Professional Documents
Culture Documents
Introduction
This application guideline gives an overview of some reasons to move from traditional CT to LPCT,
what is a LPCT and how to configure them in eSetup Easergy Pro (at least V3.0.0).
Further details, such as how to wire the LPCT or the VT adapter is described in the user manual in
the “Installation” chapter.
Benefits of LPCTs
In short, the use of Low Power Instrument Current Transformers brings many benefits through-out
the project lifecycle, which are detailed below.
With LPCT technology, due to its specific design, there is no longer any danger in the event of
accidental opening of the secondary circuit, as the output is always low voltage:
• The 1 A or 5 A ICT secondary current is replaced by either 22.5 mV, 150 mV, or 225 mV in
LPCTs.
• As these secondaries can be left open or short-circuited without risk, there is no longer the
need for short-circuit devices that were designed to mitigate those risks.
2. One LPCT can replace the needs of dedicated measurement and protection CTs
As LPCTs commonly saturate much later than ICTs, they can allow fault measurement ranging
from 5 kA to 80 kA primary.
The measurement accuracy of an LPCT could range from 5% of rated primary current to the
extended primary current. It may be specified as class 0.1, 0.2, 0.5, or 1.
However, its protection accuracy could range from the extended primary current to the
accuracy limit of primary current. It may be specified as either class 5P, 10P or 5TPE.
*Because LPCTs have an extended rated primary current range, their application scope is
much wider, the LPCT primary rating is no longer required to be as close as possible to the
nominal current, and therefore no longer a major determining factor in specifications.
In this example, a multipurpose normalized LPCT with a 100 A rated primary current and a
1000 A extended primary current can be used in place of the 10 different Inductive Current
Transformers (ICTs) with the following primary currents:
100, (125), 150, 200, (250), 300, (400), 500, (600), 750** (but not 1000**)
** An ICT has an extended primary current equal to only 120% of its rated current.
If we know that the initial nominal current to be measured is between 100 and 750 A, we can
order a 100 A rated LPCT with 1000 A extended primary current and still be flexible to last-
minute changes or when load flow may increase subsequently.
Same example, a multipurpose normalized LPCT with a 100 A rated primary current and a
1000 A extended primary current can be used in place of the 13 different ICTs with the
following primary currents:
25, 50, 100, (125), 150, 200, (250), 300, (400), 500, (600), 750 and 1000
If we know that the initial nominal current for protection is between 25 and 1000 A, we can
order a 100 A rated LPCT with 1000 A extended primary current and still be flexible to last-
minute changes or when load flow may increase subsequently.
Standardized products can now be used with a wider range of application, providing faster and
simpler integration. No longer do you need to wait for CT sizing clarifications, because fewer
designs cover the majority of requirements, providing many other benefits.
The size and weight of the Low Power Current Transformers are reduced to less than 10%
compared to ICTs. This allows future switchgear designs to be more compact, reducing
materials used and the environmental impact. Switchgear handling, transport, installation and
replacement are also much simplified.
LPCT characteristics
The multipurpose LPCT is designed to measure from 5% of Ipr to kalf x Ipr and is defined with a:
• Rated primary current (Ipr) (minimum current for measuring accuracy class)
• Rated extended primary current (Iepr = Ipr*Kpcr) (maximum current for measuring accuracy
class)
• Rated accuracy limit (Ikpr = Ipr*kalf) (maximum current for protection accuracy class)
For example, the Schneider Electric LPCTs have the following characteristics:
The P3 LPCT input measuring range is 50 In. That means 25 In fully offset:
The selection for the LPCT is done in eSetup Easergy Pro (at least V3.0.0), at the creation of the
configuration file once the “Voltage measurement +I/O, X5” has been set to the option C in “Phase
currents and voltage input X1:”:
P3 LPCT configuration
Unlike CTs that need to meet the application CT requirements, LPCTs do not have any.
LPCT suitability needs to be calculated according to the two following main rules:
The maximum short circuit (IfMax) must be below the LPCT protection rated accuracy limit:
• IfMax < Ikpr
a. Select the LPCT rated primary current (Ipr) in “LPCT rated nominal current”
b. Set the primary nominal current (In) in “Protection nominal current”
• Below the LPCT rated accuracy limit divided by 25: In < Ikpr/25
• Below the LPCT rated extended primary current: In < Iepr whenever possible
• Above 20% of the LPCT rated primary current In > Ipr/5
• As close as possible to the nominal load current and among the standardized
values.
For example, with a multipurpose LPCT with a 100 A rated primary current, a 1250 A extended
primary current and an accuracy limit of 16000 A:
1. The maximum short circuit must be below the LPCT rated accuracy limit:
a. IfMax < Ikpr: 10 kA < 16 kA (OK)
2. The maximum nominal current to be set in the P3 relay must be:
a. Below the LPCT rated accuracy limit / 25: In < Ikpr/25: 16000/25 = 640 A (OK)
b. Below the LPCT rated extended primary current: In < Iepr: < 1250 A (possible)
c. Above 20% of the LPCT rated primary current In > Ipr/5: 20 A (OK)
d. As close as possible to the nominal load current and among the standardized
values:
a. 100, (125), 150, 200, (250), 300, (400), 500, (600), 750, 1000 and (1250)
1. The maximum short circuit must be below the LPCT rated accuracy limit: IfMax < Ikpr: 20
kA < 16 kA
This is NOT OK, a different LPCT must be chosen, for example, a multipurpose LPCT with a
100 A rated primary current, a 1250 A extended primary current and an accuracy limit of 25000 A
3. The maximum short circuit must be below the LPCT rated accuracy limit: IfMax < Ikpr: 50
kA < 16 kA
This is NOT OK, a different LPCT must be chosen, for example, a multipurpose LPCT with a
100 A rated primary current, a 1250 A extended primary current and an accuracy limit of 50000 A
Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison
FRANCE © 2020 Schneider Electric Industries SAS - All rights reserved.
Electrical equipment should be installed, operated, serviced,
Phone: +33 (0) 1 41 29 70 00 and maintained only by qualified personnel. No responsibility
Fax: +33 (0) 1 41 29 71 00 is assumed by Schneider Electric for any consequences
www.schneider-electric.com arising out of the use of this material.
Publishing: 10/2020