18128
INSTALLATION OF SPRINKLER SYSTEMS
30" 045°
GE.
venous be
@mmio3 mm)
thon
(@mmio 3mm) (Smmom)
‘Open Root Butt Weld
AT5.3:1.1 Standardized groove specifications pertain 0 the
‘grooved couplings that comply with and the groove dimensions
described in ANSI/UL. 213, Rubber Gasketed Fittings for Fie
Protection Service. The standard dimensions are specified in
ANSI/UL 213,
AL54. The fire hazard of the brazing and soldering processes
should be suitably safeguarded.
AT.5.4.5. Soldering fluxes manufictured to the specifications
required by Table 7.3.1.1 ate unlikely to cause damage to the
seats of sprinklers. When brazing flux is used, it must be of a
{ype not likely wo damage the seats of sprinklers,
AZZ. The intent of the 5 minute allowance is to aecommo-
date fluctuations in water flow in large systems.
7.7.2 Where buildings are equipped with fie alarm systems,
the requirements of the applicable fire alarm code should
prevail. Iti the intent ofthis section to also apply to electrically
Activated local alarm bells, The 100 second allowance i to mect
the requirement of 90 second plus 10 second delay in respond-
ing to the signal from the initiating device (.. flow or pressure
swsiteh)-
AB.L1.2 Pressure gauges installed on both sides of a check
valve are necessary for several reasons. They can quickly ind
cate an abnormal condition such as closed valve of an inoper=
able check vale. If the pressure on the downstream side of a
check valve is Tess than the pressure on the upstream side,
cither the pressure gitiges are faulty or the check valve is inop”
erable, Ifthe pressure on the upstream side of a cheek valve is
less than the pressure on the downstream side, the pressure is
‘rapped indicating a higher than normal pressure, This ervone-
fous pressure will then be part ofa main drain test. fa pressure
gauge is installed only on the downstream side of the check
salve a pressure would be indicated but the pressure on the
"upstream side could be 0.0 psi indicating a severe problem,
AB2_A diy pipe satem should be installed only where heat b
not adequate to prevent freering of water in all parts of, oF in
sections of, the system. Dry pipe systems should be converted to
wet pipe ‘systems when they become unnecessary because
adeqiate heat is provided. Sprinklers should not be shut off in
cold weather
Where two or more dry pipe valves are used, systems prefera-
bly should be divided horizontally to. prevent simultaneous
‘operation of more than one system and the resultant increased
time delay in filling systems and discharging water and to
prevent receipt of more than one waterflow alarm signal
2022 Eston
ein. nom > rm
0° 4s"
SSS
ain Mein
(mmio2mm)
Butt Weld with Backing Ring
Where adequate heat is present in sections of the dy pipe
system, consideration should be given to dividing the system
into a separate wet pipe system and dry pipe system. Minimized
"use of dy pipe sistems is desirable where speed of operation is
of particular concern,
A8.2.2.2@) Invallation imitations of sted dry pendent
sprinklers can vary with different products. Limitations should
de included in. product installation instruetions w warn the
user of the potential accumulation of water, scale, and sedi-
‘ment from collecting a the sprinkler.
A8.2.8 The capacities of the various sizes of pipe given in
Table A823 are for convenience in calculating the capacity of
system,
8.2.3.1 The 60-second limit does not apply to dry systems
with capacities of 500 gal (1900 L) or less, nor to dry systems
With capacities of 750 gal (2850 L) or less if equipped with a
quickopening device.
A827 See Figure A82
A8.2.5. The dry pipe valve should be located in an accessible
place near the sprinkler system it controls. Where exposed t0
Cold, the dy pipe valve should be located in a valve toom or
enclosure of adequate size to properly service equipment.
8.2.5.1 The dry pipe valve and supply piping should be in
fan area maintained at or above 40°F (4°C), Icis the intent of
the committee to protect the valves from freezing. The occa-
sional exposure of valves to short exposures of ait temperatures
below 40°F (4°C) that would not cause the valves to freeze does
not justify the construction of a valve room,
A8.2.6.3 The compressor should draw its air supply from
Within the operating criteria allowed by the manufacturer of
the compressor. Air piping should not be attached to the intake
‘of the compressor unless acceptable to the compressor man
facturer and installed in accordance with 882.7, Damage, air
reduction, or reduced life expectancy can result if guidelines
are not followed,
A8.2.6.3.2 When a single compressor serves multiple dry pipe
sstems, the 30-minute fill time is based on the single largest
system,
A8.2.64.1 ‘The connection from an ait compressor to the dry
pipe vale should be of a type recommended by the manufac-
turer and approved by the authority having jurisdiction, taking
into consideration the pressures, temperatures, and vibrations
that the connection and adjacent equipment will endute, Flexi