Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations

Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)
TBEA Shengyand China ODFS- 150000 /
1 ATB-1 450 500/220 12 07.07.2009 20-10-21 Satisfactory -
500 TA
CGE Canada
2 ATB-2 450 500/220 36 10.08.1985 20-10-21 Satisfactory Due to Old Age
Auto Transformer Y-Y
500KV Grid Station CGE Canada
3 ATB-3 450 500/220 42 22.07.1979 11-08-21 Satisfactory Due to Old Age
NTDC Gatti, Faisalabad Auto Transformer Y-Y
CGE Canada
4 ATB-4 450 500/220 42 22.07.1979 20-10-21 Satisfactory Due to Old Age
Auto Transformer Y-Y
XIAN XD China
5 ATB-5 600 500/220 2.5 28.05.2019 20-05-20 Satisfactory -
ODFSZ-200000/500
6 ATB-1 600 500/220 Trafo- Union Germany NRPN 8157 30 5/6/1992 3/9/2020 Satisfactory Due to Old Age
7 ATB-2 600 500/220 Trafo- Union Germany NRPN 8157 30 10/23/1992 25/12/2019 Satisfactory Due to Old Age
8 ATB-3 600 500/220 Trafo- Union Germany NRPN 8157 30 9/18/1992 3/9/2020 Satisfactory Due to Old Age
9 ATB-4 600 500/220 TBEA China ODFES-200000/500 TA 12 2/21/2009 3/9/2020 Satisfactory -
10 T-5 160 220/132 Nei Peebles Scotland NRPN 8157 11 28/08/2010 4/9/2020 Satisfactory -
500-kV Grid Station
NTDC Sheikhupura Shengyang China OSFPSZ/160000/220
11 T-6 160 220/132 26 13/06/1995 4/9/2020 Satisfactory -
TA
12 T-7 160 220/132 Gingsu Haupeng China OSFZ10-160000/220 16 16/11/2006 4/9/2020 Satisfactory -

Hawker Seddley England ODFES-


13 T-8 160 220/132 4 12/12/2017 4/9/2020 Satisfactory -
200000/500 TA
14 T-1 160 220/132 Hyundai Bulgharia 16 01-05-2005 22/01/2021 Satisfactory -
220 KV Grid Station
15 T-2 250 220/132 SHAN DONG DACHI China 3 21-03-2019 23/01/2021 Satisfactory -
Ludewala Sargodha
16 T-3 250 220/132 XIAN XD T/F CO. China 4 28-05-2017 24/01/2021 Satisfactory -
17 T-1 250 220/132 China, Shandong Dachi 4 09-04-2019 15-09-2020 Satisfactory -
220kV Grid Station
Due to Old Age & Repaired installed at this
18 Samundri Road, T-2 160 220/132 England, NEI Peebles 6 19-08-2015 15-09-2020 Satisfactory
Grid Station Since "19-08-2015".
Faisalabad
19 T-3 160 220/132 China, Jiangsu Huapeng 15 20-12-2006 15-09-2020 Satisfactory -
XIAN XD, China OSF3Z10-
20 T-1 160 MVA 220/132 18 26.03.2004 30.06.2021 Satisfactory
160000/220

31 Years since manufacturing date 1990 and


10 years in service since date of energization
HAWKER SIDDELEY, LONDON at JWR Grid 27.08.2011 (This Transformer
21 T-2 160 MVA 220/132 10 27.08.2011 30.06.2021 Satisfactory
TTT85 was installed after repairing from
reclaimation workshop). DGA results are
satisfactory
220kV Grid Station
NTDC Jaranwala Road 25 Years since manufacturing date 1997 and
Faisalabad ABB, Spain 19.5 years in service since date of
22 T-3 160 MVA 220/132 20 05.03.2002 30.06.2021 Satisfactory
XEN460-950-ACZ energization at JWR Grid 05.03.2002. DGA
results are satisfactory
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
220kV Grid Station
Transformer
NTDC Jaranwala Road Transformer Transformer DGA Test Results
Faisalabad Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)

31 Years since manufacturing date 1990 and


9 years in service since date of energization at
ABB Transformatoren
23 T-4 160 MVA 220/132 10 28.02.2012 30.06.2021 Satisfactory JWR Grid 28.02.2012 (This Transformer was
PDOR 82730/245
installed after repairing from reclaimation
workshop). DGA results are satisfactory

24 T-1 250 220/132 TBEA China 7 18.11.2014 28.04.2021 Satisfactory -


25 T-2 250 220/132 Shandong Dachi China 2 15.01.2019 28.04.2021 Satisfactory -
220KV G/S T.T.Singh
26 T-3 160 220/132 ABB Spain 6 04.08.2015 28.04.2021 Satisfactory
27 T-4 250 220/132 LEEEC China 3 02.06.2018 28.04.2021 Satisfactory -
TBEA CHINA
28 T-1 250 220/132 7 26-06-2014 9/10/2020 Satisfactory -
(OSFSZ-250000/220TA)
220KV Grid Station JIANGSU HUAPENG CHINA (OSFZ10-
29 T-2 160 220/132 6 16-05-2015 9/10/2020 Satisfactory -
Bandala Fsd. 160000/220)
ABB
30 T-3 160 220/132 1 24-03-2020 Not performed yet -
(PDOR82730/245)
31 T-1 160 220/132 Hyundai Bulgaria 6 27-07-2015 13-08-2020 Satisfactory -
32 220kV Grid Station T-2 160 220/132 ABB Transformatoran 6 15-11-2015 23-10-2020 Satisfactory -
33 NTDC Nishatabad, T-3 160 220/132 Shenyang China 4 1/2/2017 13-08-2020 Satisfactory -
34 Faisalabad T-4 160 220/132 Hyundai Bulgaria 1 19-06-2020 23-10-2020 Satisfactory -
35 T-5 160 220/132 Hyundai Bulgaria 10 3/6/2011 13-08-2020 Satisfactory -
Iran
36 T-1 250 220/132 6 11.06.15 03-11-2021 Satisfactory
MLPN8354
Iran
37 T-2 250 220/132 7 21.07.14 02-08-2021 Satisfactory
220kV Band MLPN8354
Road Lahore Iran
38 T-3 250 220/132 6 14.04.15 02-08-2021 Satisfactory
MLPN8354
Iran
39 T-4 250 220/132 7 13.12.14 02-08-2021 Satisfactory
MLPN8354
AEG
40 T-1 160 220/132 23 12.05.98 24-02-2021 Satisfactory
MRSN8254
SIEMENS
41 T-2 160 220/132 1 30.07.20 24-02-2021 Satisfactory
220kV MLPN8254
Gakkhar China
42 T-3 160 220/132 13 19.07.08 24-02-2021 Satisfactory
OSFZ -160000 /220
China
43 T-4 160 220/132 13 28.06.08 24-02-2021 Satisfactory
OSFZ -160000 /220
Make: IranTransfo Iran, Type:MLPN
44 T-1 250 220/132 6 31-01-2020 26-11-2020 Satisfactory
8354
220kV
Make: ALSTOM, Turkey, Type:
45 Ghazi Road T-2 250 220/132 3 5/4/2019 26-11-2020 Satisfactory
T00683292
Lahore
Make: ALSTOM, Turkey, Type:
46 T-3 250 220/132 3 16-01-2019 26-11-2020 Satisfactory
T00683292
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)
HYOSUNG
47 T1 250 220/132 China 4 26.04.17 09-06-2021 Satisfactory
HNPD1029-1
HYOSUNG
48 220KV Gujrat T2 250 220/132 China 4 06.05.17 09-06-2021 Satisfactory
HNPD1029-1
HYOSUNG
49 T3 250 220/132 China 4 26.04.17 09-06-2021 Satisfactory
HNPD1029-1
50 T-1 160 220/132 Hawker Siddeley / TTT-85 31 16.07.10 10/9/2020 Satisfactory Old Age
51 220KV Kala T-2 160 220/132 Meidensha / FBORSDL 36 15.02.87 10/9/2020 Satisfactory Old Age
52 Shah Kaku T-3 160 220/132 TBEA / 0SZR 160000/220TH 15 12.10.06 10/9/2020 Satisfactory
53 T-4 160 220/132 Shenyang / OSZR-160000/220A 18 16.01.18 10/9/2020 Satisfactory
TBEA (China)
54 T-1 160 220/132 6.5 15.07.15 13-10-2020 Satisfactory -
220KV Type: OSZR - 160000/220T
Kassowal TBEA (China)
55 T-2 160 220/132 6.5 17.04.15 13-10-2020 Satisfactory -
Type: OSZR - 160000/220T
TBEA China
56 T-1 250 220/132 OSFSZ - 250000 10 23.02.11 28-06-2021 Awaited
/ 220TA The previou results (2019) showed the
values of carbon mono oxide ( CO) exeeding
TBEA China
220kV NKLP the limits . So it is necessary to continiosly
57 T-2 250 220/132 OSFSZ - 250000 12 13.07.09 28-06-2021 Awaited
Lahore monitor the degradation of insulation T/F
/ 220TA
through online DGA device to avert any
TBEA China equipment loss.
58 T-3 250 220/132 OSFSZ - 250000 12 24.05.09 28-06-2021 Awaited
/ 220TA
TBEA: China
59 T-1 250 220/132 7 3.07.14 16-10-2020 Satisfactory Test results are satisfactory.
Type: OSFSZ250000/220TA
220kV Okara
TBEA: China
60 T-2 250 220/132 5 19.08.17 16-10-2020 Satisfactory Test results are satisfactory.
Type: OSFSZ250000/220TA
TBEA (China)
61 T-1 250 220/132 11 01.02.10 26-10-2020 Unsatisfactory
OSFSZ-25000/220TA
Transformers are commissioned 10 years
220kV Ravi TBEA (China)
62 T-2 250 220/132 10 18.04.11 26-10-2020 Unsatisfactory before
Lahore OSFSZ-25000/220TA
and current DGA results are poor.
TBEA (China)
63 T-3 250 220/132 10 29.10.11 16-10-2020 Satisfactory
OSFSZ-25000/220TA

JIANGSU HUAPENG
Transformer
64 T-1 160 220/132 LTD PRC 2.5 30.04.2019 13-07-2020 Satisfactory With in Limit
OSFZ10-
160000/220

Shenyang Transformer Work


65 220KV T-2 160 220/132 OSFPSZ 7 1 14.05.2007 13-07-2020 Satisfactory With in Limit
Sarfraz Nagar 160000/220TA
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
220KV Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
Sarfraz Nagar (kV/kV)
JIANGSU
Carbon Monoxide (CO)
66 T-3 160 220/132 OSFZ10- 14.5 19.02.2010 13-07-2020 Un Satisfactory
Out of Limit
160000/220
JIANGSU
Carbon Monoxide (CO)
67 T-6 160 220/132 OSFZ10- 6.5 02.05.2015 13-07-2020 Un Satisfactory
Out of Limit
160000/220
TAIKAI CHINA
68 T-1 160 220/132 9 20.06.15 6/11/2021 Satisfactory -
OSFZ16 0000 / 220TA
220kV New TAIKAI CHINA
69 T-2 160 220/132 9 07.03.14 6/11/2021 Satisfactory -
Shalamar LHR OSFZ16 0000 / 220TA
TAIKAI CHINA
70 T-3 160 220/132 9 07.03.14 6/11/2021 Satisfactory -
OSFZ16 0000 / 220TA
AEG
71 T-1 160 220/132 ( TURKEY) 26 11.08.99 28-10-2021 Satisfactory Age Above 25 years
MRSN 8254
AEG
72 220kV Sialkot T-2 160 220/132 ( TURKEY) 26 11.08.99 28-10-2021 Satisfactory Age Above 25 years
MRSN 8254
AEG
73 T-3 160 220/132 ( TURKEY) 26 21.01.10 28-10-2021 Satisfactory Age Above 25 years
MRSN 8254

74 T-1 160 220/132 MR 3XM1802-170D-14271W 12 14.11.10 02-11-2020 Satisfactory -

220kV Wapda
75 T-2 160 220/132 MR 3XM1802-170D-14271W 12 14.11.10 16-08-2020 Satisfactory -
Town, Lahore
MR 3XM1802-
76 T-3 160 220/132 12 14.11.10 02-11-2020 Satisfactory -
170D-14271W
SPECO
77 T-1 750 500/220 (CHINA) 4 1/11/2017 22-02-2021 Satisfactory -
ODFSZ-250000/500
SPECO
500kV New
78 T-2 750 500/220 (CHINA) 4 1/11/2017 22-02-2021 Satisfactory -
Lahore (South)
ODFSZ-250000/500
SPECO
79 T-3 750 500/220 (CHINA) 2.5 10/4/2019 22-02-2021 Satisfactory -
ODFSZ-250000/500
SIEMENS NLPN 8357 + HLAK
80 T-1 600 500/220 12 11.04.09 3/11/2020 Satisfactory -
6144
SIEMENS NLPN 8357 + HLAK
81 T-2 600 500/220 12 12.04.09 3/11/2020 Satisfactory
6145
SIEMENS 1 ARP
82 T-4 160 220/132 12 14.04.09 3/11/2020 Satisfactory
160 000-245
500kV Nokhar
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)
500kV Nokhar SIEMENS 1 ARP
83 T-5 160 220/132 12 30.07.09 3/11/2020 Satisfactory
160 000-246
SIEMENS 1 ARP
84 T-6 160 220/132 12 30.07.09 3/11/2020 Satisfactory
160 000-247
Auto-
85 Transformer 200 500/220 --- 3/11/2020 Satisfactory
(Spare Unit)

DGA test result of year 2020 show


concentration of CO gas near borderline. Also
SIEMNES,
86 T-1 600 500/220 15 07.08.06 22-09-2020 Satisfactory concentration of acetylene in OLTC was near
NLPN8357 + HLAK
borderline. So it is recommended to install
asset health monitoring devices for ATB-1

DGA test result of year 2020 showed


concentration of CO gas to be near
SIEMNES, borderline. Also concentration of acetylene in
87 T-2 600 500/220 15 31.03.07 22-09-2020 Satisfactory
NLPN8357 + HLAK OLTC was slightly out of limit. So it is
recommended to install asset health
monitoring devices for ATB-2

SIEMENS,
88 T-9 600 500/220 1 22.07.2020 01-07-2020 Satisfactory
NDNP8157D
500kV
Yousafwala
Age. Unit has been in service for more
AEG
89 T-3 160 220/132 26 14.04.08 22-09-2020 Satisfactory than 26 years and it is recommeded to
MRSN8254
install online DGA Device for monitoring

MEIDENSHA, Age. Unit has been in service for more


90 T-4 160 220/132 JAPAN 34 23.05.87 22-09-2020 Satisfactory than 34 years and it is recommeded to
FPORSDL install online DGA Device for monitoring

JSHP-China
91 T-5 160 220/132 OSFZ10 - 13 25.12.08 22-09-2020 Satisfactory
1640 /220
JSHP-China
92 T-6 160 220/132 OSFZ10 - 12 05.09.09 22-09-2020 Satisfactory
1640 /220
1 500KV Rawat T-1 450 500/220 ELIN (Austria) 24.5 19.2.1997 26.01.2021 Satisfactory Age
2 T-2 450 500/220 ELIN (Austria) 24.5 9.6.1997 26.01.2021 Satisfactory Age
R&Y phase:
3 T-3 450 500/220 TBEA (China) 15 05.1.2007 26.01.2021 Satisfactory -
B phase: 03.03.2021
4 T-4 750 500/220 HYOSUNG (China) 2.5 05.04.2019 26.01.2021 Satisfactory -
5 T-5 250 220/132 TBEA (China) 8.5 03.05.2013 03.03.2021 Satisfactory -
6 T-6 250 220/132 TBEA (China) 4 01.11.2017 26.01.2021 Satisfactory -
500KV Rawat

Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations


Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)
7 T-7 250 220/132 TBEA China 10.5 21.04.2011 03.03.2021 Satisfactory -
8 T-8 250 220/132 NEE Pebbles Installation work of 220/132KV, 250MVA auto transformer is under progress.
9 220KV University, Isd T-1 250 220/132 TBEA (CHINA) 12 13.01.2010 17.02.2021 Satisfactory -
10 T-2 250 220/132 TBEA (CHINA) 9.5 04.5.2012 17.02.2021 Satisfactory -
11 220KV Sangjani T-1 160 220/132 AEG(W.Germany) 23 17.12.1998 19.05.2021 Satisfactory Age
12 T-2 160 220/132 AEG(W.Germany) 23 17.12.1998 19.05.2021 Satisfactory Age
13 T-3 160 220/132 Jiangsu Haupeng China 15 26.12.2006 19.05.2021 Satisfactory -
14 T-4 160 220/132 Jiangsu Haupeng China 4 10.09.2017 19.05.2021 Satisfactory -
15 220KV Burhan T1 250 220/132 IRAN 5 10.01.2017 22.01.2021 Satisfactory -
16 T2 250 220/132 IRAN 6 04.09.2015 22.01.2021 Satisfactory -
17 T3 250 220/132 IRAN 6.5 27.02.2015 22.01.2021 Satisfactory -
18 T4 250 220/132 LEEEC China 4 29.09.2017 05.10.2021 Satisfactory -
19 220KV Mansehra T-1 250 220/132 Chint (China) 3.5 04.04.2018 26.08.2021 Satisfactory -
20 T-2 250 220/132 Chint (China) 3.5 02.05.2018 26.08.2021 Satisfactory -
1 T-1 450 500/220 kV T/UNION 31 08.12.1995 3.5.2021 Satisfactory -
2 T-2 450 500/220 kV T/UNION 31 28.2.1996 3.5.2021 Satisfactory -
3 T-3 450 500/220 kV CHINA (Xianxd) 13 06.6.2012 3.5.2021 Satisfactory -
4 T-5 250 220/132 kV Transfo Iran 8 16.10.2015 3.5.2021 Satisfactory -
500kV Peshawar
5 T-6 250 220/132 kV Xian (China) 4 24.05.2017 3.5.2021 Satisfactory -
6 T-7 250 220/132 kV LEEEC (China) 4 31.08.2017 3.5.2021 Satisfactory -
7 T-8 250 220/132 kV Transfo Iran 8 17.03.2014 3.5.2021 Satisfactory -
8 T-10 20/26 132/11 kV Electroputer (Romania) 32 04.7.2015 3.5.2021 Satisfactory -
9 T-1 160 220/132 CHINA 26 25-9-1995 23-09-2020 Satisfactory -
10 220kV Daudkhel T-2 160 220/132 CHINA 26 25-9-1995 23-09-2020 Satisfactory -
11 T-3 10/13 132/11.0 SIEMENS (Pak) 26 25-9-1995 23-09-2020 Satisfactory -
12 T-1 250 220/132 SHANDONG (CHINA) 2 18.02.2019 11/10/2021 Satisfactory -
220kV D.I.Khan
13 T-2 250 220/132 SHANDONG (CHINA) 2 18.02.2019 11/10/2021 Satisfactory -
14 T-1 160 220/132 ABB 20 26.8.2004 03.04.2021 Satisfactory -
15 T-2 160 220/132 ABB 20 26.8.2004 03.04.2021 Satisfactory -
16 220KV Bannu T-5 250 220/132 Shandong Dachi China 3 01.04.2012 03.04.2021 Satisfactory -
17 T-3 26 132/11 ABB(Sweeden) 22 18-7-1999 03.04.2021 Satisfactory -
18 T-4 40 132/11 PEL 3 07.11.2015 03.04.2021 Satisfactory -
19 T-1 160 220/132 CHINA (Xian Elect:) 15 27.2.2006 29-01-2021 Satisfactory -
20 T-2 160 220/132 CHINA (Xian Elect:) 15 27.2.2006 29-01-2021 Satisfactory -
21 T-3 160 220/132 CHINA (Xian Elect:) 15 27.2.2006 29-01-2021 Satisfactory -
220kV Shahi Bagh
22 T-4 160 220/132 Fuji (Japan) 15 09.12.2015 29-01-2021 Satisfactory -
23 T-5 10/13 132/11 SIEMENS (PAK) 15 28.2.2006 29-01-2021 Satisfactory -
24 T-6 10/13 132/11 SIEMENS (PAK) 15 28.2.2006 29-01-2021 Satisfactory -
25 T-I 250 220/132 SHANDONG (CHINA) 3 19.04.2019 4/11/2020 Satisfactory -
26 220kV G/S Nowshera T-2 250 220/132 SHANDONG (CHINA) 3 19.04.2019 4/11/2020 Satisfactory -
27 T-4 10/13 132/11 PEL 3 19.04.2019 4/11/2020 Satisfactory -
28 T-1 250 220/132 LEEEC 3 16.09.2018 28.09.2020 Satisfactory -
29 220kV Chakdara T-2 250 220/132 LEEEC 3 19.03.2019 28.09.2020 Satisfactory -
30 T-3 10/13 132/11 PEL 3 18.09.2018 28.09.2020 Satisfactory -
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)
31 T-1 250 220/132 TBEA (China) 6 14.3.2012 9/21/2021 Satisfactory -
32 220KV Mardan T-2 250 220/132 JSHP (China) 6 28.11.2015 5/6/2021 Satisfactory -
33 T-3 250 220/132 JSHP (China) 6 24.10.2015 9/21/2021 Satisfactory -
Make: TBEA China
146 TR-2 600 525/231 Type: ODFSZ-200000/500T
4 04.02.2018 28.10.2019 Satisfactory -
Make: TBEA China
147 TR-3 600 525/231 Type: ODFSZ-200000/500T
4 04.02.2018 30.10.2019 Satisfactory -
500KV Rahm
Yar Khan Make: TBEA China
148 TR-5 250 220/132 Type: OSFSZ-250000/220TA
4 04.02.2018 30.10.2019 Satisfactory -
Make TBEA China
149 TR-6 250 220/132 Type: OSFSZ-250000/220TA
4 04.02.2018 31.10.2019 Satisfactory -
150 TR-1 450 525/231/22 Toshiba (Japan) 35 11/17/1986 25.08.2020 Satisfactory Due to Age
151 TR-2 450 525/231/22 Toshiba (Japan) 35 11/16/1986 25.08.2020 Satisfactory Due to Age
152 500kV G/S TR-3 160 220/132 China 11 6/14/2010 25.08.2020 Satisfactory Due to Highly Overload
153 NTDC Multan TR-4 160 220/132 China 11 6/14/2010 25.08.2020 Satisfactory Due to Highly Overload
154 TR-5 160 220/132 China 11 6/14/2010 25.08.2020 Satisfactory Due to Highly Overload
155 TR-6 6.3 132/11 Romania 11 22-09-2010 03.03.2021 Satisfactory To check Healthiness
DGA Test for all transformers is under
156 TR-1 600 500/220 XD China 7 26-07-2014 Not performed yet Nil process . Quotations are taken from Rawat
157 500KV TR-2 600 500/220 XD China 7 24-08-2014 6/7/2018 Satisfactory Lab and Noting for approval is sent vide
158 Dera Ghazi Khan TR-3 250 220/132 Jaingsu Haupeng China 7 28-08-2014 Not perfomred yet Nil UO No .19 Dated 05-11-21. Online DGA
159 TR-4 250 220/132 Jaingsu Haupeng China 7 28-08-2014 Not perfomred yet Nil devices are installed but still not
commissioned.
Make: ABB (Germany), Type: PEOR Online DGA device is not installed. DGA
160 TR-1 600 525/231 21 26.03.2000 14-06-2021 Satisfactory
137000/525 test is carried out from Rawat Lab

500KV Muzaffargarh For all three phases, concentration of CO


is out of tyical ranges (CO2/CO is 2.39,
Make: TBEA China, Type: ODFSZ-
161 TR-2 600 525/231 12 25.2.2009 14-06-2021 Unsatisfactory 2.45 & 2.82 resectively i.e., <3), which
200000/500TA
indicates sever overheating &
deterioration of cellulose insulation
162 T1 250 220/132 Iran Transfo, Iran 3.75 15-02-2018 Scheduled - DGA Test Case under process.
220kV Lal Sohanra
163 T4 10/13 132/11.5 PEL Pakistan 3.75 15-02-2018 Scheduled - DGA Test Case under process.
TBEA (China) TYPE OSZR-
164 T1 160 220/132 13 30-06-2008 09-04-2019 Satisfactory
220KV Grid Station 160000/220TH 3 PHASE WINDING
NTDC Muzaffargarh TBEA (China) TYPE OSZR-
165 T2 160 220/132 13 30-06-2008 14-05-2020 Unsatisfactory Due to Unsatisfactory DGA Result of T-2
160000/220TH 3 PHASE WINDING
De-hydration of the tap changer oil will
Unsatisfactory (tap
166 T-1 160 220/132 Hyndai 16 6/4/2005 6/29/2021 be conducted in coming shutdown i.e 20-
Changer)
220KV G/S NTDC 12-2021
167 Bahawalpur T-2 250 220/132 Iran Transfo 6 3/20/2015 6/29/2021 Satisfactory
168 T-3 250 220/132 Iran Transfo 7 11/30/2014 6/29/2021 Satisfactory
169 T-4 20/26 132/11.5 PEL 12 6/9/2021 6/29/2021 Satisfactory
Details of 500/220kV and 220/132kV Auto-Transformer at NTDC Grid Stations
Transformer
Transformer Transformer DGA Test Results
Transformer Voltage Commissioning Last DGA Test Date
Sr. # Grid Station Rating Transformer Make & Type Age Satisfactory/ Remarks/ Reason for poor DGA Result
Name Ratio (HV/LV) Date (dd-mm-yyyy)
(MVA) (Years) Unsatisfactory
(kV/kV)

Scanned copies of DGA results not


avilable as due to billing issue with
Date not provided
170 T-5 160 220/132 JIANGSU HUAPENG 14 Oct-19 Satisfactory PITESU lad they only verbally conveyed
by GENCO
DGA esults and did not provide hard
copies.
220KV NGPS Multan
Scanned copies of DGA results not
avilable as due to billing issue with
Date not provided
171 T-1 160 220/132 JIANGSU HUAPENG 14 Nov-19 Satisfactory PITESU lad they only verbally conveyed
by GENCO
DGA esults and did not provide hard
copies.
172 T-1 160 220/132 Make:AEG Type: MRSN 8254 23 3/29/1998 6/11/2021 Satisfactory
173 T-2 160 220/132 Make:AEG Type: MRSN 8254 23 3/29/1998 6/11/2021 Satisfactory
CO content was high, then furan analysis
Make: Shandong Dachi Type:OSFSZ-
174 T-3 250 220/132 2 3/27/2019 6/11/2021 Un-Satisfactory was carried out. In which regular
25000KVA/220kV
monitoring is recommended.
This Transformer
220kv Vehari is installed By
175 T-4 20/26 132/11.5 Make: Seimens type: TLPN 7452 26 6/11/2021 Satisfactory
MEPCO. Initial
DOM N/A
This Transformer
Make: ELtA Poland Type: TNARC is installed By Ethane content is high. Very Old TF. This
176 T-5 20/26 132/11.5 36 6/11/2021 Un-Satisfactory
26000/132PT MEPCO. Initial Transformer Is installed by MEPCO
DOM N/A
Analysis is DGA Devices (Hydrocal 1003) but said
177 220kV Grid Station T-1 160 220/132 Make:JSHP China Type:OSFZ10- 5 5-Oct-16 2/10/2021 recommended , then device are not calibrated so their results
178 Chishtian T-2 160 220/132 160000/220 5 5-Oct-16 2/10/2021 Furan Analysis of are not authentic . Therefore, said devices
the TF Oil Carried may be calibrated or New Devices may be
Details of Shunt Reactor
Shunt Reactor Capacity
Sr. # Grid Station
Name (MVAR)

1
2
500KV Grid Station
3 NTDC Gatti, Faisalabad
4
5
Details of Shunt Reactor at NTDC Grid Stations
Shunt Reactor
Commissioning Last DGA Test Date
Shunt Reactor Make & Type Age
Date (dd-mm-yyyy)
(Years)
DGA Test Results
Satisfactory/ Remarks/ Reason for poor DGA Result
Unsatisfactory