SICAM PAS CC
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er
General
SICAM PAS CC
SICAM PAS CC
stands for
is a
Process visualisation system SICAM
for SICAM PAS Power Automation System
Control Center
SICAM PAS CC
The basis for SICAM PAS CC
enlarges SIMATIC WinCC
is
SIMATIC WinCC V6.0 for the use of SICAM PAS
in the Substation automation
Components
Initialization of WinCC-Projects
Import of SICAM-PAS engineering data
SICAM PAS
Wizard
SICAM-spezific
Communi- Objects
Library
cation Functiones
Diagrams
SIMATIC
WinCC
Analysis of
measured SICAM Switchgear- IndustrialX-Controls
and counter Valpro objects
values
SICAM
Recpro Request and evaluation of fault records
Communication
ÜbersichtsBild fehlt
and furthermore
Elements for operation like
Schwitchgear Objects I
• IndustrialX-Controls are used for the visualization and controlling of the
• switching devices
• The SICAM objects for switching devices
– Circuit breaker
– Disconnector
Supports 4 visualization options
– SICAM
– DIN 42200
– IEC 445
– LSA
Switchgear Objects II
Display of status
– Clear visualization of the status 'not up-to-date' and
'WinCC status not ok'
– Additionally the status 'bay interlocking' and
'substituted' are visualized
– Additionally the status can be displayed in
text form in a pop-up window using the
right hand mouse key
Switchgear Objects IV
The switching devices are controlled in two steps with IndustrialX Controls
1st operation step: Selection of the switching direction
2nd operation step: Initiation of switching execution
If a connected device supports „Select before Operate“, this two-step
operation can be combined with this characteristic.
• Further characteristics
Switchgear Objects V
Further parameters are available in the WinCC setting menu
– EnableSwitching
In dependence of other variables the control dialogues and thus the controllability can be prevented at
run-time
Ex.: switching authority between several control PC‘s in a WinCC Client/Server configuration.
– PermissionLevel
Permission for operation
– LabelButtonOn, …
Object specific texts for the runtime can be defined with these parameters, e.g. higher/lower
Support of other languages
– In the scope of supply the two languages German and English are supported
– All texts which are used in configuration and Runtime dialogs are deposited in text files.
– These can be copied and the texts be translated in other languages.
Others
– The IndustrialX Controls are applicably in multi-client and web navigator environment.
– ‚Variable-Prefix in screen window‘ are supported (=>Typical-Diagrams)
‚Indirect addressing‘ is supported
– These objects are only used for monitoring direction
(a missing entry of the control variables doesn't result in a control dialog but deactivates the left mouse
button)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 12
s
Powe
Train r
in
Cent g
Power Transmission and Distribution Service er
Connection States
If the connection is lost the colour for the switching devices and the
measurement objects change.
Connection state of devices can be visualized in the display
Connection state of IEDs can be logged In the alarm logging
Connection state between PAS and WinCC can be visualized with an
independent object from the library
PAS CC Licenses:
• Runtime for list functions (Event List / Alarm List etc.)
• Configuration for use of PAS Wizard (Data import / Initialization)
• VALPRO / RECPRO optional
*) Note: For each PAS-Information object, several WinCC tags are created in the tag
management;
in terms of authorisation, only one Tag per PAS-information-object is counted.
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – Local Operator Station PAS CC
PTD-SE-A1/ 15