THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before

installation.)
1 EN FOR SERVICE PERSONNEL ONLY
WARNING WARNING
s The unit should be mounted at stable, non-vibratory location s The Outdoor unit must be mounted at a location which can
which can provide full support to the unit. support heavy weight. Otherwise, noise and vibration will
increase.
CAUTION CAUTION

OUTDOOR UNIT
s Selecting the installation location: Suitable location that
s No nearby heat source and no obstruction near the air

INDOOR UNIT
will reduce the impact from rain and direct sun that may
outlet is allowed.
RAK-18PEC/RAC-18WEC RAK-35PECC/RAC-35WEC s The clearance distances from top, right and left are
affect the unit performance.
RAK-25PEC/RAC-25WEC RAK-50PECC/RAC-50WEC specified in figure below.
Besides, ventilation must be good and clear of obstruction.
s The air blown out of the unit should not point directly to
RAK-35PEC/RAC-35WEC RAK-10PECI/RAC-10WECI s The location must be convenient for water drainage and animals or plants.
RAK-50PEC/RAC-50WEC RAK-14PECI/RAC-14WECI pipe connection with the Outdoor unit. s The clearances of the unit from top, left, right and front are
RAK-25PECC/RAC-25WEC RAK-20PECI/RAC-20WECI s To avoid interference from noise, please place the unit and specified in figure below. At least there of the above sides
its remote controller at least 1m from the radio and must be open air.
television. s Be sure that the hot air blown out of the unit and noise do
SAFETY PRECAUTION s To avoid any error in signal transmission from the remote not disturb the neighbourhood.
s Read the safety precautions carefully before operating the unit. controller, please put the controller far away from high- s Do not install at a location where there is flammable gas,
s The contents of this section are vital to ensure safety. Please pay special attention to the following sign. frequency machines and high-power wireless systems. steam, oil and smoke.
WARNING .......... Incorrect methods of installation may cause death or serious injury. s The location must be convenient for water drainage.
s The installation height should be at least 2300 mm or more s Place the Outdoor unit and its connecting cord at least 1 m
CAUTION .......... Improper installation may result in serious consequence. from the floor. away from the antenna or signal line of television, radio or
Make sure to connect earth line. telephone. This is to avoid noise interference.
This sign in the figures indicates prohibition. Names of Indoor Components
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual. No. Item Qty Direction of Piping
Hanger Backward piping Figure showing the Installation
WARNING 1 from left
of Indoor and Outdoor Unit.
s Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
s Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause Screw for Hanger
water leakage, electric shock and fire. 2 Connection above
s Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may There are 6 directions allowed, 50mm
collapse and impose danger. namely, backward piping,
s Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing backward piping from left, 1 2
AAA size Battery
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and horizontally piping from right, above 50mm above 50mm
fire may occur due to the use of low quality wire or improper work. 3 horizontally piping from left,
Be sure to
s Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the vertically down from right, vertically completely
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the down from left. seal any gap

about 450m
terminal base. Improper insertion and loose contact may cause over-heating and fire. Screw for holder of with putty.
s Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or Remote Controller Dimension of Mounting
4

about 300mm

must not bend


stronger vibration may occur. Stand of the Outdoor unit 2300 mm or more
s Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults. (unit : mm)
s When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A) Remote Controller RAC-18/25/35WEC Mounting
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally L.H
RAC-10/14WECI Stand
which could result in a rupture and injury. 5

(10)
50

s Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.

297
317
s After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the Insulation sheet
6 12
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

10
34
500

Maximum pipe length 20m


s Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner 660 80

Minimum pipe length 3m


technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc. Drain Pipe RAC-50WEC
s Be sure to connect the earth line from the power supply wire to the outdoor unit and between RAC-20WECI Mounting
7
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the Stand The indoor piping should be

(10)
telephone unit. Improper earthing may cause electric shocks. 57 insulated with the enclosed
insulation pipe. (If the insulator is
s When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. Bush insufficient, please use commercial

340
320
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a products.)
pressure in the freezing cycle system will build up steeply, causing an explosion or injury. 8
s When installing the unit, be sure to install the refrigerant pipe before starting the compressor. (RAC-50WEC,RAC-20WECI) 12 s The refrigerating machine oil is

10
39
500 146 easily affected by moisture. Use
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the 792 caution to prevent water from
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury. The component of 7 8 is included in entering the cycle.
s The electric cables should neither be reworked nor added. the package of the outdoor unit. s The difference in height between
above 200mm
Make sure to use an exclusive circuit breaker. The clearances of the the indoor and outdoor unit
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current. unit from top, left, right should be kept below 10m.
s Make sure to connect cables to terminal properly and terminal cover should close firmly. and front are specified above 50mm s The connecting pipe, no matter
Otherwise, over heating at terminal contact, fire or electric shock might occur. in figure below. At least big or small, should all be
give clearance
three of the above sides as wide as
insulated with insulation pipe and
s Make sure that there is no dust on any connected points of electric cables and fix firmly. must be open air. possible then wrapped with vinyl tape.
Otherwise, fire or electric shock might occur. (The insulator will deteriorate if
it is not wrapped with tape).
CAUTION above 100mm
above The connection of insulated drain
s A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the 200mm hose.
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Inner diameter 16mm
Without a circuit breaker, the danger of electric shock exists. above 300mm
s Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire Please use insulated drain hose for
For outdoor unit installation, allow at least the indoor piping (commercial
if flammable gas leaks around it. 2 sides of space around the unit to ensure product)
s Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your furniture. ventilation flue.
s An IEC approved power cord should be used. Power cord type: NYM.

1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe 2 Installation Of The Indoor Unit INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
s The refrigerating pipe should be adjusted to fit into
Cutting Low Cover bush the hole on the wall and then ready for further
CAUTION s While installing the pipe from the right, left or connection.
Drain hose

s The draining of the water container inside the Indoor unit can be done from the left. bottom side, use a knife to cut openings as s The terminals of 2 connected pipes must be covered
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of shown in figure. Then smoothen the edges of with insulator used for terminal connection. Then the
drain hose. Otherwise, condensed water may overflow the water container. openings with a file. pipes are wrapped with insulation pipe. Connecting
Pipe
Openings s Connect the connecting cord after removing low cord
Direct Mounting On The Wall Openings cover.
s Please use hidden beams in the wall to hold the hanger. (Refer to "CONNECTION OF POWER CORD")

Visible outline of the


PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL) s After adjustment, fit the connecting cord and pipes
556 mm into the space available under the unit. Use holder to Holder
66.5 mm

outdoor unit Preparation


50.5 mm

450 mm hold them tight.


225 mm 18 mm
s Connect connecting cord. s Holder can be attached at the either of 2 places. Insulation pipe (must be wrapped with
s Pull out the pipe, connecting cord and drain hose. Please select the easier position. vinyl tape at every 120 mm)
95 mm 95 mm Installation
42,5 mm

THE CONNECTION OF REFRIGERATING PIPE DURING


164 mm
280 mm

37.5mm Connecting cords, pipe and


s Insert the pipe through the wall hole. drain hose must be laid
THE INSTALLATION OF INDOOR UNIT
42,5 mm

65mm 47.5 mm The upper part of the Indoor unit is hanged on the together with Vinyl tape.
115 mm The end of the refrigerating pipes are at
m
hanger. Wall hole Preparation To Install Refrigerating Pipes locations marked with “ ” symbol.
5m
6 The projection at the lower part of the Indoor unit is s The refrigerating pipes and connecting cord
310 mm
60 mm 70mm 80mm 80 mm hooked onto the hanger.
590 mm Drain Hose Pipe transform and are attached.
780 mm
Hanger Cable Drain hose
Hanger
Drain layout of below
Lift the body
Level  Screw for Hanger Refrigerating of the unit backward piping Please bend at a small 5mm
Pipe upwards and Installation radius to form an arc
 Hanger
Screw the hanger at the then force it
positions possibly near the Hang the indoor unit onto the hanger. Use the temporary stand Projection
INDOOR UNIT

downwards.
upper and lower hooks where at the back of the Indoor unit to push its lower part 15cm
Hook
the indoor unit is hung. Use 4 or Protection forwards.
Line more screws to fix the hanger. Pipe Drain Hose Connecting Cord s Place the drain hose through the hole on the wall.
Projection
Wall hole s Wrap the refrigerating pipes with insulation pipe after
Weight
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL) connecting refrigerating pipe.
Preparation s Connect the connecting cord after removing low cover.
about 15cm
(Refer to "Connection of Power Cord")
Changed of Drain Hose and Installation Procedures.
s After adjustment, the connecting cord and refrigerating pipes
s Exchange the location of drain hose and drain cap while installing the pipe from the left side as
Procedures of Installation and Precautions shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
are placed into the space available under the Indoor unit.
s The projection of Indoor unit must hook to the hanger.
s Procedures to fix the hanger. Protection
s Please use pliers to pull out the drain cap. CAUTION Wall hole
pipe
Drain hose
1. Drill holes on wall. 2. Push plug into the holes. 3. Fix the hanger on wall with (This is an easier way to remove the drain Pipe
Refrigerating
Insufficient insert may pipe Pull this to the front during the
(As shown below) (As shown below) 4.1 x 32 screw. cap). Drain
result in water leakage. Cable hose Heat connection of refrigerating
(As shown in figure below) Drain layout of insulation pipe pipe to ease task.
Wall Connecting Connecting cord Connected
Plug Ceiling backward piping
section
 Hanger from left cord
(Procure Drain hole
ø4.8mm

 Screw locally) 3 Heat Insulation and Finish of the Piping


s The connected terminals should be completed sealed Insulation material for pipe
Hexagonal wrench with heat insulator and then tied up with rubber strap. connection
32mm key (Φ4mm) Drain cap Drain Hose s Push the pipe deeply until the insulating s Do not tie the terminals with the tape too tight.
Wall
section of the drain hose end gets over If any clearance or over-tightening may cause
the rib at the indoor unit side.
s Remove low cover condensation.
s Please tie the pipe and power line together with vinyl Sleeve of
s Insert drain cap up to the location securely till the cap stops. tape as shown in the figure showing the installation of
Wall Penetration and Installation of Protection Pipe s Please use hexagonal wrench key(Φ4mm) to insert the drain cap. Indoor and Outdoor units.
protection pipe Putty
Hexagonal wrench
Drain hole key (Φ4mm) (This is an easier way to install the drain cap.) s To enhance the heat insulation and to prevent water
s Drill a ø65mm hole on wall which is condensation, please cover the outdoor part of the
slightly tilted towards the outdoor side. drain hose and pipe with insulation pipe.
Drill the wall at a small angle. Indoor Outdoor WARNING CAUTION s Completely seal any gap with putty. Putty
s Cut the protection pipe according to the 2-5mm Be sure that the wire is not
wall thickness. Seal with Seal with in contact with any metal in s The rubber strap used for fixing the insulator 4 Installation of Drain Hose
s Empty gap in the sleeve of protection putty putty the wall. Please use the should not be tied with great force. Otherwise,
pipe should be completely sealed with protection pipe as wire this will damage heat insulation and causes Pipe Rubber strap tied
putty to avoid dripping of rain water into passing through the hollow water condensation. with great force CAUTION
Ditch
the room. part of the wall so as to s Please pull the lower part of the Indoor unit Condensed Be sure that the drain hose is
s Please ensure smooth flow of water Protection WALL prevent the possibility of outwards to check if the unit is hooked onto water pond not loosely connected bend or
when installing the drain hose. Improper pipe damaged by mouse. the hanger. Improper installation may cause proper condition like left figure.
Sleeve of Bending upwards Condensed water
installing may wet your funiture. Unless it seals completely, vibration and noise. pond
protection Pipe
s An IEC approved power cord should be any air with high humidity s Transform the piping while holding down the
pipe support You are free to choose the side (left or right) for the installation of drain
used. Power cord type: NYM. flows from outdoor and any lower portion of pipe-support by hand. Transform after
hose. Please ensure the smooth flow of condensed water of the Indoor
dew may drop. bending downward.
CAUTION unit during installation. (Careless may result in water leakage.)

RAK_RAS_18/25/35/50PEC_IM_English 1
s Please mount the Outdoor unit of stable ground to prevent vibration and increase 1 Preparation of Pipe 3 Remove of Air From The Pipe And Gas Leakage Inspection

INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL


of noise level.
s Use a pipe cutter to cut the copper pipe and remove burr.
s Decide the location for piping after sorting out the different types of pipe available. Procedures of using Vacuum Pump for Air Removal
s When removing side cover, please pull the handle after undoing the hook by pulling Trimming tool
it downward. Reinstall the side cover in the reverse order of the removal. When the meter reaches - 101KPa
As shown in right figure, remove the cap
Please face this side (suction side) of valve core. Then, connect the charge (-76cmHg) during pumping fully
Please remove terminal cover
of the unit to the wall. hose. Remove the cap of valve head. tighten the shuttle.
when connecting the piping
and connecting cord. Copper pipe 1 Connect the vacuum pump adapter to the Meter showing
vacuum pump and connect the charge pressure

Pull downward
CAUTION hose to the adapter. Closed
R410A
Charge
s Remove burr and jagged edge will cause leakage. Manifold
hose valve
s Point the side to be trimmed downwards during trimming to prevent copper Vacuum

AIR REMOVAL
Fully tighter the "Hi" shuttle of the manifold
Valve pump
RAC-18/25/35WEC chips from entering the pipe. valve and completely unscrew the "Lo"
RAC-10/14WECI
s Before flaring, please put on the flare nut. shuttle. Run the vacuum pump for about
Please remove terminal cover
Please face this side (suction side)
when connecting the piping 10-15 minutes, then completely tighten the Vacuum
of the unit to the wall. Die Die
and connecting cord. "Lo" shuttle and switch off the vacuum pump
OUTDOOR UNIT

A s Please use adapter


CAUTION exclusive tool for 2 pump. Valve
s Loosen the spindle of the service valve When pumping starts, slightly
s Do not touch the suction refrigerant R410A. with small diameter by 1/4 turn and loosen the flare nut to check of
Copper pipe
Pull downward por t, bottom surface, or air sucked in. Then tighten the
tighten the spindle immediately after 5 flare nut.
aluminum fin of the outdoor Outer A (mm) Rigid Flaring Tool
unit. to 6 seconds.
Failure to do so may cause Diameter (Ø) For R410A tool For R22 tool s Remove the charging hose from the
RAC-50WEC
RAC-20WECI an injury. 6,35 (1/4") 0 - 0,5 1,0 service valve.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT 9,52 (3/8") 0 - 0,5 1,0
s There is holes on the base of Outdoor unit for condensed water to exhaust. 12,7 (1/2") 0 - 0,5 1,0 Completely unscrew the spindle of the
service valve (at 2 places) in anticlockwise
s In order to flow condensed water to the drain, the unit is installed on a stand or a
2 Pipe Connection 3 direction to allow the flow of refrigerant
block so that the unit is 100mm above the ground as shown figure. Join the drain
pipe to one hole. (using Hexagonal Wrench key).
s After installation, check whether the drain pipe clings to the base firmly. s In case of removing flare nut of a indoor unit, first remove
a nut of small diameter side, or a seal cap of big diameter
RAC-18/25/35WEC,RAC-10/14WECI RAC-50WEC,RAC-20WECI side will fly out. Free from water into the piping when Tighten the cap of valve head. Check the
working.
DRAIN HOLE CAUTION s Be sure to tighten the flare nut to the specified torque with 4 cap's periphery if there is any gas leakage.
BASE BASE The task is then completed.
a torque wrench.
above If the flare nut is overtightened, the nut may be split after a The body of service
above
100mm valve
70mm long period has passed, and may cause a refrigerant leak.
8 BUSH
DRAIN HOLE
Outer diameter: 8 BUSH Push Push
16 mm or more
7 DRAIN PIPE s Please be careful when bending the copper pipe.
Outer diameter: 7 DRAIN PIPE
16 mm or more s Screw in manually while adjusting the center. After that, use a torque wrench to Cap of
valve core Cap of valve
tighten the connection. Outer diameter Torque N·m Cap of valve
head
head
s Install the outdoor unit horizontally and make sure that condensate drains away. Flare nut of pipe (ø) (kgf·cm) Hexagonal wrench Key
s In case of using in chilly area Small diameter side 6.35 (1/4") 13.7-18.6 (140 - 190)
Especially, in case that there are many snows by very cold in chilly area, condensed Large diameter side
9.52 (3/8") 34.3-44.1 (350 - 450) Gas leakage inspection
water freezes on the base and may result not to drain. In this case, please remove 12.7 (1/2") 44.1-53.9 (450 - 550)
the bush and the drain pipe at the bottom of unit. (Left and center near discharge Valve Small diameter side 6.35 (1/4") 19.6-24.5 (200 - 250) Please use gas leakage detector to check if leakage occurs at
Wrench 9.52 (3/8") 19.6-24.5 (200 - 250) connection of Flare nut as shown on the right.
head cap
portion of air, each 1 place). It becomes smooth drain. Torque Large diameter side
12.7 (1/2") 29.4-34.3 (300 - 350) If gas leakage occurs, further tighten the connection to stop leakage.
Ensure that the distance from the drain hole to the ground is 250 mm or more. wrench Valve core cap 12.3-15.7 (125 - 160)

Wiring of The Indoor Unit How to connect the optional parts


s THIS APPLIANCE MUST BE
(WIFI Adapter, H-LINK RAC Adapter, Dry contact, Wired Remote Controller)
WARNING EARTHED. s For wire connection of the Indoor unit, you need to remove the front cover, the low cover
under the body of the unit and terminal cover. s For cable connection to control P.W.B., you need to
Procedures of Wiring s Remove the cover from the terminal base and screw the cable. remove front cover and electrical box cover.
Each connecting location is as below.
Indoor Unit Outdoor Unit
 Dry contact: CN6
CN20
 WIFI Adapter/H-LINK RAC Adapter: CN7

CN21
123 LN1 2 3  Wired Remote Controller : CN20

CN7


CN6
s Please check and confirm manuals attached to each
CONNECTION OF POWER CORD

Connecting Cord optional parts for more connection details.


Connecting s You can refer to this installation manual how to remove
cord and re-attach the front cover.
s Please be careful not to damage lead wires by edge of CN6
AC 220-230V CN7
plate when connecting the optional parts.
1ø 50Hz Earth
Detail of Cutting the Connecting Cord Wiring of the Outdoor Unit
s Please remove the side cover for wire connection.
Cord band
Indoor Unit Outdoor Unit s If you cannot attach the side plate due to the connection cord, please
70mm Green + Yellow press the connecting cord in the direction to the front panel to fix it.
160mm
10mm (ground) After remove the screw s Be sure that the hooks of the side cover fixed in certainly. Otherwise water
Strip 1 10mm
1
WARNING leakage may occur and this causes short circuit or faults.
wires 2 and terminal cover, and
Strip 2
s The connecting cord should not touch to service valve and pipes. (it
3
wires put the connecting cords becomes high temperature in heating operation.)
3
10mm
and fix the terminal cover
Connecting cord Green +
with screw. Checking for the electric source and the voltage range
Yellow
45mm 20mm s Before installation, the power source must be checked and necessary wiring work must
Connecting cord
100mm be completed. To make the wiring capacity proper, use the wire gauge list below for the
Method to remove the low cover wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.
s Pull at the  and  in
WARNING the directions as shown RAC-18/25/35WEC,RAC-10/14WECI RAC-50WEC,RAC-20WECI
by arrows to remove the
Terminal marking
s The naked part of the wire core should be 10mm fix it to the terminal tightly. Then cover. LN123 coverAbdeck
LN123 cover
try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.
Earth terminal Earth terminal
s Be sure to use only wire specified for the use of air-conditioner.
s Please refer to the manual for wire connection and the wiring technique should
meet the standard of the electrical installation.
Cord band Cord band
s There is an AC voltage drop between the LN terminal if the power is on. Therefore,
be sure to remove the plug from its socket. s Investigate the power supply capacity and other IMPORTANT
electrical conditions at the installing location. Fuse Capacity
Depending on the model of room air conditioner to be RAC-18/25/35WEC 15A time delay fuse
RAC-10/14WECI
WARNING installed, request the customer to make arrangements
RAC-50WEC
25A time delay fuse
WARNING for the necessary electrical work etc. RAC-20WECI
s Leave some space in the connecting cord for maintenance The electrical work includes the wiring work up the
purpose and be sure to secure it with the cord band. s When the fuse (F5 or F6) has been blown out by the improper connection of Wire length Wire cross-section
outdoor unit. In localities where electrical conditions
s Secure the connecting cord along the coated part of the wire power cable, it can be restored by the attached reserve fuse. up to 6m 1.5mm2
are poor, use of a voltage regulation is recommended.
using the cord band. Do not exert pressure on the wire as this Please exchange the blown-out fuse after making sure the right connection. up to 15m 2.5mm2
s Install outdoor for the room air conditioner within the
may cause overheating or fire. up to 20m 4.0mm2
reaching range of the line cord.

Power Source And Operation Test How to remove the front cover How to Attach the Front Cover

Power Source Remove the front panel Check that the drain pan is securely attached.
s Please remove and attach the front panel by both hands.
After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
WARNING
FINAL STAGE OF INSTALLATION

the front cover to lock the claws.


s Never remodel the power plug nor extend the long-distance
cord. Tighten the two screws.
s Keep additional length for the power cord and do not render
the plug under external force as this may cause poor contact.
s Do not fix the power cord with U-shape nail.
s The power cable easily generates heat. Do not bring the s After opening the front panel by both hands.
cable together with a wire or vinyl tie. Undo the right arm while pushing it inside.
Slide the front panel to right as shown in figure. Then remove
while pulling it to front.
Operation test
Remove the filters.
• Please ensure that the air conditioner is in normal operating Install the filter.
condition during the operation test. After removing two screws, pull the center of the front cover
towards you and release the claws. Slide the shafts of the right and left arms on the front panel
• Explain to your customer about the proper operation procedures along the steps to insert the shafts into the holes till they stop.
as described in the operation manual. Pull the side faces (lower sections) of the front cover towards After checking that the shafts are securely inserted, close the
• If the indoor unit won’t operate, check the cable for correct you as shown in the figure and remove the cover. panel.
connection.

Screw

HOW TO REMOVE INDOOR UNIT


s Push up the [PUSH] sections at the bottom of the indoor unit and
pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)
[PUSH] mark positions