Professional Documents
Culture Documents
FM220-12(12V220AH)
Specification
Nominal Voltage 12V
Nominal Capacity(10HR) 220.0AH
Length 522 3mm (20.55 inches)
Width 240 3mm (9.45 inches)
Dimensions
Container Height 218 3mm (8.58 inches)
Total Height (with Terminal) 224 3mm (8.81 inches)
Approx Weight Approx 53.0 kg
Terminal T11
Container Material ABS
208.0 AH/10.4A (20hr ,1.80V/cell,250 C/770F)
200.0 AH/20.0A Applications
0 0
(10hr,1.80V/cell,25 C/77 F)
Rated Capacity 172.0 AH/34.4A (5hr,1.75V/cell,25 C/770 F)
0
All purpose
156.0 AH/52.0A (3hr,1.75V/cell,250 C/770 F)
122.0 AH/122.0A
0 0
(1hr,1.60V/cell,25 C/77 F) Uninterruptable Power Supply (UPS)
Electric Power System (EPS)
Max. Discharge Current 2000A (5s)
Internal Resistance Emergency backup power supply
Approx 2.7mΩ
Emergency light
Discharge : -15 500C (5 1220F)
Operating Temp.Range Charge : 0 40 C (32 104 F)
0 0
Railway signal
Storage : -15 40 C (5 104 0F)
0
Aircraft signal
Nominal Operating Temp. Range 25 30C (77 50F ) Alarm and security system
Initial Charging Current less than 60.0A.Voltage Electronic apparatus and equipment
Cycle Use
14.4V~15.0V at 25 0 C(77 0F)Temp. Coefficient -30mV/ 0C Communication power supply
No limit on Initial Charging Current Voltage DC power supply
Standby Use
13.5V~13.8V at 25 0 C(77 0F)Temp. Coefficient -20mV/ 0C Auto control system
40 C (104 F)
o o
103%
Capacity affected by
25 C ( 77 F)
o o
100%
Temperature VdS
0 C ( 32 F)
o o
86%
FM series batteries may be stored for up to 6 months
Self Discharge 0 0
at 25 C(77 F) and then a freshening charge is required.
9
t est ed
T11 Terminal
Unit: mm [inches]
20 [0.787]
M8 [0.315]
6 [0.236]
224 2
218 2
140 2
240 2
_
_
_
_
522 2
12.0
0.25
120 15.0
110 Charged Volume
11.0
Terminal Voltage(V)
0.20
100
0.1C 0.0525C 14.0
0.205C 90 Charge Voltage
10.0 0.4C 80 (Constant 2.25v/cell)
0.15
70 13.0
1C 0.6C
9.0 60
After 50% Discharge
50 0.10
12.0
40 After 100% Discharge
8.0 30
2C 0.05 11.0
20
10 Charging Current
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20
0 0
Min H
0 4 8 12 16 20 24 28 32 36 40
Discharge Time Charging Time(hours)
Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life
120 10
0.1CA 8
100 0.17CA 6
5
0.25CA 4
Charging voltage :
%
80 2.25V/cell
3
Life expectancy(year)
Capacity
60 2
40
1
20
0.5
20 30 40 50 0
C
-20 -10 0 10 20 30 40 50 60 68 86 104 122 O
F
0 Battery temperature
Temperature( C)
120 60
B
0
400C 30 C
100 40
80 C
20
Capcity(%)
60
100% 50% 30% 0
DOD DOD DOD 2 4 6 8 10 12
40
Ambient Termperature: Storage Time(Months)
25oC (77 oF)
20 No supplementary charge required
A (Carry out supplementary charge before use if 100% capacity is required.)
0 Supplementary charge required before use.Optional charging way as below:
0 200 400 600 800 1000 1200 1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
B 2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.
Number of Cycles 3.Charged for 8~10hours at limted current 0.05CA .
Contact US