3 ANY TRIP: OFF
3 R4 186C TRIP: OFF
4 R5 O/V to AVR CO: OFF
5 R6 V/Hz>1 -SCADA: OFF
6 R7 V/Hz>2 -SCADA: OFF
Easergy Studio
Page: 17
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:35
Easergy Studio
Page: 18
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:35
Easergy Studio
Page: 19
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:35
20 R21 SPARE: ON
21 R22 SPARE: ON
Wednesday 17 August 2022 02:26:47.786 : FFail1 Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3A
Event type: Standard Event
Event Value: 00000000000000000000000000110001
Wednesday 17 August 2022 02:26:47.786 : Field Fail1 Trip OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:34
Event type: Standard Event
Event Value: 00000000000000000000000000000000
Wednesday 17 August 2022 02:26:47.786 : Power1 Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00100000000000000000000000000000
Wednesday 17 August 2022 02:26:47.786 : Power1 Trip OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:35
Event type: Standard Event
Event Value: 00100000000000000000000000000000
Wednesday 17 August 2022 01:49:34.245 : Field Fail Alarm ON
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:00 Row:22
Event type: Alarm event
Event Value: 00000000001000000000000000000000
0 Unused: OFF
1 Unused: OFF
2 SG-DDB Invalid: OFF
3 Prot'n Disabled: OFF
4 VT Fail Alarm: OFF
5 CT-1 Fail Alarm: OFF
6 CB Fail Alarm: OFF
7 I^ Maint Alarm: OFF
8 I^ Lockout Alarm: OFF
9 CB Ops Maint: OFF
10 CB Ops Lockout: OFF
11 CB Op Time Maint: OFF
12 CB Op Time Lock: OFF
13 Fault Freq Lock: OFF
14 CB Status Alarm: OFF
15 Not Used: OFF
Easergy Studio
Page: 20
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:36
Easergy Studio
Page: 21
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:36
Easergy Studio
Page: 22
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:36
Easergy Studio
Page: 23
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:37
Easergy Studio
Page: 24
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:37
Easergy Studio
Page: 25
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:37
Easergy Studio
Page: 26
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:38
Easergy Studio
Page: 27
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:38
Easergy Studio
Page: 28
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:38
22 CTS-2: OFF
Fault Time: Wednesday 17 August 2022 01:49:22.886
Active Group: 1
System Frequency: 50.17 Hz
IA-1: 1047 A
IB-1: 963.5 A
IC-1: 943.2 A
VAB: 11.15kV
VBC: 11.20kV
VCA: 11.18kV
VAN: 6453 V
VBN: 6424 V
VCN: 6478 V
IA-2: 1045 A
IB-2: 968.2 A
IC-2: 937.6 A
IA Differential: 0 A
IB Differential: 0 A
IC Differential: 0 A
VN1 Measured: 0 V
VN Derived: 76.43 V
IN Measured: 0 A
I Sensitive: 0 A
I2: 64.11 A
V2: 16.05 V
3 Phase Watts: -1.592MW
3 Phase VArs: 18.96MVAr
3Ph Power Factor: -83.55e-3
Wednesday 17 August 2022 01:49:23.294 : Any Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3A
Event type: Standard Event
Event Value: 00000000000000000000000000110000
Wednesday 17 August 2022 01:49:23.294 : Power2 Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00000000000000000000000000000000
Wednesday 17 August 2022 01:49:23.204 : Power1 Start OFF
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Address: 001 Column:0F Row:3B
Event type: Standard Event
Event Value: 00100000000000000000000000000000
Wednesday 17 August 2022 01:49:22.905 : Power1 Start ON
Description: Gen Prot GR1
Plant reference: KTPS - 4GRP
Model number: P343211E3M0320J
Easergy Studio
Page: 29
Events Report
Substation:
File: 2022-06-12 20.31.08.evt
Model Number: P343211E3M0320J Printed on: 12/06/2022 21:10:38
Easergy Studio