Professional Documents
Culture Documents
EC02 (ED-01, STANDARD EARTH BOSS) QUANTITY FOLLOWING FINAL INSTALLATION AND TESTING.
1 - EA
A/R
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048 8. CONDUCTORS PRECAUTIONS SHOULD BE TAKEN TO PREVENT PHYSICAL DAMAGE
TOTAL NO. OF INSTALLATION = 1 No. TO INSULATED CABLE JACKET BY SHARP METAL EDGES.
EC05 A/R
ED-17
*-0005 NOTE 3 NOTE 3
ED-02
TOP OF DECK
EC05
LEGEND
A/R
(TYP)
ED-10 WELDING SOCKET OUTLET ED-10A WELDING SOCKET OUTLET
NOTE 1b NOTE 1b STANDARD EARTH BOSS
(STARTER BRACKET BOLTED) (STARTER BRACKET WELDED)
ED-09 HORIZONTAL TANK OR VESSEL BOLTED EARTH CONNECTION
EARTHING CABLE
ED-17 ED-17 11 11A EC05 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R LM ED-XX
STRANDED CIRCULAR COPPER CONDUCTOR,
*-0005 *-0005 EC01 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R A/R LM OUTER SHEATH FLAME RETARDANT, *-000X
CONVENIENCE STRANDED CIRCULAR COPPER CONDUCTOR, DETAIL DRAWING NUMBER
HALOGEN-FREE AND MUD RESISTANT
OUTLET OR OUTER SHEATH FLAME RETARDANT, THERMOSET COMPOUND, SHF2, UNARMOURED,
EARTHING CONTROL EARTHING HALOGEN-FREE AND MUD RESISTANT GREEN YELLOW 1C X 70 SQMM ABBREVIATIONS:
CABLE TO STATION CABLE TO THERMOSET COMPOUND, SHF2,
BE LANDED BE LANDED A/R AS REQUIRED
UNARMOURED, GREEN YELLOW 1C X 10 SQMM CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 4 EA
ON EARTH ON EARTH 8309 EA EACH
COPPER, UNINSULATED, COMPRESSION TYPE,
TAB OF GLAND TAB OF GLAND 8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 2 2 EA LM LENGTH IN METERS
ONE HOLE, STANDARD BARREL, 70 MM2 , M10 STUD.
NOTE 14 NOTE 14 COPPER, UNINSULATED, COMPRESSION TYPE,
ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD. (ED-01, STANDARD EARTH BOSS) QUANTITY 2 EA
SHALL BE INCLUDED IN ED-01 MTO
(ED-01, STANDARD EARTH BOSS) QUANTITY 1 - EA
(TYP) (TYP) SHALL BE INCLUDED IN ED-01 MTO (ED-03, BONDING CONNECTION) QUANTITY
ED-07 ED-07
1 EA
EC01 EC01 SHALL BE INCLUDED IN ED-03 MTO
(ED-17, TWO CABLES IN SAME LUG)
A/R A/R
1 1 EA
QUANTITY SHALL BE INCLUDED IN HV (ED-18, EARTH LUG SS PLATE) QUANTITY 1 EA
ED-17 MTO JUNCTION BOX SHALL BE INCLUDED IN ED-18 MTO
P001 PAINT : CORROSIVE PREVENTIVE COATING A/R A/R LTR
EARTH STUD BY VENDOR
TOTAL NO. OF INSTALLATION = 1No.
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048
TOTAL NO. OF INSTALLATION = 1 No. TWYY-07-10001-0001 OVER ALL EARTHING SINGLE LINE DIAGRAM TYRA WEST
NOTES FOR ED-12
DK-TYYY-ELE-PHL-018-10000 EARTHING DESIGN PHILOSOPHY FOR WHRP
* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048
15. IF OGLAEND STARTER BRACKET IS DIRETLY WELDED ON DECK PLATE/STRUCTURE THE Drawing no. Reference dwgs.
PROTECTIVE EARTH CABLE WILL BE CONNETED BETWENN EQUIPMENT AND OGLAEND
NOTES FOR ED-11
STARTER BRACKET (STAND/SUPPORT). HENCE EARTH BOSS NOT REQUIRED.
16. OGLAEND STARTER BRACKET IS BOLTED ON DECK PLATE/STRUCTURE THE ED-02
ED-03
PROTECTIVE EARTH CABLE WILL BE CONNETED BETWENN EQUIPMENT AND EC05 A/R
*-0001
EARTH BOSS.
17. OGLAEND STARTER BRACKET IS DIRETLY WELDED ON DECK PLATE/STRUCTURE THE 10:11:28 +05'30'