Professional Documents
Culture Documents
VA2-YR07-P0ZEN-140001 - Design Criteria For Electrical - Rev.F
VA2-YR07-P0ZEN-140001 - Design Criteria For Electrical - Rev.F
Owner’s Engineer
Contractor
Sub-Supplier
Project
Title
RECORD OF REVISION
Rev. Date Page Affected Description of Revision
Rev.F 2 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
CONTENTS
1. GENERAL ............................................................................................................................5
1.1. Introduction ..........................................................................................................................5
1.2. Environmental Condition ....................................................................................................5
1.3. Noise Level ............................................................................................................................5
1.4. Code and Standards .............................................................................................................6
1.5. Electrical Source ...................................................................................................................6
1.6. Motor Rating ........................................................................................................................7
1.7. Total Harmonic Distortion ..................................................................................................7
1.8. Frequency Variation ............................................................................................................7
1.9. Engineering Units .................................................................................................................8
1.10. Symbol and Language ..........................................................................................................8
1.11. Design Temperature .............................................................................................................8
1.12. Protection degree of Electrical Equipment ........................................................................8
1.13. Scope ......................................................................................................................................9
2. ELECTRICAL SYSTEM ..................................................................................................10
2.1. General ................................................................................................................................10
2.2. Main Power System ............................................................................................................10
2.2.1. General ................................................................................................................................10
2.3. Auxiliary Power System.....................................................................................................11
2.4. Emergency Power System..................................................................................................11
3. DESCRIPTION OF ELECTRICAL EQUIPMENT AND SYSTEM ............................11
3.1. 500kV AIS(AIR INSULATED SUBSTATION) ..............................................................11
3.1.1. General ................................................................................................................................11
3.1.2. Main Electrical Equipment ...............................................................................................12
3.1.3. Control and Monitoring.....................................................................................................12
3.2. Generator Step Up Transformer (GSUT) ........................................................................13
3.2.1. General ................................................................................................................................13
3.2.2. Design Requirements .........................................................................................................13
3.2.3. Technical Information .......................................................................................................13
3.3. Unit Auxiliary Transformer (UAT) ..................................................................................14
3.3.1. General ................................................................................................................................14
3.3.2. Design Requirements .........................................................................................................14
3.3.3. Technical Information .......................................................................................................14
Rev.F 3 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Rev.F 4 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
1. GENERAL
1.1. Introduction
This design criteria document is to define the Electrical Basis of Design for Vung Ang Ⅱ Thermal
Power Plant project to be located at Ha Tinh City, Vietnam.
The electrical system and equipment to be covered in this document shall include items related to power
generation for the main plant as well as their auxiliary system. The ratings and capacities to be
considered in this report for various systems shall be generally based on information / data furnished by
manufacturers and in house data bank for similar units. Detailed engineering work shall be carried out
in accordance with basic concepts developed in this design criteria and the same shall be considered as
the basis for drawing the detail equipment specification.
An overview of the electrical auxiliary power distribution system is shown in the Electrical Key Single
Line Diagram. (DWG No. VA2-YU02-P0ZEN-145001).
Rev.F 5 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Standard No Description.
IEEE C37.23 Guide for metal enclosed bus and calculating loss in isolated phase bus
BS 159 Specification for High Voltage Busbars abd Busbar Connections
IEC 60529 Degree of protection provided by enclosure(IP-code)
IEC60076 Part 1~3 Power Transformers
IEC60726 Dry Type Power Transformers
IEC 62271-1 Common clauses for high-voltage switchgear and controlgear standards
IEC 62271-100 High-voltage alternating current circuit-breakers
IEC 62271-102 High-voltage alternating current disconnectors and earthing switches
IEC 62271-200 High-voltage switchgear - AC metal-enclosed switchgear and controlgear
IEEE Std. 485 IEEE Recommended Practice for Lead-acid Batteries
IIEC 62040 -1 General and Safety requirements for UPS
IEC 61869-1/2/5 Instrument transformers
IEC 60099-4 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems
Characteristic of indoor and outdoor post insulators for systems with nominal
IEC 60273
voltages greater than 1000 V
Low-voltage switchgear and controlgear assemblies - Part 2: Power switchgear and
IEC 61439-2
controlgear assemblies
IEC 60947-1/2 Low-voltage switchgear and controlgear - Part 1: General rules
Electricity metering equipment (a.c.) - General requirements, tests and test conditions
IEC 62052-11
- Part 11: Metering equipment
Electricity metering equipment (a.c.) - Particular Requirements - Part 22: Static
IEC 62053-22
meters for active energy (classes 0,2 S and 0,5 S)
IEC 60129 Alternating Current Disconnectors (Isolators) and Earthing
IEC 60137 Insulated bushings for alternating voltage above 1000 V
Star Point
System/Source Voltage variations
/ Neutral Treatment
Rev.F 6 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Star Point
System/Source Voltage variations
/ Neutral Treatment
500 KV Transmission system Excluded as per the Vietnamese National Grid Code
MV and LV auxiliary system As per IEC 61000-3-6 compatibility level
1.8. Frequency Variation
The frequency of the Grid System will be nominally 50 Hz. In normal operation mode, electricity
system frequency may fluctuate within ± 0.2 Hz compared with nominal frequency. Minimum time to
maintain operation of power plants connected to the transmission grid in proportion to frequency bands
of the electricity system is specified as following:
Rev.F 7 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
IPB IP 55 Outdoor
Rev.F 8 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
1.13. Scope
The scope of the electrical power distribution system is to provide necessary electrical equipment for
delivering the generated power and energy to EVN’s grid though a 500kV Air Insulated Switchyard,
auxiliary power for mechanical and electrical equipment, and provides adequate protective and control
features.
The electrical system will include follows :
- 500kV AIS Switchyard facililties (Extension to the existing Switchyard)
- 500kV Overhead line ACSR from GSUT to gantry tower at 500kV Switchyard
- Generator complete with all auxiliary systems
- Generator Step-up Transformers (GSUT)
- Isolated Phase Busducts (IPB)
- Generator Circuit Breakers (GCB)
- Unit Auxiliary Transformers (UAT)
- LV Transformers
- MV and LV Switchgears and Motor Control Centres
- Direct Current (DC) systems including batteries and Uninterrupted Power Supply (UPS) systems
- Emergency Diesel Generator Facilities (EDG)
- All electrical protection equipment and systems
- All tariff and operational metering equipment
- All necessary motors
- All cables, cable support and termination and identification systems
- Raceway system including cable tray, conduit and conduit fitting, cable tray support and conduit
support, fire stop and installation accessories
- MV/LV power and control cables, cable supports
- Overall grounding and earthing and bonding system
- Lightning protection systems
Rev.F 9 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
2. ELECTRICAL SYSTEM
2.1. General
The electrical plant configuration shall be designed with a view to ensure the reliability of the plant’s
service in all units of operation and of the export of generated electrical power. All components shall be
new and of an approved reliable design that shall facilitate maintenance and repair.
The equipment shall be suitable for operation at the elevation and under the design ambient air
temperatures at the site.
Electrical equipment shall be selected so that types and ratings are in line with mass-produced electrical
equipment, to be purchased easily at the free market, with long-term secured spare parts availability.
Electrical equipment shall be installed in filtered, ventilated buildings wherever possible. Equipment
called for outdoor installation shall be properly protected from harmful effects of environmental
conditions by providing sunshade, suitable enclosure or any suitable means if required.
Installation of electrical equipment in the gas or dust hazardous area shall be avoided as far as
practicable. However, in such a case that the installation of electrical equipment is inevitably required,
this electrical equipment shall be of an explosion-proof type that is adequate for the area classified
according to the applicable IEC standard.
The generator distribution system consisting of generators, generator step-up transformers, isolated
phase bus ducts, generator circuit breakers and 500 kV Switchyard will be designed with sufficient
capacity to carry maximum facility output.
Rev.F 10 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
In case of total loss of auxiliary power, or in situations when the utility system is out of service,
emergency diesel generator set and DC and UPS supply with batteries will provide for safe shut down,
maintenance of essential services and to enable an immediate restart of the Unit upon restoration of
external auxiliary power supply to the Plant.
Upon loss of aux power and emergency supply from emergency diesel generator set, then essential plant
services will be maintained by standby DC and/or UPS system.
Emergency diesel generator system will provide essential electrical AC supply to station auxiliaries to
ensure the safe shut-down during shut down both units simultaneously.(for example, the steam turbines
to turning gear operation)
Essential loads will be segregated from non-essential loads within the respective motor control centres.
Rev.F 11 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
a. Two (2) incoming connected to the generator step-up transformers of VA II Power Plant
b. Four (2) outgoings for connection to the overhead lines
The general structure of the 500kV AISsystem can be taken from single line diagram (DWG No. VA2-
YU02-P0AB-140003 _SINGLE LINE DIAGRAM - 500KV AIS).
Supervision/control, monitoring and information systems, and complete substation equipment and
systems shall comply with EVN system control concepts and procedures and shall be subject to the
approval of EVN as per Vietnam Grid Code.
Each switch bay shall have a local control cubicle. These shall accommodate all equipment for the local
control and supervision of the switch bay.
The switch bay shall be consisted of following components:
a. 500kV AIS including CTs, PTs, isolators, earth switches, instrumentation safety and monitoring.
b. Control panel and Protection Panel include SCADA panels, communication panels , workstations
other related equipment
c. Provision for interfacing with remote control system like DCS, SCADA, Telecommunication
for control, monitoring and metering.
The 500kV AIS shall be selected on the basis of rated current, nominal system voltage, design ambient
air temperature, fault current and voltage variation as indicated under design parameters.
Communication Protocol for SCADA system shall be in accordance with IEC 60870-5-101 for 500kV
AIS and IEC 60870-5-104 for Vung Ang 2 TPP based on SCADA agreement with EVN/NLDC. F
Rev.F 12 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Description Data
Standards IEC 60076
Type Oil-immersed, 2-winding, 3-phase
Rating MVA Rating (*)
450 / 600 / 750MVA at 50ºC
(to be confirmed by calculation)
Rated voltage (HV/LV) 500 kV / 23.5kV
Connections (Primary-Secondary) Wye-Delta, YNd11, Solidly grounded at HV neutral side
Rated frequency 50 Hz
Type of Cooling ONAN / ONAF / ODAF
Taps for on load operation (OLTC) on the
±12 x 0.833% taps on HV side
high-voltage winding including AVR
Impedance (at ODAF MVA base), after
16.5% at 750MVA(ODAF)
allowing for standard tolerances(*)
Rated Winding Temperature Rise Hot Spot(68K), Winding(60K), Oil(50K)
(*)
Theses rating data shall be fixed based on the electrical system study results.
Generator step-up transformer will be equipped with the following main equipment :
- Bushing mounted ring type current transformers (BCT)
- Local Control Panel (cabinet)
Rev.F 13 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
3.3.1. General
The unit auxiliary transformer will provide the main auxiliary power supply to the unit MV switchgear.
The UAT will be electrically connected to a branch of IPB between the generator circuit breaker and the
generator transformer. Each Unit will have two (2) UATs of three-phase three-winding transformer
capable of supplying its associated Unit loads, and the station auxiliary load for both Units.
Description Data
Standards IEC 60076
Type Oil-immersed, 3-winding, 3-phase
Rating MVA Rating(*) H=69/90MVA/ X=38/50MVA/ Y=31/40MVA
(to be confirmed by calculation) (ONAN/ONAF) at 50ºC
Rated voltage (HV/LV) 23.5 kV / 11.5 kV / 11.5 kV
Connections (Primary-Secondary) Delta-Wye, Dyn1yn1, Resistance Grounded
Rated frequency 50 Hz
Type of Cooling ONAN / ONAF
Taps for on load operation (OLTC) on the
±8 x 1.25% taps on HV side
high-voltage winding including AVR
Z(H-X)=14.4%
Impedance (at ONAF MVA base), after
Z(H-Y)=18.0%
allowing for standard tolerances(*)
Z(X-Y)=32.4%
Rated Winding Temperature Rise Hot Spot(68K), Winding(55K), Oil(50K)
(*)
Theses rating data shall be fixed based on the electrical system study results.
The unit auxiliary transformer will be equipped with the following main equipment :
- Neutral grounding resistor(NGR) cubicle
- Bushing mounted ring type current transformers (BCT)
- Local Control Panel (cabinet)
Rev.F 14 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
LV transformers will be of indoor type, three-phase, two (2) winding cast resin dry type with AN
cooling system. Dry type transformer will be enclosed in sheet steel enclosure of at least IP 21 degree of
protection.
The high voltage rating is usually specified to be equal to the nominal voltage of the medium voltage
bus. The low voltage rating is specified to be equal to a nominal low voltage (420V) approximately 5%
above the voltage rating of the low voltage motors (400V).
The MV cables will be connected directly to the transformer MV terminals, the LV windings will be
connected to the busbar of the LV switchboard via flexible connectors. And the transformers are
adjacent to the LV switchboards.
LV transformer will be equipped with off circuit taps of ±2 x 2.5% on HV side.
Winding temperature measurements and alarm signals will be transferred to the DCS, so that the
transformers can be monitored from the control room.
The isolated phase bus duct system will be used to evacuate the electrical power from each generator.
IPB will form the interconnection between the generator, generator circuit breaker and generator step up
transformer. And the tee-off connections will be provided to feed the unit auxiliary transformers and
excitation transformer.
The IPB will be outdoors and enclosed type with weather-proof dust-proof housing to degree of
protection of IP 55. It will be naturally cooling type.
The rated continuous current of the main section will be calculated to match the generator output
current at power factor 0.85 and generator voltage at 95% rated value.
The temperature during rated continuous current flow will not exceed the limits given in ANSI C37.23,
105°C for main conductor, bus connections and 80°C for enclosure.
Rev.F 15 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
The main section will be designed to withstand for a period of one (1) second, the thermal and
mechanical effects of an external metallic three-phase short-circuit on the generator transformer or
generator terminals, within normal voltage range.
IPB will be supplied with the amount of clean and dry air from instrument air system and to ensure that
the IPB can work under positive pressure condition, and IPB Instrument Air pressure will be motoring
by DCS.
The generator will be connected to the generator step-up transformer via generator circuit breaker to the
500kV system. The generator circuit breaker will be used for normal service open & close operation for
synchronization.
3.7.1. General
The Medium Voltage (MV) 11 kV switchgears will be fed by the Unit auxiliary transformers and
distribute power to the MV motors and LV transformers.
Rev.F 16 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Rated symmetrical short-circuit level of 11kV switchgears is 40kA(*)/1sec limited((*); this value will be
finalized as per system study result). This system shall be resistance earthed to limit the ground fault
current to 300Amp for 10sec at UAT’s LV winding.
The UAT capacity will be designed to be capable to supplying the auxiliary power the other unit for
40% output, so the power feeding system MV switchgear will be as follows;
- MV switchgear for Unit loads : Will be provided with two (2) infeeds and one (1) bus coupler with
manual transfer function
- MV switchgear for Common loads : Will be provided with two (2) infeeds and one (1) bus coupler
with auto/manual transfer function by HSBT(High Speed Bus Transfer) system.
MV system will be configured as a high resistance earthed network via a NGR connected to the neutral
of the UAT. Integral earthing switches with fault making capacity will be provided for all incoming and
outgoing circuits. Each cubicle will be provided with an interior lamp and space heater.
Each MV switchgear group will have one (1) empty panel as spare. It is not required to equip each spare
cubicle with a breaker and protection relays but the cubicle will include the rails and racking
mechanism etc. such that a breaker can be added later if/when required. Any protection can be added
later if/when the cubicle is used and at that time the relays can be installed. The cubicle will be designed
so that protection can be added later (new relays can be added by cut-outs on the door at that time).
Each circuit will have local and remote control capability. The remote control will be through the DCS.
The control compartment is located in the front and at the top of the switchgear panel with the
protection relays, indication and control facilities accessible (visible) with the door closed.
All equipment will be routine and type tested according to IEC standards. The type tests will not be
repeated if type test certificates of identical or similar equipment are available.
Rev.F 17 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
The short circuit time duration for LV switchgear will be 50kA(*)/1sec limited((*); this value will be
finalized as per system study result).
Power feeding system of LV switchgear, motor control center (MCC) and sub- distribution boards will
be as follows :
- LV Switchgear for Unit loads : Will be provided with one (1) infeed
- LV Switchgear for Common loads : Will be provided with two (2) infeeds and one (1) bus coupler
with auto/manual transfer function
- LV MCC : Will be provided with one (1) infeed
- Distribution panel : Will be provided with one (1) infeed
In case of LV system for ash disposal area will be of single incoming configuration due to single power
supply by the Owner.
Each LV switchgear group will have one (1) spare feeder for different rating of outgoing feeder and
each LV MCC group will have ten (10) percent of spare feeder.
All equipment will be routine and type tested according to IEC standards. The type tests will not be
repeated if type test certificates of identical or similar equipment are available.
The closing and tripping devices and the closing, tripping and indication supply voltage(s) will be 220V
DC for the 400V switchgear and Motor Control Centre circuits, 110V AC for Motor Control Centre
contactor closing circuits can be used also if required.
The forms of internal separation for LV switchgear and MCC will be Form 3b and Form 1 will apply to
Distribution panels.
Battery
The battery will be of the valve regulated lead-acid type mounted in multi-tier stands and
accommodated in a room. The battery will support the DC and UPS loads for one (1) hour.
The battery size will be calculated in accordance with IEEE 485 IEEE Recommended Practice for
sizing Lead-Acid Batteries for Stationary Applications.
The connections between cells will be made using standard pre-manufactured interconnecting cables or
bars, and the connection between batteries and distribution board will be made using power cables and
via fuse boxes arranged outside the battery room.
Rev.F 18 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Battery Charger
The charger will be of the thyristor controlled automatic constant voltage type with current limit
facilities. The whole of the charging equipment and static inverter will be contained in a naturally or
forced ventilated cubicle.
Charger output voltage and output current will be displayed at the front of the equipment together with
operating mode selector and status indication.
Distribution board
The distribution board will be of the fixed type. The distribution panel will incorporate fuse switches or
miniature circuit breaker for outgoing circuits, double pole isolators for the incoming supply from the
battery and moulded case circuit breaker for battery charger incoming supply.
The electrical systems will be designed to facilitate remote control and monitoring facilities of the
electrical system through DCS operator’s workstation in the CCR. The DCS will be suitably interfaced
with the electrical system using hard wiring or communication to allow remote control/monitoring
including followings :
Transformer
Rev.F 19 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
MV Switchgear
LV Switchgear
• Breaker status/alarms/fault
Incomer Breakers on/off control
• Analogue for voltage, ampere
• Breaker status/alarms/fault
Breakers on/off control
Bus coupler • Analogue for voltage
Transfer control
• Transfer function status
• Breaker status/alarms/fault
Outgoing Feeder Breakers on/off control
• Analogue for ampere (90kW & above)
MCC
Rev.F 20 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
The protection system from generator to generator step-up transformer and UAT shall be arranged to
provide two independent, high performance and reliable systems with separately monitored DC supplies,
separate CT / VT cores, separate cables & trip / hand reset lock out relays to obtain 100% redundancy.
Associated trip relays of these two redundant systems shall be separate, having sufficient number of
Rev.F 21 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
contacts for all the functions. Each protection shall individually energize both trip coils of the circuit
breakers to be tripped
Function Description
21G Distance Protection
24G Over Excitation (V/Hz)
Function Description
87E Excitation Transformer Differential Protection
50/51E Excitation Transformer Overcurrent Protection
Rev.F 22 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Function Description
24 Overfluxing for GSUT
26WA/WT Winding Temperature High Alarm / Trip
26OA/OT Oil Temperature High Alarm / Trip
49GT Overload Protection
50/51 Over-Current Protection
50/51N Over-Current Protection for Earth Fault
59GB Bus Bar Earth Fault
60 Voltage Transformer Supervision
64REF Restricted Earth Fault
74 Trip Circuit Supervision
87GT Transformer Differential Protection
The dedicated mechanical relay which are equipped on the GSUT should be provided for the following
functions :
Function Description
63B Buchholtz Alarm
63P Pressure Relief Device Trip
63OP On Load Tap Changer Protection
63S Sudden Pressure
71H/L Oil Level High / Low Alarm
Function Description
24 Overfluxing for UAT
26WA/WT Winding Temperature High Alarm / Trip
26OA/OT Oil Temperature High Alarm / Trip
49UT Overload Protection
50/51 Over-Current
50/51N Earth Fault
64REF Restricted Earth Fault
74 Trip Circuit Supervision
87UT Transformer Differential Protection
The dedicated mechanical relay which are equipped on the UAT should be provided for the following
functions :
Function Description
63B Buchholtz Alarm
63P Pressure Relief Device Trip
63OP On Load Tap Changer Protection
Rev.F 23 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Function Description
63B Buchholtz Alarm
63S Sudden Pressure
71H/L Oil Level High / Low Alarm
MV Swictgear Protection
Function Description
For Incomer/Bus-tie
25 Synchro-Check
27 Under Voltage
50BF Breaker Failure
51 Inverse Time Over-Current for Phase Fault
51N Inverse Time Over-Current for Earth Fault
98 PT Fuse failure protection
11kV Motors
27M Under Voltage
46 Phase Unbalance
49 Thermal Overload
50 Phase Fault (short circuit)
50G Earth Fault through Core Balance CT
87M Differential Protection for Motor above 1000 KW
Stalling, Number of Starts per hour, Switching Surge Protection, Locked
Rotor Protection
Power Feeder
50/51 Over-Current Protection
50N/51N Over-Current Protection for Earth Fault
Transformer Feeder
50/51 Over-Current Protection
51N Inverse Time Over-Current for Earth Fault
Bus VT Panel
27 Bus Under Voltage
98 PT Fuse failure protection
LV Swictgear Protection
Numerical relay or static device shall be provided as the following functions.
The protection function of each protection relay e.g. incomer, bus-tie, motor, static feeder shall be
selected based on the coordination study to achieve the best protection level of the electrical system.
Function Description
For Incomer/Bus-tie
Rev.F 24 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Function Description
25 Synchronizing
27 Under Voltage
51 Inverse Time Over-Current for Phase Fault
51N Inverse Time Over-Current for Earth Fault
51G Winding Neutral Earth Fault (For LV Transformer)
26W Winding Temperature High (For LV Transformer)
Motor Feeder for LV Swichgear (above 90kW)
27M Under Voltage
46 Phase Unbalance
49 Thermal Overload
50 Phase Fault (Short Circuit)
50G/51G Earth Fault through Core Balance CT
Stalling, Number of Starts per hour, Switching Surge Protection, Locked
Rotor Protection
Non-Motor Feeder for LV Switchgear (above 200kW)
50 Phase Fault (Short Circuit)
51 Inverse Time Over-current for Phase Fault.
51N Inverse Time Over-current for Earth Fault.
Diesel Generator
Function Description
87G Generator Differential Protection
50/51G Generator Overcurrent Protection
64GN Stator Earth Fault Protection
Rev.F 25 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Function Description
46G Negative Phase Sequence
59G Generator Over Voltage
27G Generator Under Voltage
25 Synchronizing
60 Voltage Transformer Supervision
81O/U Over/Under Frequency Protection
40 Loss of field Protection
49 Thermal overload protection (Bearing/Winding)
32 Reverse Power
3.11.1. General
Emergency diesel generator (EDG) sets will be provided for emergency supplies for the safe shut-down
of the Plant. EDG will be automatically started up and connected to provide essential loads, in the event
of total power failure.
One (1) set of EDG for both unit will be provided for emergency safety shut-down of both units and
their auxiliary equipment.
The capacity of EDG set will be suitably sized for catering loads for safe shut-down of plant and 100% F
of emergency station auxiliary loads in the event of total black out.
Following start up, all other circuit breakers that supply the essential loads will automatically open. The
circuit breaker associated with the emergency generator will then be switched automatically so that it
can supply the essential loads without operator action. Following the restoration of the normal supply, it
will be manually changed over to the normal source of power supply. The EDG set will be controlled
either automatically on loss of AC supplies or manually from the local control panel. It may also be
controlled from the central control room via the DCS.
Each emergency diesel generator will be capable of operating in parallel with the main Plant supplies
for load testing and the contractor will provide synchronization facilities in appropriate locations for
both EDG testing and re-synchronization to the normal supply.
EDG will be provided with auto main failure (AMF) panel and it will comprise of AVR, protection &
metering equipment, indicating instruments and start / stop interlocking hardware.
The capacity of the emergency diesel generator Shall design with a margin of 10% for the maximum
calculated EDG load power among case 1, 2, and 3 as below.
Case1; Total load demand of all the essential load equipment omponents under Normal/Rated operation.
Case2; Maximum load demand in starting motor which have the maximum starting load.
Case3; Momentary Maximum load demand at any case.
Rev.F 26 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
MV and LV motors will have class F insulation with temperature rise limited to class B.
Motors of rating 30kW and above will be provided with space heaters, rated for 230V, 1ph, 50Hz.
Current transformers for differential protection for motors rating 1,000kW and above will be provided
with three (3) differential current transformers mounted over the neutral leads within the enclosure.
3.13. Generator
3.13.1. General
The generators shall be hydrogen-cooled type or air-cooled type, cylindrical rotor type of 50 Hz three
phase synchronous generator. Heat shall be transferred by heat exchangers from the hydrogen system to
the closed cooling water system.
The generator high voltage terminal casing shall be constructed for connection to isolated phase busduct
(IPB) type of bus system. The stator and rotor winding insulation materials shall be of class F.
The rating shall be based on class B temperature rises. The rating shall be based on class B temperature
rises as specified in IEC 60034-1.
Rev.F 27 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
(a) Generators windings shall be double star connected with all phase and neutral terminals
brought out. The neutral of the generator shall be earthed through a grounding transformer,
the secondary of which is loaded with a resistor. The core design shall permit the flow of
earth current of at least 15 amperes for one second without any core damage.
(b) The generator shall be capable of delivering continuously its rated power at rated power factor
with voltage variations within ± 5% of the rated value and frequency variation is from ± 2% of
rated value of 50 Hz with the temperature rise not exceeding class B limits. It shall still be
capable of delivering the rated power when the voltage variation does not exceed 5% and the
frequency variation is from -5% to +3%.
(c) The generator shall be capable of operating continuously under unbalance load as per IEC
60034-1. It shall be capable of withstanding during any transient unsymmetrical short circuit
condition a negative sequence current (I2) expressed in per unit of rated current for a duration
of t seconds such that the value of I22 x t shall comply to IEC 60034-1. It shall be capable of
withstanding 3-phase short circuit at its terminals when operating at rated MVA and power
factor with 5% over voltage.
(d) For voltage wave form, the telephone interference factor (TIF) shall be within the limit
specified in IEC 60034-1.
(e) The generator shall be capable of withstanding the electrical, mechanical and thermal stresses
developed during fast re-closing of high voltage line, transmission line switching, faults, out
of step operation, out of phase synchronism and worst-case short circuit fault at generator
terminal etc.
(f) Generator coolers shall be designed such that the maximum temperature rise is not exceeding
Class B limits. The coolers shall be so designed that due to outage of one section, the
generator can still carry 80% of the rated load continuously without exceeding the temperature
limit specified for class F insulation.
Rev.F 28 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
mm2. Instrumentation cables will be of multi-pairs 500V grade, 1.0 mm2 rigid copper conductor, PVC
insulated, FRLS, and PVC sheathed type.
Fire resisting cable tested to the test temperature in IEC 60331 shall be used for following essential
circuits considering necessary to safely shut down the plant, emergency communication and audible
alarm circuits as belows :
- ST lubricating oil pump motor
- Turning gear motor
- Main Incoming Power Cable for Fire Alarm System
(Main Alarm Control Panel, Local Alarm Control Panel)
Cables will be installed either on cable trays or racking in ducts/conduits made of hot dipped galvanized
type, corrugated HDPE or PVC type fixed to steelwork or laid in concrete trenches or underground duct
banks.
For indoor locations, cables will be installed on cable tray, cable ladder, in cable conduit or in purpose
designed cable trenches.
For outdoor locations, cables will be installed in cable conduit, cable trenches or duct banks.
The MV power cables will be mounted on cable trays in one (1) layer stretched parallel or to be laid in
trefoil.
The LV power cables (single core) will be mounted on cable trays in one (1) layer stretched parallel or
to be laid in trefoil.
The LV power cables (multi core) will be mounted on cable trays in multi-layer stretched parallel.
Cable separation between bottom and bottom of trays will be at least 300 mm for access purposes and
the cable will be separated as below group :
- Power Cables > 1 kV (Ladder type cable tray)
- Power Cables < 1 kV (Ladder type cable tray)
- Control Cables (Ladder type cable tray)
- Instrument and Communication Cables include fire alarm / detection cables (Perforated or Solid
bottom type cable tray)
Rev.F 29 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Cable trays will be securely fastened to supporting steelwork and will be adequately supported to
prevent sagging.
Cable tray covers will be furnished and installed on cable trays for Coal Handling System. And cable
trays in following areas will be covered for top-tray (top layer) only :
- where cable trays for instrument cable
- where cable trays installed in outdoor area
- where cables on tray pass under or adjacent to pipe containing fluids (other than water)
- in areas which are subjected to fire hazards (i.e. rubbish accumulation, oil/grease areas, chemical
areas)
- where materials could accumulate onto cables in such quantities to cause a de-rating or chemical
attack of the cable (e.g. coal dust, ash etc.)
The height of cable tray will be 100mm or 150mm and standard cable tray widths used will be 150m,
300m, 450m and 600mm.
Rev.F 30 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Cable trays arranged one (1) above the other will have a minimum separation from bottom to bottom of
cable tray as per cable classification is as below :
- J(L1) : Analogue Signals and Communication Signals
- C(L2) : Control Cable, CT & PT Cables (for AC/DC)
- L(L3) : Low Voltage AC/DC Power Cables below 1000V
- M(L4) : Medium Voltage AC Power Cables above 1000V
Bottom layer of Cable Tray Group is M(L4). And the other cable tray layer will be installed upside of
M(L4) in sequential.
Based on the above mentioned category, the cables will be separated as follows :
Voltage Level Separation (Bottom to Bottom)
(J, C) and (L) 300 mm
(L) and (M) 300 mm
(M) and (J,C) 600 mm
Rev.F 31 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
An earthing system will be installed to support the DCS/PLC and coordinated control systems for the
steam turbine-generators in accordance with the manufacturer's recommendations.
The lightning protection system for the plant will be in accordance with NFPA 780.
A complete lightning protection system will be furnished for all exposed buildings, metal tanks, towers,
chimneys, and structures.
All buildings will be provided with lightning protection based on rotating sphere method.
Lighting System
The lighting system for the site will enable the identification and safe operation of the Plant and
movement of personnel. The lighting system will comply with IEC standards in addition to all statutory
and local authority regulations and requirements. Fluorescent lighting fixture wiill apply the LED type. F
Lighting in hazardous locations will be specifically designed for use in those areas. Light fittings and
installations in hazardous areas will comply with the relevant international standards for hazardous
areas. Roadway lighting and lighting in exposed positions will be controlled by photoelectric switches.
The circuitry will prevent inadvertent switching, due to electro-magnetic interference from lightning or
other causes. Lighting in other locations will be controlled by switches.
The lighting fixture for outdoor area such as ESP, ASH, Coal handling, etc will be applied industrial
type with water proof grade above.
The lighting illuminations will be designed in accordance with current international and Vietnamese
standards and will meet following requirements :
Illumination (Lux)
Area Fixture
Normal Emergency AC
Control Rooms Fluorescent 550 10 %
Office Rooms Fluorescent 550 10 %
Laboratories Fluorescent 550 10 %
Building corridors &
Fluorescent 100 10 %
Stairways
Rev.F 32 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
Rev.F 33 of 34
DESIGN CRITERIA FOR ELECTRICAL
VA2-YR07-P0ZEN-140001
resistance and chemical characteristics of the soil. The cathodic protection system will be mainly of the
impressed current type.
Project owner will provide external telephone lines up to Junction box in communication room of
Central Control Building. Further cabling and integration into IP-PABX is in scope of Contractor.
The office LAN system will be complete with servers, communications, networks, cabling and
infrastructure to provide for and support a system of personal computers (PC) for the staff.
Walkie-talkie System
Ten (10) sets of multiple channels (minimum of 8 channels) heavy duty commercial grade walkie-
talkies approved by the Government Entity will be provided for the Plant. The walkie-talkie system will
be capable of operating independently of all other communication systems. The battery charging
equipment will be included. The walkie-talkie system will operate at UHF band with frequency
modulation (FM). The Walkie-Talkie system will obtain license from the Government entity for the
owner to operate.
Closed circuit television system (CCTV) shall be provided for security purpose and operational purpose.
The security-purpose complete Closed Circuit Television system (CCTV) will be installed in the main
guard house and the camera will be installed at fence area which is accessible easily from outside at
interval of about 90m, access road and entry gate area for surveillance and monitoring of the Plant.
The operational-purpose CCTV shall monitor the operational area such as burner area, turbine hall, coal
unloading jetty, stacking of coal in coal yard, coal transfer tower, sea water FGD, water treatment plant,
transformers, switchyard and other machineries and equipment. This set of CCTV shall be installed in
the CCR.
Rev.F 34 of 34