1. Introduction
This section describes heating, ventilating, and air conditioning (HVAC) systems and
discusses characteristics and components of automatic control systems.
Properly applied automatic controls ensure that a correctly designed HVAC system
will maintain a comfortable environment and perform economically under a wide
range of operating conditions. Automatic controls regulate HVAC system output in
response to varying indoor and outdoor conditions to maintain general comfort
conditions in office areas and provide narrow temperature and humidity limits
where required in production areas for product quality.
Automatic controls optimize HVAC system operation. They can adjust temperatures
and pressures automatically to reduce demand when spaces are unoccupied and
regulate heating and cooling to provide comfort conditions while limiting energy
usage. Limit controls ensure safe operation of HVAC system equipment and prevent
injury to personnel and damage to the system.
1
2.1 Controlled Variables
In a room heated by air moving through a hot water coil, for example, the
thermostat measures the temperature (controlled variable) of the room air
(controlled medium) at a specified location. As the room cools, the thermostat
operates a valve that regulates the flow (manipulated variable) of hot water (control
agent) through the coil. In this way, the coil furnishes heat to warm the room air.
The sensor can be separate from or part of the controller and is located in the
controlled medium. The sensor measures the value of the controlled variable and
sends the resulting signal to the controller. The controller receives the sensor signal,
compares it to the desired value, or set-point, and generates a correction signal to
direct the operation of the controlled device. The controlled device varies the
control agent to regulate the output of the control equipment that produces the
desired condition.
HVAC applications use two types of control loops: open and closed. An open-loop
system assumes a fixed relationship between a controlled condition and an external
condition. An example of open-loop control would be the control of perimeter
radiation heating based on an input from an outdoor air temperature sensor. A
circulating pump and boiler are energized when an outdoor air temperature drops to
a specified setting, and the water temperature or flow is proportionally controlled as
a function of the outdoor temperature. An open-loop system does not take into
account changing space conditions from internal heat gains, infiltration/exfiltration,
solar gain, or other changing variables in the building. Open-loop control alone does
2
not provide close control and may result in under-heating or over-heating. For this
reason, open-loop systems are not common in residential or commercial
applications.
In this example, the sensing element measures the discharge air temperature and
sends a feedback signal to the controller. The controller compares the feedback
signal to the set-point. Based on the difference, or deviation, the controller issues a
corrective signal to a valve, which regulates the flow of hot water to meet the
process demand. Changes in the controlled variable thus reflect the demand. The
sensing element continues to measure changes in the discharge air temperature and
feeds the new condition back into the controller for continuous comparison and
correction.
Automatic control systems use feedback to reduce the magnitude of the deviation
and produce system stability as described above. A secondary input, such as the
input from an outdoor air compensation sensor, can provide information about
disturbances that affect the controlled variable. Using an input in addition to the
controlled variable enables the controller to anticipate the effect of the disturbance
3
and compensate for it, thus reducing the impact of disturbances on the controlled
variable.
2.3 Control Methods
2.3.1 General
An automatic control system is classified by the type of energy transmission and the
type of control signal (analogue or digital) it uses to perform its functions.
The most common forms of energy for automatic control systems are electricity and
compressed air. Systems may comprise one or both forms of energy.
Self-powered systems are a comparatively minor but still important type of control.
These systems use the power of the measured variable to induce the necessary
corrective action. For example, temperature changes at a sensor cause pressure or
volume changes that are applied directly to the diaphragm or bellows in the valve or
damper actuator.
4
the variable being measured. The controller compares the air pressure sent by the
sensor to the desired value of air pressure as determined by the set-point and sends
out a control signal based on the comparison.
The digital controller receives electronic signals from sensors, converts the electronic
signals to digital pulses (values), and performs mathematical operations on these
values. The controller reconverts the output value to a signal to operate an actuator.
The controller samples digital data at set time intervals, rather than reading it
continually. The sampling method is called discrete control signaling. If the sampling
interval for the digital controller is chosen properly, discrete output changes provide
even and uninterrupted control performance.
Figure 2 compares analogue and digital control signals. The digital controller
periodically updates the process as a function of a set of measured control variables
and a given set of control algorithms. The controller works out the entire
computation, including the control algorithm, and sends a signal to an actuator. In
most commercial control systems, an electronic-pneumatic transducer converts the
electric output to a variable pressure output for pneumatic actuation of the final
control element.
5
Control systems use different control modes to accomplish their purposes. Control
modes in commercial applications include two-position, step, and floating control;
proportional, proportional-integral, and proportional-integral-derivative control; and
adaptive control.
2.4.1 Two-position Control (On-Off Control)
2.4.1.1 General
In two-position control, the final control element occupies one of two possible
positions except for the brief period when it is passing from one position to the
other. Two-position control is used in simple HVAC systems to start and stop electric
motors on unit heaters, fan coil units and refrigeration machines..
In two-position control, two values of the controlled variable (usually equated with
on and off) determine the position of the final control element. Between these
values is a zone called the “differential gap” or “differential” in which the controller
cannot initiate an action of the final control element. As the controlled variable
reaches one of the two values, the final control element assumes the position that
corresponds to the demands of the controller, and remains there until the controlled
variable changes to the other value. The final control element moves to the other
position and remains there until the controlled variable returns to the other limit.
Basic two-position control works well for many applications. For close temperature
control, however, the cycling must be accelerated or timed.
In basic two-position control, the controller and the final control element interact
without modification from a mechanical or thermal source. The result is cyclical
operation of the controlled equipment and a condition in which the controlled
variable cycles back and forth between two values (the on and off points) and is
influenced by the lag in the system. The controller cannot change the position of the
6
final control element until the controlled variable reaches one or the other of the
two limits of the differential. For that reason, the differential is the minimum
possible swing of the controlled variable. Figure 20 shows a typical heating system
cycling pattern.
The overshoot and undershoot conditions shown in Figure 3 are caused by the lag in
the system. When the heating system is energized, it builds up heat which moves
into the space to warm the air, the contents of the space and the thermostat. By the
time the thermostat temperature reaches the off point (e.g., 22oC), the room air is
already warmer than that temperature. When the thermostat shuts off the heat, the
heating system dissipates its stored heat to heat the space even more, causing
overshoot. Undershoot is the same process in reverse.
In basic two-position control, the presence of lag causes the controller to correct a
condition that has already passed rather than one that is taking place or is about to
take place. Consequently, basic two-position control is best used in systems with
minimal total system lag (including transfer, measuring, and final control element
lags) and where close control is not required.
7
Figure 4 - Basic Two-Position Control Loop
2.4.1.3 Timed two-position control (Timer On-Off Control)
General
The ideal method of controlling the temperature in a space is to replace lost heat or
displace gained heat in exactly the amount needed. With basic two-position control,
such exact operation is impossible because the heating or cooling system is either
full on or full off and the delivery at any specific instant is either too much or too
little. Timed two-position control, however, anticipates requirements and delivers
measured quantities of heating or cooling on a percentage on-time basis to reduce
control point fluctuations. The timing is accomplished by a timer in electronic and
digital controls.
In timed two-position control, the basic interaction between the controller and the
final control element is the same as for basic two-position control. However, the
controller responds to gradual changes in the average value of the controlled
variable rather than to cyclical fluctuations.
Overshoot and undershoot are reduced or eliminated because the heat anticipation
or time proportioning feature results in a faster cycling rate of the mechanical
equipment. The result is closer control of the variable than is possible in basic two-
position control (Fig. 5).
8
Figure 5 - Comparison of Basic Two-Position and Timed Two-Position Control.
2.4.1.4 Time proportioning
Time proportioning control provides more effective two-position control than heat
anticipation control and is available with sophisticated electromechanical
thermostats and electronic and microprocessor-based controllers. Heat is
introduced into the space using on/off cycles based on the actual heat load on the
building and programmable time cycle settings. This method reduces large
temperature swings caused by a large total lag and achieves a more even flow of
heat.
9
The cycle time in Figure 6 is set at ten minutes. At a 50 percent load condition, the
controller, operating at set-point, produces a 5-minute on/5-minute off cycle. At a
75 percent load condition, the on time increases to 7.5 minutes, the off time
decreases to 2.5 minutes. All load conditions maintain the preset 10-minute total
cycle.
Floating control keeps the control point near the set-point at any load level, and can
only be used on systems with minimal lag between the controlled medium and the
control sensor. Floating control is used primarily for discharge control systems
where the sensor is immediately downstream from the coil, damper, or device that it
10
controls. An example of floating control is the regulation of static pressure in a duct
(Fig. 7).
In a typical application, the control point moves in and out of the dead band,
crossing the switch differential (Fig. 8). A drop in static pressure below the controller
set-point causes the actuator to drive the damper toward open. The narrow
differential of the controller stops the actuator after it has moved a short distance.
The damper remains in this position until the static pressure further decreases,
causing the actuator to drive the damper further open. On a rise in static pressure
above the set-point, the reverse occurs. Thus, the control point can float between
open and closed limits and the actuator does not move. When the control point
moves out of the dead band, the controller moves the actuator toward open or
closed until the control point moves into the dead band again.
11
2.4.3 Proportional control
Proportional control proportions the output capacity of the equipment (e.g., the
percent a valve is open or closed) to match the heating or cooling load on the
building, unlike two-position control in which the mechanical equipment is either full
on or full off. In this way, proportional control achieves the desired heat addition or
removal rate.
In a chilled water cooling system, for example (Fig. 9), the sensor is placed in the
discharge air. The sensor measures the air temperature and sends a signal to the
controller. If a correction is required, the controller calculates the change and sends
a new signal to the valve actuator. The actuator repositions the valve to change the
water flow in the coil, and thus the discharge temperature.
The final control element is seldom in the middle of its range because of the linear
relationship between the position of the final control element and the value of the
controlled variable. In proportional control systems, the set-point is typically the
middle of the throttling range, so there is usually an offset between control point
and set-point.
12
Figure 10 - Final Control Element Position as a Function of the Control Point (Cooling
system)
An example of offset would be the proportional control of a chilled water coil used
to cool a space. When the cooling load is 50 percent, the controller is in the middle
of its throttling range, the properly sized coil valve is half-open, and there is no offset.
As the outdoor temperature increases, the room temperature rises and more cooling
is required to maintain the space temperature. The coil valve must open wider to
deliver the required cooling and remain in that position as long as the increased
requirement exists. Because the position of the final control element is proportional
to the amount of deviation, the temperature must deviate from the set-point and
sustain that deviation to open the coil valve as far as required.
The throttling range is the amount of change in the controlled variable required for
the controller to move the controlled device through its full operating range. The
amount of change is expressed in degrees Celsius for temperature, in percentages
for relative humidity, and in kPa for pressure. For some controllers, throttling range
is referred to as “proportional band”. Proportional band is throttling range
expressed as a percentage of the controller sensor span:
Throttling Range
Proportional Band = × 100%
Sensor Span
“Gain” is a term often used in industrial control systems for the change in the
controlled variable. Gain is the reciprocal of proportional band:
100
Gain =
Proportional Band
The output of the controller is proportional to the deviation of the control point
from set-point. A proportional controller can be mathematically described by:
13
V = KE + M
where:
V = output signal;
K = proportionality constant (gain);
E = deviation (control point – set-point)
M = value of the output when the deviation is zero (Usually the
output value at 50 percent or the middle of the output range.)
In the proportional-integral (PI) control mode, reset of the control point is automatic.
PI control, also called “proportional-plus-reset” control, virtually eliminates offset
and makes the proportional band nearly invisible. As soon as the controlled variable
deviates above or below the set-point and offset develops, the proportional band
gradually and automatically shifts, and the variable is brought back to the set-point.
The major difference between proportional and PI control is that proportional
control is limited to a single final control element position for each value of the
controlled variable. PI control changes the final control element position to
accommodate load changes while keeping the control point at or very near the set-
point.
Reset time is proportional to the deviation of the controlled variable. Reset is also
proportional to the duration of the deviation. Reset accumulates as long as there is
offset, but ceases as soon as the controlled variable returns to the set-point.
With the PI controller, therefore, the position of the final control element depends
not only upon the location of the controlled variable within the proportional band
(proportional band adjustment) but also upon the duration and magnitude of the
deviation of the controlled variable from the set-point (reset time adjustment).
Under steady state conditions, the control point and set-point are the same for any
load conditions.
K ∫ Edt
V = KE + +M
T1
14
where:
V = output signal
K = proportionality constant (gain)
E = deviation (control point -setpoint)
Tl = reset time
K/Tl = reset gain
dt = differential of time (increment in time)
M = value of the output when the deviation is zero
If the control point moves away from the set-point, the derivative function outputs a
corrective action to bring the control point back more quickly than through integral
action alone. If the control point moves toward the set-point, the derivative
15
function reduces the corrective action to slow down the approach to set-point,
which reduces the possibility of overshoot.
The derivative portion of PID control is expressed in the following formula. Note
that only a change in the magnitude of the deviation can affect the output signal.
dE
V = KTD
dt
where:
V = output signal
K = proportionality constant (gain)
TD = rate time (time interval by which the derivative advances the
effect of proportional action)
KTD = rate gain constant
dE/dt = derivative of the deviation with respect to time (error signal
rate of change)
K ∫ Edt dE
V = KE + + KTD +M
T1 dt
V = output signal
K = proportionality constant (gain)
E = deviation (control point - setpoint)
Tl = reset time
K/T1 = reset gain
dt = differential of time (increment in time)
16
TD = rate time (time interval by which the derivative advances the
effect of proportional action)
KTD = rate gain constant
dE/dt = derivative of the deviation with respect to time (error signal
rate of change)
M = value of the output when the deviation is zero
The graphs in Figures 11, 12, and 13 show the effects of all three modes on the
controlled variable at system start-up. With proportional control (Fig. 11), the
output is a function of the deviation of the controlled variable from the set-point. As
the control point stabilizes, offset occurs. With the addition of integral control (Fig.
12), the control point returns to set-point over a period of time with some degree of
overshoot. The significant difference is the elimination of offset after the system has
stabilized. Figure 13 shows that adding the derivative element reduces overshoot
and decreases response time.
17
Figure 12 - Proportional-Integral Control
19
2.4.8 Control application guidelines
The following are considerations when determining control requirements:
• The degree of accuracy required and the amount of offset, if any, that is
acceptable.
• The type of load changes expected, including their size, rate, frequency, and
duration.
• The system process characteristics, such as time constants, number of time lag
elements, and reaction rate.
Each control mode is applicable to processes having certain combinations of the basic
characteristics. The simplest mode of control that meets application requirements is
the best mode to use, both for economy and for best results. Using a control mode
that is too complicated for the application may result in poor rather than good control.
Conversely, using a control mode that is too basic for requirements can make
adequate control impossible. Table 1 lists typical control applications and
recommended control modes.
Space Temperature P
Chiller Discharge PI
Temperature
20
(a) Fresh air demand control with CO2 sensor
(b) Example 2: Variable Air Volume (VAV) System Static Pressure Reset Control
Figure 16 –Variable Air Volume (VAV) System Static Pressure Reset Control (Ref. 3)
Air volume flowrate required by each zone will be different depending on the usage and
number of people and the optimum flowrate to each zone is controlled individually by VAV
box.
When the flowrate supplied by AHU fan is larger than the total flowrate required by the
zones, static pressure inside the duct will rise accordingly.
21
Air duct static pressure sensor is used to measure supply air duct pressure from the cooling
coil. The air duct pressure will be compared with the pressure set-point.
Error = value of set point – measured value
The error will be used to control the frequency of the motor driven by the Variable speed
drive (VSD). The supply air flowrate of AHU will be reduced to match the required static
pressure. Then the flowrate supply by AHU fan will be equal to the total flowrate required
by the zones.
Useful References:
1. Guidelines on application of Central Control and Monitoring Systems, Energy Efficiency
Office, EMSD
2. https://www.emsd.gov.hk/en/energy_efficiency/energy_management/publications/app
lication_guide_to_variable_speed_drives_vsd/index.html
3. Variable Air Volume (VAV) System Static Pressure Reset Control, Energy Efficiency Office,
EMSD
- END -