50 °C 150 kVA 165 kVA Manufacturer Baudouin Moteurs 50 °C 120 kW 132 kW Engine Model 6M11G165/5 Frequency: 50/60 Hz Engine Speed 1500 RPM Voltage: 415V Type In-Line, 4 cycle Engine Speed: 1500RPM Number of Cylinder 6 Bore x Stroke 105 x 130 mm Fuel Tank Run time: 12hrs @ 75% load Displacement 6.75L BAUDOUIN MOTEURS Compression Ratio 18 : 1 FEATURES Fuel Injection Pump Mechanical Pump Governor Electronic Low in fuel consumption Fuel Consumption at 75% load 24.6 L/h (prime) Switchable Engine 50/60 Hz Flywheel SAE 3 / 11.5 Low exhaust emissions Alternator DURABILITY AND LOW NOISE Manufacturer LEROY-SOMER 70 dB(A) @ 7m +- 3 dB(A) Model TAL 044J ELECTRICAL SYSTEM Control System Shunt Excitation 12V negative earthed starter, battery charging alternator. Voltage Regulation +/- 1% FILTERING SYSTEM Insulation Class Class H Heavy Duty Air Cleaner Protection IP23 STAMFORD ALTERNATOR Rated Power Factor 0.8 APPLICATIONS Stator Winding Double Layer Lap The TAL alternator range is designed to Winding Pitch 2/3 meet the needs of general applications Winding Leads 6 (12 option) such as prime power and stand-by. Total Harmonic Distortion THD No Load <2% Total Harmonic Distortion In linear load THD < 5% STANDARD OF COMPLIANCE The TAL range complies with international standards and regulations: Maximum Over speed 2250 rpm IEC 60034 and derivative. Overall Specification The range is designed, manufactured and marketed in an ISO 9001 and 14001 environment. Dimensions ( L x W x H ) 3360 x 1250 x 1997 mm TOP OF THE RANGE ELECTRICAL PERFORMANCE Wet Weight 2217 kg Sound Level: 70 dB(A) @ 7m +- 3 dBA Class H insulation Ambient Temperature 50 °C Standard 6(12 option ) wire re-connectable winding, and 2/3 pitch Altitude 0m High DEEP efficiency SEA and motor DSE6120 CONTROLLER starting capacity MKI Relative Humidity Below 90% The DSE61xx MKII module monitors the engine, Coolant capacity 21 L Fuel Tank Capacity 450 litres indicating the operational status and fault Total oil capacity (including filters) 19 L conditions. Automatically shutting down the engine and CONDITIONS AND DEFINITIONS giving a true first up fault condition of an PRIME POWER RATING engine failure by the text LCD display. is the maximum power available for unlimited hours of usage in a variable Features load application. The average load factor should not exceed 70% of the engine’s PRP power rating during any 24 hour period. An overload Text based LCD display capability of 10% is available, however, this is limited to 1 hour within True RMS Voltage every 12 hour period. Current and Power monitoring STANDBY POWER RATING USB Communications is the maximum power available for a varying load for the duration of a Engine parameter monitoring. main power network failure. The average load factor over 24 hours of Fully configurable inputs for use as alarms or a range of different operation should not exceed 70% of the engine’s ESP power rating. functions. Typical operational hours of the engine is 200 hours per year, with a Engine ECU interface to electronic engines. maximum usage of 500 hours per year. This includes an annual maximum Data Logging of 25 hours per year at the ESP power rating. STANDARD REFERRED ISO 8528-1, ISO 3046, DIN6271. Performance tolerance of ±5%. Email: Info@Voltagenerators.com 4P-04, P.B.No.51564 Hamriyah Free Zone Sharjah, United Arab Emirates