Professional Documents
Culture Documents
Training Material
Training Material
1. CABLE SIZING
4. CT AND PT SIZING
5. EARTHING CALCULATION
The cable that is used for the transmission and distribution of electrical power is known as the
electrical power cable. It is used for the transmission of high voltages in places where overhead
lines are impractical to use.
The power cable is made of three main components, namely, conductor, dielectric, and sheath.
The conducting path for the current in the cable is provided by the conductor. The insulation
or dielectric withstands the service voltage and isolates the live conductor with other objects.
The sheath does not allow the moistures to enter and protects the cables from all external
influences like chemical or electrochemical attacks and fire.
Exercise:
1. Cable Sizing and selection based on load.
2. Cable schedule preparation for ACDB.
AUXILIARY TRANSFORMER SIZING
Auxiliary transformers are used for lighting purposes, heating the train wagons or for
producing single-phase auxiliary for the safety systems supply or the substation's own supply.
Total load connected to the Auxiliary Transformer = Maximum Load (kW) x Diversity Factor
KVA = kW/Power factor
Oil Filtration socket load = kW/Power Factor
Total load connected = Maximum load KVA+ Oil filtration Socket load
Criteria For size selection:
The simultaneous peak load excluding oil treatment filtration is < 80% of total capacity.
Exercise:
1. Auxiliary Power Transformer Sizing
2. MCC Transformer Sizing
EMERGENCY DIESEL GENERATOR SIZING
An emergency diesel generator supplies electrical power to a facility during a blackout (loss of
power). The emergency generator bus bar is typically isolated from the main bus. Power is
distributed to electrical loads that are classified as 'critical' for plant operations.
DG Selection Details :
Current Transformer:
A Current Transformer (CT) is used to measure the current of another circuit. CTs are used
worldwide to monitor high-voltage lines across national power grids. A CT is designed to
produce an alternating current in its secondary winding that is proportional to the current that
it is measuring in its primary.
Current Transformer Lead Resistance Calculation:
Page 39 of 58
Page 40 of 58
7UT85
Technical Data
12.1 General Device Data
Current Inputs
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Protection-class current trans- Rated current Irated Measuring range of Measuring range of the
formers the modular devices non-modular devices
5A 0 A to 500 A 0 A to 250 A
1A 0 A to 100 A 0 A to 50 A
Instrument transformers 5A 0 A to 8 A 0 A to 8 A
1A 0 A to 1.6 A 0 A to 1.6 A
Burden for rated current Approx. 0.1 VA
Thermal rating 20 A continuously
(protection and instrument trans- 25 A for 3 min
formers) 30 A for 2 min
150 A for 10 s
500 A for 1 s
Dynamic load-carrying capacity 1250 A one half wave
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
GIS-LPCT input Primary rated current Irated Measuring range
Kr ⋅ GIS-LPCT secondary rated value Kpcr = 50 (protection channel)
Kr = Transformation ratio of the Kpcr = 1.6 (measuring channel)
GIS-LPCT (DIGSI setting)
Refer to the GIS manual for the GIS-
LPCT secondary rated value.
Power consumption per current Max. 40 mVA
circuit at rated current Burden = 9.5 kΩ
Thermal rating Max. input voltage = 20 V
Accuracy Class 5TPE (protection channel)
Class 0.2S (measuring channel)
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Input and output modules IO102, IO202, IO208, IO211, IO215
IO214
Measuring range 0 V to 200 V 0 V to 7.07 V
Burden < 0.1 VA < 0.01 VA
Thermal rating 230 V continuously 20 V continuously
Current Transformers
Parameter Description
ALF Accuracy limit factor
ALF' Operational accuracy limit factor
The operational accuracy limit factor is derived from the connected burden Rbc:
Protected Object
Parameter Description
ISC Int Maximum symmetrical short-circuit current in the event of an internal fault
ISC Ext Maximum symmetrical short-circuit current in the event of an external fault (a fault
current flowing through)
IrTr Rated current of the transformer
vsc Short-circuit voltage of the transformer
IrG Rated current of the generator
x"d Sat Saturated direct-axis synchronous reactance of the generator
IrM Rated current of the motor
IAM Motor starting current
IAM trans Max. motor starting current (transient starting current after starting from a standstill)
Requirements for Transformer Differential Protection to Dimension the Phase and Neutral-Point Current
Transformers
The requirements for current transformers are derived from observing the internal and external short circuit.
The protection system must remain stable for the external short circuit and must trip safely for the internal
short circuit due to potentially high short-circuit currents.
IEC Class At Least Internal Fault External Fault
Required ALF'
5P, 10P196 25
(up to 80 % remanence)
Remanence leads to a premature saturation which is crucial for differential protection. For new plants,
Siemens recommends anti-remanence cores in classes 5PR, PXR and TPY. In case high direct current compo-
nents are expected, Siemens recommends class TPZ, in order to avoid overfunction with external faults. Avoid
using different classes of current transformer at measuring points. This is the particularly the case when
196 Phase displacement is not specified in IEC 61869-2. Class 10P is not recommended for differential protection.
197 Phase displacement is not specified in IEC 61869-2. Class 10PR is not recommended for differential protection.
As the burden can be considerable different for three-phase faults and phase-to-earth faults it
is important to consider both cases. Even in a case where the phase-to-earth fault current is
smaller than the three-phase fault current the phase-to-earth fault can be dimensioning for the
CT depending on the higher burden.
In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case and therefore the resistance of the single secondary wire always can be
used in the calculation, for this case.
The current transformer ratio is mainly selected based on power system data for example,
maximum load. However, it should be verified that the current to the protection is higher than
the minimum operating value for all faults that are to be detected with the selected CT ratio.
The minimum operating current is different for different functions and normally settable so
each function should be checked.
The current error of the current transformer can limit the possibility to use a very sensitive
setting of a sensitive residual overcurrent protection. If a very sensitive setting of this function
will be used it is recommended that the current transformer should have an accuracy class
which have an current error at rated primary current that is less than ±1% (for example, 5P). If
current transformers with less accuracy are used it is advisable to check the actual unwanted
residual current during the commissioning.
M11616-3 v2
With regard to saturation of the current transformer all current transformers of high
remanence and low remanence type that fulfill the requirements on the rated equivalent
limiting secondary e.m.f. Eal below can be used. The characteristic of the non remanence type
CT (TPZ) is not well defined as far as the phase angle error is concerned. If no explicit
recommendation is given for a specific function we therefore recommend contacting ABB to
confirm that the non remanence type can be used.
The CT requirements for the different functions below are specified as a rated equivalent
limiting secondary e.m.f. Eal according to the IEC 61869-2 standard. Requirements for CTs
specified according to other classes and standards are given at the end of this section.
The CTs connected to the IED must have a rated equivalent secondary e.m.f. Eal that is larger
than or equal to the required equivalent secondary e.m.f. Ealreq below:
Busbar protection REB650 © Copyright 2013 ABB. All rights reserved 225
Application manual
Page 44 of 58
Section 16 1MRK 505 287-UEN B
Requirements
Isn
E al ³ E alreq = 2 × U s = 2 × I tmax × × (R CT + R L )
I pn
where:
Us Set operate value to the voltage relay (V)
Ikmax Maximum primary fundamental frequency fault current for through fault current for external faults (A)
RL The resistance of the secondary cable from the CT up to a common junction point (Ω). The loop
resistance containing the phase and neutral wires, must be used for faults in solidly earthed systems
and the resistance of a single-phase wire should be used for faults in high impedance earthed
systems.
All CTs to the same protection should have identical turn ratios. Consequently auxiliary CTs
cannot normally be used. The IED must be provided with separate cores.
The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the
required secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = 5 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
EQUATION1380 V1 EN-US (Equation 33)
where:
Iop The primary operate value (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A and SR=0.250 VA/
channel for Ir=5 A
The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the
required secondary e.m.f. Ealreq below:
226 © Copyright 2013 ABB. All rights reserved Busbar protection REB650
Application manual
Page 45 of 58
1MRK 505 287-UEN B Section 16
Requirements
Isn æ S ö
E al ³ E alreq = 1, 5 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
EQUATION1381 V1 EN-US (Equation 34)
where:
Iop The primary operate value (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A and SR=0.250 VA/
channel for Ir=5 A
The requirement according to Equation 35 and Equation 36 does not need to be fulfilled if the
high set instantaneous or definitive time stage is used. In this case Equation is the only
necessary requirement.
If the inverse time delayed function is the only used overcurrent protection function the CTs
must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the required
secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = 20 × I op × × ç R CT + R L + R2 ÷
I pn è Ir ø
EQUATION1076 V1 EN-US (Equation 35)
where
Iop The primary current set value of the inverse time function (A)
RL The resistance of the secondary cable and additional load (W). The loop
resistance containing the phase and neutral wires, must be used for faults
in solidly earthed systems. The resistance of a single secondary wire should
be used for faults in high impedance earthed systems.
SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for
Ir=1 A and SR=0.250 VA/channel for Ir=5 A
Busbar protection REB650 © Copyright 2013 ABB. All rights reserved 227
Application manual
Page 46 of 58
Section 16 1MRK 505 287-UEN B
Requirements
Independent of the value of Iop the maximum required Eal is specified according to the
following:
Isn æ S ö
E al ³ E alreq max = I k max × × ç R CT + R L + R2 ÷
I pn è Ir ø
EQUATION1077 V1 EN-US (Equation 36)
where
Ikmax Maximum primary fundamental frequency current for close-in faults (A)
If the directional overcurrent function is used the CTs must have a rated equivalent secondary
e.m.f. Eal that is larger than or equal to the required equivalent secondary e.m.f. Ealreq below:
Isn æ S ö
E al ³ E alreq = I k max × × ç R CT + R L + R2 ÷
I pn è Ir ø
EQUATION1078 V1 EN-US (Equation 37)
where:
Ikmax Maximum primary fundamental frequency current for close-in forward and reverse faults (A)
RL The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
SR The burden of an IED current input channel (VA). Sr=0.010 VA/channel for Ir=1 A and Sr=0.250 VA/
channel for Ir=5 A
M11623-4 v3
All kinds of conventional magnetic core CTs are possible to use with the IEDs if they fulfill the
requirements corresponding to the above specified expressed as the rated equivalent limiting
secondary e.m.f. Eal according to the IEC 61869-2 standard. From different standards and
available data for relaying applications it is possible to approximately calculate a secondary
e.m.f. of the CT comparable with Eal. By comparing this with the required rated equivalent
limiting secondary e.m.f. Ealreq it is possible to judge if the CT fulfills the requirements. The
requirements according to some other standards are specified below.
Page 47 of 58
Busbar protection REB650 1MRK 505 290-BEN B
REB 650
Product version: 1.3
Analog inputs
Table 2. TRM — Energizing quantities, rated values and limits for transformer inputs
Description Value
Frequency
Rated frequency fr 50 or 60 Hz
Current inputs
4 A continuously 20 A continuously
Dynamic withstand 250 A one half wave 1250 A one half wave
Voltage inputs**)
420 V continuously
Note! All current and voltage data are specified as RMS values at rated frequency
1) Residual current
2) Phase currents or residual current
ABB 25
Page 48 of 58
RED 670
Page 49 of 58
Section 23 lMRK 505 343-UEN B
Requirements
where:
Maximum primary fundamental frequency fault current for internal close-in
faults (A)
ltmax Maximum primary fundamental frequency fault current for through fault
current for external faults (A)
The rated primary CT current (A)
The resistance of the secondary wire and additional load (n). The loop
resistance containing the phase and neutral wires must be used for faults
in solidly earthed systems. The resistance of a single secondary wire should
be used for faults in high impedance earthed systems.
The burden of an IED current input channel (VA). S R= 0.020 VA/channel for
l, = 1 A and S R= 0.150 VA/channel for l, = 5 A
J
E al > - I tfdb · � · (R ct + R L + SR2
- E alreq -
Ipr Ir
(Equation 564)
where:
lttdb Maximum primary fundamental frequency through fault current that passes two main CTs (one-and
a-half or double-breaker) without passing the protected line (A)
If a power transformer is included in the protected zone of the line differential protection the
CTs must also fulfill equation 565.
(Equation 565)
where:
The current transformers must have a rated equivalent limiting secondary e.m.f. Ea1 that is
larger than the maximum of the required rated equivalent limiting secondary e.m.f. Eaireq
below:
736
Application manual
Page 50 of 58
Page 51 of 58
Page 52 of 58
P543
Page 53 of 58
Page 54 of 58
3ZLWK'LVWDQFH &KDSWHU7HFKQLFDO6SHFLILFDWLRQV
5$7,1*6
$&0($685,1*,13876
$&0HDVXULQJ,QSXWV
1RPLQDOIUHTXHQF\ +]RU+]VHWWDEOH
2SHUDWLQJUDQJH WR+]
3KDVHURWDWLRQ $%&RU&%$
&855(1775$16)250(5,13876
$&&XUUHQW,QSXWV
1RPLQDOFXUUHQW,Q $RU$
1RPLQDOEXUGHQSHUSKDVH 9$DW,Q
$FRQWLQXRXVRSHUDWLRQ
$&FXUUHQWWKHUPDOZLWKVWDQG$LQSXW $IRUV
$IRUV
$FRQWLQXRXVRSHUDWLRQ
$&FXUUHQWWKHUPDOZLWKVWDQG$LQSXW $IRUV
$IRUV
6WDQGDUG/LQHDUXSWRî,QQRQRIIVHW$&FXUUHQW
/LQHDULW\
6HQVLWLYH/LQHDUXSWRî,QQRQRIIVHW$&FXUUHQW
92/7$*(75$16)250(5,13876
$&9ROWDJH,QSXWV
1RPLQDOYROWDJH9Q 9WR9RU9WR9SKDVHSKDVH
1RPLQDOEXUGHQSHUSKDVH 9$DW9Q
99VXSSO\99VXSSO\FRQWLQXRXVRSHUDWLRQSKDVHSKDVH
7KHUPDOZLWKVWDQG
[9QIRUVHFRQGV
/LQHDUXSWR99VXSSO\
/LQHDULW\
/LQHDUXSWR99VXSSO\
$8;,/,$5<6833/<92/7$*(
&RUWHFRSWLRQ'&RQO\
WR9'&
&RUWHFRSWLRQUDWHGIRU$&RU'&RSHUDWLRQ
WR9'&
1RPLQDORSHUDWLQJUDQJH
WR9$&UPV
&RUWHFRSWLRQUDWHGIRU$&RU'&RSHUDWLRQ
WR9'&
WR9$&UPV
3[=70(1
Page 55 of 58
Bay control REC670 1MRK511231-BEN E
Customized REC 670
Product version: 1.2
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Table 6. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) × Ir
Frequency fr = 50/60 Hz ± 5%
30 ABB
Page 57 of 58
EARTHING CALCULATION
Sl.No. Input Details Description Legend Unit Input Value
3.1 For conductor selection (As per Kenya spec. clause no:
tc sec. 1.00 4.1.2.9.2, Page-91 of 223)
3.2 For step and touch potential calculations t sec. 1.00
4 Depth of burial (As per Kenya spec. clause
h m 0.80 no:4.1.2.9.4, Page-93 of 223)
5.1 Soil Resistivity (Design value for safety) As per Soil resisitivity Table
r Ohm-m 23.94
Annexure -A
5.2 Surface Resistivity From IEEE-80,Table7,Page
rs Ohm-m 5000.00
no.52.
5.3 Thickness of Surface layer hs m 0.15
6 Material used for Earthing (GI/Cu) Cu
7.1 Design Ambient Temperature for conductor (As per Kenya spec. clause
Ta deg.C 40.00 no:3.1.5, Page-29 of 223)
sizing
Reference Standards :
1 IEEE-Std. 80-2000 - IEEE Guide for Safety in AC Substation Grounding
Earthing Conductor Sizing Calculation
I* 1
A=
TCAP * 10^(-4) * Ln K0 + Tm
tc*ar * rr K0 +Ta
conductor selection
31.5 x 1
A=
(3.42 x 10^-4) Ln 234 + 1083
1 x 0.00393 x 1.72 234 + 40
The proposed size for main mat conductor = 120.00 Sq.mm. Stranded Cu.
Conductor
HENCE SAFE
IIa Determination of Overall Grid Resistance
Rg = r 1 + 1 * 1+ 1
LT (20*A)^0.5 1+ (h*(20/A)^0.5)
Where ,
Rg = Grid resistance
1 1
Rg = 23.94 + 1 * 1+
1428.00 20 X5095.45^0.5 1+(0.8x ( 20/5095.45)^0.5)
Since the Grid potential rise GPR is more than the tolerable touch voltage,
the attainable touch voltage & attainable step voltage will be verified as per IEEE 80 - 2000.
2.) Therefore tolerable step and touch voltages are,
Where,
rs = Surface layer resistivity in ohm-metre = 5000.00 Ohm-m
where na, = 2.Lc/Lp (Reference : Equation No.85 & Page no: 93 of IEEE 80 -2000)
na= 2 X 1425
296.5
na= 9.62
296.5/4 X 5095.45^0.5)^0.5
nb= 1.02
0.7 X 5095.45
100.5 X 56.3 ^
100.5 X 56.3
5095.45
1.070
100.5
SQRT (100.5^2+56.3^2)
nd= 0.88
n na*nb*nc*nd
Hence, n= 9.24
kii= 1 (Corrective Weighting Factor
As per IEEE-80, & Page no: 93 - 2000)
HENCE SAFE
1 1 1 1
Ks = + + 1-[0.5^(n-2)]
P 2*h D+h D
where,
Es = (rKs*Ki*Ig)/Ls
HENCE SAFE
I Maximum Grid Current (IG)
where
IG is the maximum grid current in A
Df is the decrement factor for the entire duration of fault
Ig is the symmetrical grid current in A
I g = Sf x I (IEEE 80 2000 & Page no: 73; Clause 15.1.4; Equation 65)
Sf = Zeq / (Zeq + Rg) (IEEE 80 2000 & Page no: 82; Clause 15.9)
where
Sf is fault current division factor
Zeq is Equivalent impedance of Transmission line OH shield wires & Distribution feeder neutrals
Since GPR is higher than the allowable value, we proceed with the calculation of Step
& Touch Voltages and check whether they are within tolerable limits.
Conclusion :
Since the Attainable Values of the Step and Touch Voltages are lesser than
the Tolerable Values, the Proposed Earthing Design is safe.
.
CL TOWER/
CABLE
SEALING END
CL BUILDING
WALL
X X X
X
X
X
X
X
CL BUILDING
X
WALL
X
X
CL NCT
X
X
X
X
X X X
CL TRAFO
ROAD CROSS
ROAD CROSS
CL 4M ROAD
CL CABLE
SEALING END/
LLM
LLM
CL LA
CL CT
CL CB
CL TOWER
0.00 REFERENCE:
The direct stroke lightning protection calculation is based on "DIN VDE 0101" method
1 INPUT
Height of Control room Lightning pole H = 18 m
Height of Object to be Protected, Y Y = 4 m
The lightning rod forms the protected zone, by an Arc whose Middpoint is three
times the height (H) of the rod both from ground leven and the tipe of the lightning
R = 54
rod, Hence radius of ARC,
3 CONCLUSION
Effective radius of single Lightning Spike (Rx) for the object to be protected at the ht 4m is 19.853 m
1 of 4
0.00 REFERENCE:
The direct stroke lightning protection calculation is based on "DIN VDE 0101" method
1 INPUT
Height of Lightning mask with Spike H = 24.3 Meters
Height of Object to be Protected, Y Y = 5.85 Meters
The lightning rod forms the protected zone, by an Arc whose Middpoint is three
times the height (H) of the rod both from ground leven and the tipe of the lightning
R = 72.9
rod, Hence radius of ARC,
3 CONCLUSION
Effective radius of single Lightning Spike (Rx) for the object to be protected at the ht 5.85m is 25.723 Meters
2 of 4
0.00 REFERENCE:
The direct stroke lightning protection calculation is based on "DIN VDE 0101" method
1 INPUT
Height of Lightning Line tower with Spike H = 16.15 Meters
Height of Object to be Protected, Y Y = 4.3 Meters
The lightning rod forms the protected zone, by an Arc whose Middpoint is three
times the height (H) of the rod both from ground leven and the tipe of the lightning
R = 48.45
rod, Hence radius of ARC,
3 CONCLUSION
Effective radius of single Lightning Spike (Rx) for the object to be protected at the ht 4.3 16.158 Meters
3 of 4
0.00 REFERENCE:
The direct stroke lightning protection calculation is based on "DIN VDE 0101" method
1 INPUT
Height of Lightning Line tower with Spike H = 6.6 Meters
Height of Object to be Protected, Y Y = 3.6 Meters
The lightning rod forms the protected zone, by an Arc whose Middpoint is three
times the height (H) of the rod both from ground leven and the tipe of the lightning
R = 19.8
rod, Hence radius of ARC,
3 CONCLUSION
Effective radius of single Lightning Spike (Rx) for the object to be protected at the ht 3.6 3.374 Meters
4 of 4