ED-01 MATERIAL SUMMARY CABLE LADDER / TRAY SECURE WITH ADJUSTMENT

PLATE HARDWARE CONNECTOR


MATERIAL SUMMARY NOTES
(for 1-OFF installation only) (for 1-OFF installation only)
*-0001 ADJUSTMENT 1. EARTHING & BONDING SHALL BE MADE IN ACCORDANCE WITH MOTS 10,
ED-02 ED-02

PLATE APPENDIX B EARTHING AND BONDING WITH IEC 60364-5-54 AND EN 62204.
STRUCTURAL STEEL ITEM DESCRIPTION QTY UNIT 8315 A/R

8304 A/R

CONNECTOR ITEM DESCRIPTION QTY UNIT


UX 0.6/1KV UNARMOURED, TINNED ANNEALED UX 0.6/1KV UNARMOURED, TINNED ANNEALED 2. TYPICAL EARTHING DETAILS TO BE AS PER MOTS-10 ATTACHMENT 1.
EC01 A/R LM EC01 2 LM
STRANDED CIRCULAR COPPER CONDUCTOR, STRANDED CIRCULAR COPPER CONDUCTOR,
OUTER SHEATH FLAME RETARDANT, OUTER SHEATH FLAME RETARDANT, 3. SKIDS/STEEL PEDESTAL, LIGHTING POLES, ETC DIRECTLY WELDED TO STEEL
HALOGEN-FREE AND MUD RESISTANT HALOGEN-FREE AND MUD RESISTANT DECK/ COLUMNS NEED NOT BE PROVIDED WITH SEPARATE PROTECTIVE EARTH
ED-02
THERMOSET COMPOUND, SHF2, UNARMOURED, THERMOSET COMPOUND, SHF2, UNARMOURED, BONDING CONDUCTOR.
EC01 A/R

GREEN YELLOW 1C X 10 SQMM GREEN YELLOW 1C X 10 SQMM


4. STEEL SURFACES SHALL BE THOROUGHLY CLEANED BEFORE MAKING A EARTHING
FOR CABLE LADDER FOR CABLE TRAYS
CONNECTION. DRILLED HOLES AND FIELD CUTS SHALL BE PROTECTED WITH AN
8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 2 EA 8315 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 4 EA
(FOR LADDER APPLICATION OF ZINC-CHROMATE RICH.
COPPER, UNINSULATED, COMPRESSION TYPE, 1371437 1

ED-02

COPPER, UNINSULATED, COMPRESSION TYPE,


ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD. TRAYS) ONE HOLE, STANDARD BARREL, 10 MM2 , M6 STUD.
(FOR CABLE EC01 A/R

5. ALL EXPOSED EARTH CONNECTIONS AND TIES SHALL BE COATED WITH A SUITABLE
1371982 1

FOR CABLE LADDER TRAYS) (2 PLS.) FOR CABLE LADDER CORROSION PREVENTIVE COATING (3M SCOTCH ELECTRICAL COATING OR EQUAL)
TINNED COPPER LUG 1371437 SELF-LOCK BOLT AND ANTI-VIBRATION FLANGE 1 EA 8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 4 EA FOLLOWING FINAL INSTALLATION AND TESTING.
NUT SET WITH LOW NECK. (S-M LS-NU-M10x25) ED-28 EARTHINGING CONNECTION TO
COPPER, UNINSULATED, COMPRESSION TYPE,
1371437 1

ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD. 6. EQUIPMENT EARTHING CONDUCTOR IN MOTOR FEEDER CABLE TO BE EARTHED
(ED-01, STANDARD EARTH BOSS) QUANTITY 1 EA
LADDER TRAY SHALL BE INCLUDED IN ED-01 MTO
CABLE LADDER / TRAY HORIZONTAL FOR CABLE LADDER TO EARTHING BOLT INSIDE THE MOTOR TERMINAL BOX. FIELD SHALL EXERCISE
CARE IN SELECTING LOCATIONS FOR WELDING.
ADJUSTMENT PLATE 1371437 SELF-LOCK BOLT AND ANTI-VIBRATION FLANGE 4 EA
NUT SET WITH LOW NECK. (S-M LS-NU-M10x25)
7. EARTH PADS AND DRILLED HOLES IN EQUIPMENT AND TO SUPPORT STRUCTURES
TOTAL NO. OF INSTALLATION = 1 No. FOR CABLE TRAYS FOR EARTHING PURPOSES. SHARP BENDS SHALL BE AVOIDED IN ROUTING OF ALL
1371982 SELF-LOCK BOLT AND ANTI-VIBRATION FLANGE 4 EA GROUNDING.
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048 NUT SET WITH LOW NECK. (S-M LS-NU-M6x20)
8. CONDUCTORS PRECAUTIONS SHOULD BE TAKEN TO PREVENT PHYSICAL DAMAGE
NOTES FOR ED-25 TO INSULATED CABLE JACKET BY SHARP METAL EDGES.
ED-25 TOTAL NO. OF INSTALLATION = 1 No.
CABLE LADDER EARTHING 1. CABLE WAYS ASSEMBLED WITH MANUFACTURER GENUINE ACCESSORIES. NEED NO FURTHER 9. SHRINK SLEEVING TO BE USED OUTSIDE PANEL BETWEEN ALL LUGS AND
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048
BONDING. BONDING MANDATORY IF GAP BETWEEN TWO CABLE TRAYS. INSULATIONS. SLEEVING COLORS AS FOLLOWS: GROUNDING - YELLOW /
CONSTRUCTION NOTE: GREEN POWER - BLACK.
SCREW TO BE INSTALLED SUCH THAT
SCREW HEAD IS ON INSIDE OF TRAY. 10. ALL EARTH/BONDING CONNECTION TO BE COVERED WITH 3M SCOTCH COTE
MATERIAL SUMMARY ELECTRICAL COATING.
ED-01 (for 1-OFF installation only) NOTE FOR ED-30
*-0001 11. ALL OUTDOOR GLANDS SHALL BE DELUGE PROOF IP 66. 2
STRUCTURAL STEEL 1. FOR EQUIPMENT NOT COME WITH EARTH STUD, PROPOSED TO USE CABLE GLAND EARTH TAG.
ITEM DESCRIPTION QTY UNIT 12. WELDING OF EARTH BOSS OR STUD ACCORDING TO MOTS-12.
EC01 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R LM
STRANDED CIRCULAR COPPER CONDUCTOR, 13. ALL DIMENSIONS ARE IN MM UNLESS OTHER WISE SPECIFIED.
EARTH STUD BY VENDOR
OUTER SHEATH FLAME RETARDANT,
HALOGEN-FREE AND MUD RESISTANT 14. FOR EQUIPMENT WITHOUT EARTH STUD, THE EARTHING CABLE SHALL BE
ED-02

THERMOSET COMPOUND, SHF2, UNARMOURED, TERMINATED AT THE EARTH TAG OF THE CABLE GLAND.
EC01 A/R
FIELD INSTRUMENT CABLE
GREEN YELLOW 1C X 10 SQMM
FOR CABLE LADDER
8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 2 EA
COPPER, UNINSULATED, COMPRESSION TYPE,
ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD.

TINNED COPPER LUG FOR CABLE LADDER


1371437 SELF-LOCK BOLT AND ANTI-VIBRATION FLANGE 1 EA LEGEND
NUT SET WITH LOW NECK. (S-M LS-NU-M10x25) ED-02

1371437 1

EC01 STANDARD EARTH BOSS


A/R

MV LADDER TRAY (ED-01, STANDARD EARTH BOSS) QUANTITY 1 EA


SHALL BE INCLUDED IN ED-01 MTO
ED-01 BOLTED EARTH CONNECTION
*-0001 ED-01
TOTAL NO. OF INSTALLATION = 1 No. DECK LEVEL
ED-02

*-0001
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048 EC05 A/R

EARTHING CABLE

NOTES FOR ED-26


ED-01

1a. CABLE WAYS ASSEMBLED WITH MANUFACTURER GENUINE ACCESSORIES. XXXX MATERIAL INDENTIFICATION MARKER
ED-26 MV CABLE LADDER EARTHING NEED NO FURTHER BONDING.BONDING MANDATORY IF GAP BETWEEN TWO CABLE TRAYS.
DECK LEVEL EARTHING DETAIL
1b. MINIMUM 10 Sq.mm CU BONDING IN EACH END OF CABLE WAYS. CABLE WAYS
FOR HV CABLES TO BE BONDED TO STRUCTURE EVERY 15 METERS. BONDING NOT DETAIL NUMBER
APPLICABLE FOR GRP CABLES TRAYS. ED-29 WELL CONDUCTOR EARTHING ED-30 NON IS INSTRUMENT EARTHING ED-XX
*-000X
ED-01 MATERIAL SUMMARY DETAIL DRAWING NUMBER

*-0001 (for 1-OFF installation only) ABBREVIATIONS:


STRUCTURAL STEEL
A/R AS REQUIRED
ITEM DESCRIPTION QTY UNIT EA EACH
MATERIAL SUMMARY LM LENGTH IN METERS
EC01 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R LM CONNECTED TO EARTHING BAR / TRAFO. NEUTRAL (for 1-OFF installation only)
STRANDED CIRCULAR COPPER CONDUCTOR, (FOR CABLE SIZE / QUANTITY
OUTER SHEATH FLAME RETARDANT, REFER RELEVANT LAYOUT DRAWING)
EC01
ED-02

A/R
HALOGEN-FREE AND MUD RESISTANT ITEM DESCRIPTION QTY UNIT
THERMOSET COMPOUND, SHF2, UNARMOURED,
GREEN YELLOW 1C X 10 SQMM EC05 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R EA
ED-02

STRANDED CIRCULAR COPPER CONDUCTOR,


FOR CABLE TRAYS 9723 OUTER SHEATH FLAME RETARDANT,
A/R

8315 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED STRUCTURAL


2 EA MEMBER
ED-02

HALOGEN-FREE AND MUD RESISTANT


COPPER, UNINSULATED, COMPRESSION TYPE, 9723 A/R

THERMOSET COMPOUND, SHF2, UNARMOURED,


ONE HOLE, STANDARD BARREL, 10 MM2 , M6 STUD.
TINNED COPPER LUG
ED-02

GREEN YELLOW 1C X 70 SQMM


FOR CABLE TRAYS 7982 A/R

EC06 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R EA


1371982 SELF-LOCK BOLT AND ANTI-VIBRATION FLANGE 1 EA ED-02

STRANDED CIRCULAR COPPER CONDUCTOR,


1371982 NUT SET WITH LOW NECK. (S-M LS-NU-M6x20) EARTHING CABLE
7982
1

OUTER SHEATH FLAME RETARDANT,


A/R

CABLE TRAY STRUCTURAL HALOGEN-FREE AND MUD RESISTANT TWYY-07-10001-0001 OVER ALL EARTHING SINGLE LINE DIAGRAM TYRA WEST
(ED-01, STANDARD EARTH BOSS) QUANTITY 1 EA MEMBER THERMOSET COMPOUND, SHF2, UNARMOURED, DK-TYYY-ELE-PHL-018-10000 EARTHING DESIGN PHILOSOPHY FOR WHRP
SHALL BE INCLUDED IN ED-01 MTO
GREEN YELLOW 1C X 120 SQMM
Drawing no. Reference dwgs.
UX 0.6/1KV UNARMOURED, TINNED ANNEALED
ED-02

ED-02

EC07 A/R EA
EC05
ED-27
A/R

7966 STRANDED CIRCULAR COPPER CONDUCTOR,


CABLE TRAY EARTHING
A/R

TOTAL NO. OF INSTALLATION = 1 No.


ED-02

ED-02

EC06 A/R
OUTER SHEATH FLAME RETARDANT,
8309 HALOGEN-FREE AND MUD RESISTANT
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048
ED-02

A/R

ED-02

EC07 A/R

THERMOSET COMPOUND, SHF2, UNARMOURED,


8310 A/R

ED-01 GREEN YELLOW 1C X 185 SQMM


ED-02

*-0001 8309 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA


8311
EARTHING DETAIL-29 EARTHING DETAIL-30
A/R

COPPER, UNINSULATED, COMPRESSION TYPE, Chandrasekar, Digitally signed by Venkatavijaya Digitally signed by Kumaraswam
Digitally signed by
Kumaraswamy,

2 26-JUL-2019 ISSUED FOR CONSTRUCTION


Chandrasekar, Balakrishnan Venkatavijayakumar, Seethamsetty
kumar, DN: cn=Venkatavijayakumar,
y, Janakiraman
Balakrishnan Date: 2019.07.26 17:35:22 Seethamsetty

ONE HOLE, STANDARD BARREL, 70 MM2 , M10 STUD.


+05'30'
Seethamsetty Date: 2019.07.26 17:42:17 +05'30'
Janakiraman Date: 2019.07.29
10:10:18 +05'30'

MATERIAL SUMMARY MATERIAL SUMMARY 8310 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA
1 14-MAY-2019 DAR APA DRK ISSUED FOR CONSTRUCTION

(for 1-OFF installation only) (for 1-OFF installation only) COPPER, UNINSULATED, COMPRESSION TYPE, 0 13-DEC-2018 DAR APA DRK ISSUED FOR CONSTRUCTION

ONE HOLE, STANDARD BARREL, 120 MM2 , M10 STUD. A 26-SEP-2018 DAR APA DRK ISSUED FOR REVIEW
Rev Date Drawn Chkd Appr Description
ITEM DESCRIPTION QTY UNIT ITEM DESCRIPTION QTY UNIT 8311 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA
COPPER, UNINSULATED, COMPRESSION TYPE, CONTRACT NUMBER
EC05 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R EA EC01 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R EA ONE HOLE, STANDARD BARREL, 185 MM2 , M10 STUD. McDERMOTT, INC 8600006110
STRANDED CIRCULAR COPPER CONDUCTOR, STRANDED CIRCULAR COPPER CONDUCTOR, ED-31 EARTHING OF JACKET COLUMN LEG
7966 PLATE: 10mm THK. MAT'L: CS; ASTM A36, S1, A/R EA
OUTER SHEATH FLAME RETARDANT, OUTER SHEATH FLAME RETARDANT, GRADE S235J0, DC4, NT (200MM X 150MM)
HALOGEN-FREE AND MUD RESISTANT HALOGEN-FREE AND MUD RESISTANT CABLE LUG & CABLE ARE SHOWN FOR REFERENCE ONLY. 7982 BAR FLAT 50 X 6 MM TYPE III (500MM LONG) A/R EA
THERMOSET COMPOUND, SHF2, UNARMOURED, THERMOSET COMPOUND, SHF2,
GREEN YELLOW 1C X 70 SQMM UNARMOURED, GREEN YELLOW 1C X 10 SQMM FOR SIZE/QUANTITIES, REFER RELEVANT LAYOUT DRAWING. TIE: CABLE; 300MM LG X 6.4MM WD ;
9723 A/R EA
8309 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 2 EA 8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 2 EA
SSTL NYLON COATED, HEAVY DUTY EPC CONTRACT FOR TYRA REDEVELOPMENT PROJECT - WHRP
COPPER, UNINSULATED, COMPRESSION TYPE, COPPER, UNINSULATED, COMPRESSION TYPE, (ED-01, STANDARD EARTH BOSS) QUANTITY Title
ONE HOLE, STANDARD BARREL, 70 MM2 , M10 STUD. ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD. SHALL BE INCLUDED IN ED-01 MTO
A/R EA
TYRA WEST, PLATFORM B
(ED-01, STANDARD EARTH BOSS) QUANTITY 2 EA (ED-01, STANDARD EARTH BOSS) QUANTITY 2 EA EARTHING AND BONDING DETAILS
SHALL BE INCLUDED IN ED-01 MTO SHALL BE INCLUDED IN ED-01 MTO
TYPICAL EARTHING AND BONDING

TOTAL NO. OF INSTALLATION = 1 No. TOTAL NO. OF INSTALLATION = 1 No. Scale Size Drawing no. Rev.

* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048 * INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048 NTS A1 TWBY-07-10048-0007 2