installation.)
1 EN FOR SERVICE PERSONNEL ONLY
WARNING WARNING
s The unit should be mounted at stable, non-vibratory location s The Outdoor unit must be mounted at a location which can
which can provide full support to the unit. support heavy weight. Otherwise, noise and vibration will
increase.
CAUTION CAUTION
OUTDOOR UNIT
s Selecting the installation location: Suitable location that
s No nearby heat source and no obstruction near the air
INDOOR UNIT
will reduce the impact from rain and direct sun that may
outlet is allowed.
RAK-18PEC/RAC-18WEC RAK-35PECC/RAC-35WEC s The clearance distances from top, right and left are
affect the unit performance.
RAK-25PEC/RAC-25WEC RAK-50PECC/RAC-50WEC specified in figure below.
Besides, ventilation must be good and clear of obstruction.
s The air blown out of the unit should not point directly to
RAK-35PEC/RAC-35WEC RAK-10PECI/RAC-10WECI s The location must be convenient for water drainage and animals or plants.
RAK-50PEC/RAC-50WEC RAK-14PECI/RAC-14WECI pipe connection with the Outdoor unit. s The clearances of the unit from top, left, right and front are
RAK-25PECC/RAC-25WEC RAK-20PECI/RAC-20WECI s To avoid interference from noise, please place the unit and specified in figure below. At least there of the above sides
its remote controller at least 1m from the radio and must be open air.
television. s Be sure that the hot air blown out of the unit and noise do
SAFETY PRECAUTION s To avoid any error in signal transmission from the remote not disturb the neighbourhood.
s Read the safety precautions carefully before operating the unit. controller, please put the controller far away from high- s Do not install at a location where there is flammable gas,
s The contents of this section are vital to ensure safety. Please pay special attention to the following sign. frequency machines and high-power wireless systems. steam, oil and smoke.
WARNING .......... Incorrect methods of installation may cause death or serious injury. s The location must be convenient for water drainage.
s The installation height should be at least 2300 mm or more s Place the Outdoor unit and its connecting cord at least 1 m
CAUTION .......... Improper installation may result in serious consequence. from the floor. away from the antenna or signal line of television, radio or
Make sure to connect earth line. telephone. This is to avoid noise interference.
This sign in the figures indicates prohibition. Names of Indoor Components
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual. No. Item Qty Direction of Piping
Hanger Backward piping Figure showing the Installation
WARNING 1 from left
of Indoor and Outdoor Unit.
s Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
s Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause Screw for Hanger
water leakage, electric shock and fire. 2 Connection above
s Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may There are 6 directions allowed, 50mm
collapse and impose danger. namely, backward piping,
s Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing backward piping from left, 1 2
AAA size Battery
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and horizontally piping from right, above 50mm above 50mm
fire may occur due to the use of low quality wire or improper work. 3 horizontally piping from left,
Be sure to
s Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the vertically down from right, vertically completely
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the down from left. seal any gap
about 450m
terminal base. Improper insertion and loose contact may cause over-heating and fire. Screw for holder of with putty.
s Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or Remote Controller Dimension of Mounting
4
about 300mm
(10)
50
s Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.
297
317
s After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the Insulation sheet
6 12
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
10
34
500
(10)
telephone unit. Improper earthing may cause electric shocks. 57 insulated with the enclosed
insulation pipe. (If the insulator is
s When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. Bush insufficient, please use commercial
340
320
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a products.)
pressure in the freezing cycle system will build up steeply, causing an explosion or injury. 8
s When installing the unit, be sure to install the refrigerant pipe before starting the compressor. (RAC-50WEC,RAC-20WECI) 12 s The refrigerating machine oil is
10
39
500 146 easily affected by moisture. Use
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the 792 caution to prevent water from
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury. The component of 7 8 is included in entering the cycle.
s The electric cables should neither be reworked nor added. the package of the outdoor unit. s The difference in height between
above 200mm
Make sure to use an exclusive circuit breaker. The clearances of the the indoor and outdoor unit
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current. unit from top, left, right should be kept below 10m.
s Make sure to connect cables to terminal properly and terminal cover should close firmly. and front are specified above 50mm s The connecting pipe, no matter
Otherwise, over heating at terminal contact, fire or electric shock might occur. in figure below. At least big or small, should all be
give clearance
three of the above sides as wide as
insulated with insulation pipe and
s Make sure that there is no dust on any connected points of electric cables and fix firmly. must be open air. possible then wrapped with vinyl tape.
Otherwise, fire or electric shock might occur. (The insulator will deteriorate if
it is not wrapped with tape).
CAUTION above 100mm
above The connection of insulated drain
s A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the 200mm hose.
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Inner diameter 16mm
Without a circuit breaker, the danger of electric shock exists. above 300mm
s Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire Please use insulated drain hose for
For outdoor unit installation, allow at least the indoor piping (commercial
if flammable gas leaks around it. 2 sides of space around the unit to ensure product)
s Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your furniture. ventilation flue.
s An IEC approved power cord should be used. Power cord type: NYM.
1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe 2 Installation Of The Indoor Unit INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
s The refrigerating pipe should be adjusted to fit into
Cutting Low Cover bush the hole on the wall and then ready for further
CAUTION s While installing the pipe from the right, left or connection.
Drain hose
s The draining of the water container inside the Indoor unit can be done from the left. bottom side, use a knife to cut openings as s The terminals of 2 connected pipes must be covered
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of shown in figure. Then smoothen the edges of with insulator used for terminal connection. Then the
drain hose. Otherwise, condensed water may overflow the water container. openings with a file. pipes are wrapped with insulation pipe. Connecting
Pipe
Openings s Connect the connecting cord after removing low cord
Direct Mounting On The Wall Openings cover.
s Please use hidden beams in the wall to hold the hanger. (Refer to "CONNECTION OF POWER CORD")
65mm 47.5 mm The upper part of the Indoor unit is hanged on the together with Vinyl tape.
115 mm The end of the refrigerating pipes are at
m
hanger. Wall hole Preparation To Install Refrigerating Pipes locations marked with “ ” symbol.
5m
6 The projection at the lower part of the Indoor unit is s The refrigerating pipes and connecting cord
310 mm
60 mm 70mm 80mm 80 mm hooked onto the hanger.
590 mm Drain Hose Pipe transform and are attached.
780 mm
Hanger Cable Drain hose
Hanger
Drain layout of below
Lift the body
Level Screw for Hanger Refrigerating of the unit backward piping Please bend at a small 5mm
Pipe upwards and Installation radius to form an arc
Hanger
Screw the hanger at the then force it
positions possibly near the Hang the indoor unit onto the hanger. Use the temporary stand Projection
INDOOR UNIT
downwards.
upper and lower hooks where at the back of the Indoor unit to push its lower part 15cm
Hook
the indoor unit is hung. Use 4 or Protection forwards.
Line more screws to fix the hanger. Pipe Drain Hose Connecting Cord s Place the drain hose through the hole on the wall.
Projection
Wall hole s Wrap the refrigerating pipes with insulation pipe after
Weight
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL) connecting refrigerating pipe.
Preparation s Connect the connecting cord after removing low cover.
about 15cm
(Refer to "Connection of Power Cord")
Changed of Drain Hose and Installation Procedures.
s After adjustment, the connecting cord and refrigerating pipes
s Exchange the location of drain hose and drain cap while installing the pipe from the left side as
Procedures of Installation and Precautions shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
are placed into the space available under the Indoor unit.
s The projection of Indoor unit must hook to the hanger.
s Procedures to fix the hanger. Protection
s Please use pliers to pull out the drain cap. CAUTION Wall hole
pipe
Drain hose
1. Drill holes on wall. 2. Push plug into the holes. 3. Fix the hanger on wall with (This is an easier way to remove the drain Pipe
Refrigerating
Insufficient insert may pipe Pull this to the front during the
(As shown below) (As shown below) 4.1 x 32 screw. cap). Drain
result in water leakage. Cable hose Heat connection of refrigerating
(As shown in figure below) Drain layout of insulation pipe pipe to ease task.
Wall Connecting Connecting cord Connected
Plug Ceiling backward piping
section
Hanger from left cord
(Procure Drain hole
ø4.8mm
RAK_RAS_18/25/35/50PEC_IM_English 1
s Please mount the Outdoor unit of stable ground to prevent vibration and increase 1 Preparation of Pipe 3 Remove of Air From The Pipe And Gas Leakage Inspection
Pull downward
CAUTION hose to the adapter. Closed
R410A
Charge
s Remove burr and jagged edge will cause leakage. Manifold
hose valve
s Point the side to be trimmed downwards during trimming to prevent copper Vacuum
AIR REMOVAL
Fully tighter the "Hi" shuttle of the manifold
Valve pump
RAC-18/25/35WEC chips from entering the pipe. valve and completely unscrew the "Lo"
RAC-10/14WECI
s Before flaring, please put on the flare nut. shuttle. Run the vacuum pump for about
Please remove terminal cover
Please face this side (suction side)
when connecting the piping 10-15 minutes, then completely tighten the Vacuum
of the unit to the wall. Die Die
and connecting cord. "Lo" shuttle and switch off the vacuum pump
OUTDOOR UNIT
CN21
123 LN1 2 3 Wired Remote Controller : CN20
CN7
CN6
s Please check and confirm manuals attached to each
CONNECTION OF POWER CORD
Power Source And Operation Test How to remove the front cover How to Attach the Front Cover
Power Source Remove the front panel Check that the drain pan is securely attached.
s Please remove and attach the front panel by both hands.
After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
WARNING
FINAL STAGE OF INSTALLATION
Screw
RAK_RAS_18/25/35/50PEC_IM_English 2