Power Transmission and Distribution Service er

General

SICAM PAS CC
SICAM PAS CC
stands for
is a
Process visualisation system SICAM
for SICAM PAS Power Automation System
Control Center

SICAM PAS CC
The basis for SICAM PAS CC
enlarges SIMATIC WinCC
is
SIMATIC WinCC V6.0 for the use of SICAM PAS
in the Substation automation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 2
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Components
 Initialization of WinCC-Projects
 Import of SICAM-PAS engineering data
SICAM PAS
Wizard
SICAM-spezific
Communi-  Objects
Library
cation  Functiones
 Diagrams

SIMATIC
WinCC

 Analysis of
measured SICAM Switchgear-  IndustrialX-Controls
and counter Valpro objects
values

SICAM
Recpro  Request and evaluation of fault records

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 3
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Communication

Ethernet (TCP/IP) is used for the


Commununication to SICAM PAS

ÜbersichtsBild fehlt

 The SICAM-specific Channel.dll manages the event


based data exchange with one or more SICAM PAS
Station Units

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 4
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS Wizard


After setting a new station in the project the following steps takes place
 Import / Update of SICAM PAS – Data
o Import of SICAM PAS variables in the tag management
o Import of SICAM PAS indications
in the alarm logging
o Import of SICAM PAS measured
and counter values in the tag
logging
o Generation of the SICAM
specific structure variables and
the required internal variables

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 5
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS Wizard II


The SICAM PAS Wizard initializes the project

• Import of the SICAM symbol


library
• Setting of the SICAM specific
information system
• Setting of the SICAM text
library

• The initialization of the project can be done independent of the data


import. Therefore the configuration of the SICAM PAS CC project
can be started before readiness of the SICAM PAS projects.
• The SICAM reporter records the activities of SICAM PAS Wizards
and provides information about success respectively failures and
warnings.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 6
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

The Symbol Library includes...


 Objects for the presentation of
control units
 Objects for the visualization of
measured and counter values
 Template for the alarm logging

 and furthermore
 Elements for operation like

 Dialogue to supervise the entries into event lists


 Herewith it can be defined which actualization results
entries into the event lists

 Dialogue for the operation of the switching authority


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 7
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Schwitchgear Objects I
• IndustrialX-Controls are used for the visualization and controlling of the
• switching devices
• The SICAM objects for switching devices
– Circuit breaker
– Disconnector
Supports 4 visualization options
– SICAM
– DIN 42200
– IEC 445
– LSA

– If symbols are required deviating from these display options, the


different conditions particularly defined ' bit-maps ' can to be
assigned (the best performance is reached with the gif-format)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 8
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Switchgear Objects II
Display of status
– Clear visualization of the status 'not up-to-date' and
'WinCC status not ok'
– Additionally the status 'bay interlocking' and
'substituted' are visualized
– Additionally the status can be displayed in
text form in a pop-up window using the
right hand mouse key

– The coloured representation of the status can


be defined by the user

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 9
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Switchgear Objects III


To distinguish between synchronized and unsynchronized operation, a
dynamic function can be implemented.
The control dialogue is extended accordingly and during operation
the user can select how to control the command.
• Runtime-Dialog
• Configuration Dialog

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 10
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Switchgear Objects IV
The switching devices are controlled in two steps with IndustrialX Controls
 1st operation step: Selection of the switching direction
 2nd operation step: Initiation of switching execution
If a connected device supports „Select before Operate“, this two-step
operation can be combined with this characteristic.

• Further characteristics

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 11
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Switchgear Objects V
 Further parameters are available in the WinCC setting menu
– EnableSwitching
 In dependence of other variables the control dialogues and thus the controllability can be prevented at
run-time
Ex.: switching authority between several control PC‘s in a WinCC Client/Server configuration.
– PermissionLevel
 Permission for operation
– LabelButtonOn, …
Object specific texts for the runtime can be defined with these parameters, e.g. higher/lower
 Support of other languages
– In the scope of supply the two languages German and English are supported
– All texts which are used in configuration and Runtime dialogs are deposited in text files.
– These can be copied and the texts be translated in other languages.
 Others
– The IndustrialX Controls are applicably in multi-client and web navigator environment.
– ‚Variable-Prefix in screen window‘ are supported (=>Typical-Diagrams)
‚Indirect addressing‘ is supported
– These objects are only used for monitoring direction
(a missing entry of the control variables doesn't result in a control dialog but deactivates the left mouse
button)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 12
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Alarm Logging – Message Lists


 The original absolute time stamp created directly in IED or in IED-connection are recorded in
the alarm logging
 In the event lists are recorded besides the time stamp and the status of the indication also further
additional information like cause, source, status information, …
 The display of values in SICAM PAS CC-Alarm logging includes besides the ON/OFF also
– Intermediate position (double indications)
– Bit pattern
 Text values
– The text values can be parameterized specifically, e.g. higher/lower.
– Up to 8 different text groups can be created.
 Command indications are recorded additionally to the process indication
 The logic of the acknowledgement can be selected in the alarm lists,
it can be acknowledged
– Raised
– Cleared
– Raised and Cleared
The entry of the raised status be kept in the alarm list until the reception of the clear status
and eventually the acknowledge of the cleared status.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 13
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

Connection States

Status of the IED connections and its information

 If the connection is lost the colour for the switching devices and the
measurement objects change.
 Connection state of devices can be visualized in the display
 Connection state of IEDs can be logged In the alarm logging
 Connection state between PAS and WinCC can be visualized with an
independent object from the library

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 14
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS CC Licences

SIMATIC WinCC License: • Amount of variables (Tags)


• Runtime V6 • 128
• Runtime & Configuration V6 • 256
SICAM
• 1.024 License
Disk
• 8.000 SIMATIC
License
• 64.000 Disk V6

PAS CC Licenses:
• Runtime for list functions (Event List / Alarm List etc.)
• Configuration for use of PAS Wizard (Data import / Initialization)
• VALPRO / RECPRO optional

*) Note: For each PAS-Information object, several WinCC tags are created in the tag
management;
in terms of authorisation, only one Tag per PAS-information-object is counted.
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 15