You are on page 1of 3

DIESEL GENERATOR POWERED BY CUMMINS WALT GLOBAL POWER

WGP-C85/S6
CUMMINS Series

Features:
• Rotate speed governor: Electrical governor
• Excitation system: Self excited
• Emergency stop switch
• 24V sealed for life maintenance free battery
• Lockable battery isolator switch
• Powder coated canopy (Only for Soundproofed sets)
• 50℃radiator
• Steel base frame with fork holes
• Vibration isolators between the engine/alternator and
base frame
• Dry type air filter
• Base fuel tank for daily running
Picture For Reference Only
• Drain points for fuel tank
• Operation Manual / Specifications

Dimensions & Weight  Genset Output Ratings 
Model  L  W  H  Genset Model  Prime Power  Standby Power 
WGP‐C85/S6  2410  1050  1320  WGP‐C85/S6  75kVA/60kW  85kVA/68kW 
Gross Weight 1150KG  Ratings at 0.8 power factor 

Notes: 
*Prime Power
Continuous duty operation,under variable load 24/24h‐10%
over load
Genset Ratings and Performance Data 
**Standby Power  Engine Model:  Cummins 4BTA3.9‐G2 
Standby duty, operation under variable load, without  Alternator Brand:  WALT 
over load;  Alternator Model:  WGP‐85KVA 
Control System:  Deep Sea 6120 
Standard Reference Conditions  Circuit Breaker Type:  3 Pole MCCB 
Note: Standard reference conditions 25°C (77°F) Air  Frequency & Phase:  60Hz & 3PH 
Inlet Temp, 100m(328 ft) A.S.L. 30% relative humidity.  Engine Speed: RPM  1800 
Fuel consumption data at full load with diesel fuel with  Fuel Tank Capacity: L 
specific gravity of 0.85 and conforming to BS2869: 1998,  WGP‐C85/S6  136 Liters 
Fuel Consumption: l/hr  (100% Load) 
− Prime Power  12.9 
‐Standby  Power  14.2 

www.waltpower.com 1/3
DIESEL GENERATOR POWERED BY CUMMINS WALT GLOBAL POWER

Engine Model: 4BTA3.9-G2 @74 kWm 1800 rpm


 

Engine Specifications 

Engine Brand  CUMMINS 
Engine Model  4BTA3.9‐G2 
Cylinder No.& Configuration  4 cylinder Diesel L type 
Working Mode  Turbocharged 
Bore x Stroke  102*120 mm 
Displacement  3.9 L 
Compression Ratio  17.3:1 
Rated Power  67KW 
Standby Power  74KW 
Rated Speed  1800 rpm 
Lubrication System  Splash Lubrication 
Lube Oil  CF class or SAE10W‐30,15w‐40 above 
Lube Oil Capacity  10.9 L 
Battery Capacity  VARTA 45A *2 
Battery Cold Cranking Ampere  380 CCA 
Fuel Type  Diesel:0#(Summer),‐   10#(Winter),‐35#(Cold) 
Fuel Consumption 25% load  4.2 L/H 
Fuel Consumption 50% load  7.1 L/H 
Fuel Consumption 75% load  10 L/H 
Fuel Consumption 100% load  12.9 L/H 

Alternator Model

Alternator Specifications   

Alternator Brand  WALT 
Alternator Model  WGP‐85KVA 
Frequency  60Hz 
Phase  3 
Power Factor  0.8 
Excitation system  Self Excited 
AVR Type  SX460 
Insulation Class  H 
Number of wires  12 
Protection  IP23 
Altitude  ≤ 1000 m 
Overspeed  2250 min‐1 
Air flow  0.10m3/s, 50 Hz ‐ 0.13m3/s, 60 Hz 
Voltage regulation (*)  ± 1 % 
Totale Harmonic distortion THD (**)  no load < 3% ‐ on load < 2% 
Waveform: NEMA = TIF (**)  < 50 

(*) Steady state. (**) Total harmonic distortion between phases, no‐load or on‐load (non‐distorting). 

www.waltpower.com 2/3
DIESEL GENERATOR POWERED BY CUMMINS WALT GLOBAL POWER

Genset Module   
AUTO START AND AUTO MAINS (UTILITY) FAILURE CONTROL MODULE 

➢ Large back‐lit icon LCD text display. 
➢ 3‐phase generator sensing and protection 
➢ 3‐phase generator and mains (utility) sensing. 
➢ 600 V ph‐ph nominal system compatibility. 
➢ Generator & load power monitoring (kW, kV A, kV Ar, pf). 
➢ Generator overload protection (kW). 
➢ Configurable inputs & outputs. 
➢ Fuel & crank outputs. 
➢ Magnetic pick‐up speed sensing. 
➢ Battery voltage monitoring. 
➢ Configurable event log (50). 
➢ DSE Configuration Suite PC Software. 
Engine speed protection, engine hours counter, engine pre‐heat, engine run‐time scheduler, engine idle control 

for start/stop. 

Diesel Generator Standard and Optional Features   
Engine  Alternator 
➢ 4‐stroke, water‐cooled diesel engine  ➢ Class H insulation 
➢ Standard air filter  ➢ IP23 Protection 
➢ Standard fuel filter  ➢ Automatic Voltage Regulator (AVR) 
➢ Standard oil filter  ➢ PMG excitation(optional) 
➢ Oil temperature sensor  ➢ Single bearing alternator 
➢ Low coolant level sensor  ➢ Double bearing (optional) 
➢ Radiator with blowing fan  ➢ Condensed heater (optional) 
➢ Industrial silence  ➢ IP41 Protection (optional) 
➢ Fuel water separator (optional)  ➢ Class F or class B temperature rise (optional) 
➢ Water jacket heater (optional)  ➢ Digital Voltage Regulator (optional) 

Electrical System  Packing 
➢Maintenance‐free and anti‐explosion battery  ➢Engine manual 
➢Standard breaker  ➢Alternator manual 
➢ABB or Schneider breaker (optional)  ➢Gensets operation and maintenance manual 
➢ATS (optional)  ➢Tool kit 
➢Battery charger 
➢GMS monitoring (optional) 

Base frame    Soundproof Canopy 
➢Forklift pockets  ➢Weatherproof & sound‐attenated canopy 
➢Pulling slots  ➢Sound‐absorbing   material 
➢Earth wire protection  ➢Lifting lug 
➢Built‐in anti vibration mountings  ➢Emergency stop button 
➢ Fuel outlet value  ➢Inside silencer 
➢Standard fuel tank 
➢Enlarged fuel tank (optional)  WALT GLOBAL POWER EQUIPMENT CO.,LTD 
➢Separated fuel tank (optional)  20th Fl., #888 North Sichuan Rd, Shanghai, China 
➢Bunded fuel tank (optional)  Tel:  0086‐18717996108 
E‐mail: sales@waltpower.com 
Website: www.waltpower.com 
Edited by WALT, All right reserved 
www.waltpower.com 3/3