You are on page 1of 2

101J Seal Gas Operation: 102J Seal Gas System: 103J Seal Gas System:

The steam flows through a trip and throttle 102J uses dry gas seals on the compressor. The 103J uses dry gas seals on the compressor. The
valve, FV 431, which is provided with open and seal has a primary and secondary seal internally seal has a primary and secondary seal internally
closed valve position indicators, ZSO 431 and as well as two outer carbon barrier seals. There as well as two outer carbon barrier seals. There
ZSC 431, to the governor valve set. The trip and are four internal ‘chambers’ on the upstream are four internal ‘chambers’ on the upstream
throttle valve seal leak off steam is routed to the side of each of the internal seals. side of each of the internal seals.
second and fourth turbine seal chambers for use
as sealing steam while the governor valve set The buffer gas for these seals is normally from The buffer gas for these seals is from the
seal steam leak off is routed to the fourth seal the discharge of the compressor through line discharge of the compressor through line
chamber and the 6th stage wheel of the turbine. NG1055 1" and associated non-return valve. A SG1425 1" through a non-return valve. A start
nitrogen supply line with a non-return valve has up supply line from 104 F has also been installed
Sealing steam for the turbine seals is normally also been added for start-up when the discharge with a non-return valve to use when the
provided by the leakage from the high-pressure pressure is not high enough to flow into the discharge pressure is not high enough to flow
inlet side seal first chamber to the exhaust end seals. The 160 scfm flow of seal gas passes into the machine. The 485 SCFM flow of seal gas
seal first chamber. If the leakage is not enough through a set of filters at 732 psig and 150 F that passes through a set of filters at 1,353 psig and
to satisfy the steam demand, additional LP remove particles larger than 3 microns in size. A 154 F that remove particles larger than 3
steam will be introduced through PIC 432 seal differential pressure indicator PDI 650 indicates microns in size. A differential pressure indicator
steam control valve. If there is too much leakage the filter pressure drop and PDAH 32650 will PDI 33100 indicates the filter pressure drop and
from the seal system causing the pressure to go alarm if the pressure drop exceeds 20 psig. The PDAH 33100 alarms if the pressure drop
too high, PIC 432 is split ranged to a dump valve filters are set up using a three-way valve so that exceeds 20 psig. The filters are set up using a
that will dump the excess seal steam to the one filter is in service at a time but switching to three-way valve so that one filter is in service
surface condenser. A gland condenser has also the spare filter can be accomplished with the but switching to the spare filter can be
been provided to take the leakage that passes unit in service. PI 650 will indicate the incoming accomplished with the unit in service. PI 33100
the seals to the outer seal chambers and seal gas pressure from the machine. will indicate the incoming seal gas pressure
condense the steam in the fresh cooling water from the machine.
cooled gland condenser shell where it is sent to The seal gas, after passing through the filters, is
the outfall sewer drain through a seal loop. A jet pressure controlled by PDIC 651 to 10 psig The seal gas, after passing through the filters, is
ejector using LP motive steam provides the above the pressure in the compressor balance pressure controlled by PDIC 33101 to 10 psi
driving force by pulling a slight vacuum on the line (basically compressor suction pressure) above the pressure in the compressor balance
gland condenser shell.  which is what the initial seal is sealing against. line (suction pressure), which is what the initial
An alarm, PDAL 32651 will sound locally and seal is sealing against. An alarm, PDAL 33101
indicate in the DCS on PDAL 32651A if this will sound locally and in the DCS on PDAL
differential pressure drops to 3 psig. The seal 33101A if this differential pressure drops to 3
gas is then directed to the inner most ‘chamber’ psig. The seal gas is then directed to the inner
of the compressor seals on each end of the most ‘chamber’ of the compressor seals on each
compressor casing. The flow of seal gas is end of the compressor casing. The flow of seal
monitored locally by two pressure differential gas is monitored locally to each seal by pressure
indicators, PDI 652 to the inlet end seal and PDI differential indicators, PDI 33102 to the inlet
653 to the drive end seal. Most of the seal gas is end and PDI 33103 to the drive end.
recycled back into the machine as it flows past
the seal and into the machine and it serves to Some seal leakage is expected and will be
keep the seal faces clean. vented to the atmosphere from the second
most inner ‘chamber’ in the seal. This leakage is
Some seal leakage is expected and will be guaranteed to be less than 4.5 scfm for each
vented to the atmosphere from the second seal. This flow is monitored by two pressure
most inner ‘chamber’ in the seal. This leakage is differential indicators, one for each seal, PDI
guaranteed to be less than 2.2 scfm for each 33105 from the inlet end seal and PDI 33108
seal. The leakage flow is monitored by PDI 655 from the drive end seal. The backpressure on
from the inlet end seal and PDI 658 from the this seal vent is manually controlled using
drive end seal. An alarm, PDAH 32655 on the needle valves to maintain 20 psig. An alarm,
inlet end seal and PDAH 32658 on the drive end PDAH 33105 on the inlet end seal and PDAH
seal, will sound if the leakage flow becomes 33108 on the drive end seal, will sound if the
great enough to cause a 1 psid differential leakage flow becomes too great. A second alarm
across the orifice. A second alarm PDAH 32654 PAHH 33104 for the inlet end and PAHH 33107
for the inlet end and PDAH 32657 for the drive for the drive end, will sound if the pressure in
end, will sound if the pressure in the vent lines the vent lines exceeds 30 psig and will trip the
exceeds 15 psig and will trip the machine. The machine. The vent lines are protected by
vent lines are also protected by rupture discs rupture discs PSE 33106 for the inlet end vent
PSE 656 and PSE 659 which will rupture at 21 and PSE 33109 on the drive end vent will
psig. rupture at 51 psig.

The third ‘chamber’ in the seal vents leakage, The third ‘chamber’ in the seal vents leakage,
that is trying to flow toward the outer, lower that is trying to flow toward the outer, lower
pressure portion of the seal, to the atmosphere. pressure portion of the seal, to the atmosphere.
Nitrogen, at 10 psig and an expected flow of 4.2 Nitrogen, at 10 psig and an expected flow of 4.2
scfm, is pressure controlled in the fourth and scfm, is pressure controlled in the fourth and
outer most ‘chamber’ of the seal to force any outer most ‘chamber’ of the seal to force any
third ‘chamber’ leakage out the vent line and third ‘chamber’ leakage out of the vent line and
not allow it to leak out of the end of the seal not allow it to leak out of the end of the seal
housing. The nitrogen is controlled by PCV 660 housing. The nitrogen is controlled by PCV
from the plant nitrogen header. PDI 662 33110 from the plant nitrogen header. PDI
measures and indicates locally the difference 33112 measures and indicates locally the
between the nitrogen pressure and the vent difference between the nitrogen pressure and
header backpressure. If this pressure should the vent header backpressure. If this pressure
drop below 5 psig, an alarm PDAL 32662 will should drop below 3 psig, an alarm PDAL
sound. This 5 psig is a start permissive and 33112 will sound. This 3 psig is a start
resetting of the turbine governor will not be permissive and resetting of the turbine governor
possible until this pressure is met. Flow will not be possible until this pressure is met.
indicators have been added to each nitrogen Flow indicators have been added to each
seal supply line to allow the operators to visibly nitrogen seal supply line to allow the operators
confirm that nitrogen is flowing.  to visibly confirm that nitrogen is flowing. 
seal supply line to allow the operators to visibly
105J Seal Gas System: confirm that nitrogen is flowing.

105J uses dry gas seals on both of the The buffer gas for the high-pressure case seals is
compressor cases. The seals have a primary and normally supplied from the discharge of the
secondary seal internally as well as two outer compressor case through line NH1116 1" with
carbon barrier seals and there are four internal an associated non-return valve. During start
‘chambers’ on the upstream side of each of the up, before the machine has built up sufficient
internal seals. discharge pressure to supply the buffer gas,
nitrogen is tied into the seal gas inlet piping
The low-pressure case buffer gas for the seals through a check valve to supply the seals until
on this case is normally supplied from the final the discharge pressure is high enough to
discharge of the compressor through a pressure overcome the nitrogen pressure and starts
control valve in line NH1116 1" with an supplying ammonia to the seal buffer system.
associated non return valve. During start
up, before the machine has built up sufficient The 140 scfm flow of seal gas passes through a
discharge pressure to supply the buffer gas, set of filters at 222 psig and 150 F that remove
nitrogen is tied into the seal gas inlet piping particles larger than 3 microns in size. A
through a check valve to supply the seals until differential pressure indicator PDI 140 indicates
the discharge pressure is high enough to the filter pressure drop and PDAH 35140 will
overcome the nitrogen pressure and starts alarm if the pressure drop exceeds 20 psig. The
supplying ammonia to the seal buffer system. filters are set up using a three-way valve so that
one filter is in service but switching to the spare
The 95 scfm flow of seal gas passes through a filter can be accomplished with the unit in
set of filters at 45 psig and 150 F that remove service. PI 35140 indicates the incoming seal gas
particles larger than 3 microns in size. A pressure from the machine.
differential pressure indicator PDI 35120
indicates the filter pressure drop and PDAH The seal gas, after passing through the filters, is
35120 alarms if the pressure drop exceeds 20 pressure controlled by PDIC 141 to 10 psig
psig. The filters are set up using a three way above the pressure in the compressor balance
valve so that one filter is in service but switching line which is what the initial seal is sealing
to the spare filter can be accomplished with the against. An alarm, PDAL 33141 sounds locally
unit in service. PI 35120 indicates the incoming and in the DCS on PDAL 35141A if this
seal gas pressure from the machine. differential pressure drops to 3 psig. The seal
gas is then directed to the inner most ‘chamber’
The seal gas, after passing through the filters, is of the compressor seals on each end of the
pressure controlled by PDIC 35121 to 10 psig compressor casing. The flow of seal gas is
above the pressure in the compressor balance monitored locally by pressure differential
line which is what the initial seal is sealing indicators, PDI 35142 to the inlet end and PDI
against. An alarm, PDAL 35121 sounds locally 35143 to the drive end.
and in the DCS on PDAL 35121A if this
differential pressure drops to 3 psig. The seal Some seal leakage is expected and will be
gas is then directed to the inner most ‘chamber’ vented to the atmosphere from second most
of the compressor seals on each end of the inner ‘chamber’ in the seal. This leakage is
compressor casing. The flow of seal gas is guaranteed to be less than 1.0 scfm for each
monitored locally by two pressure differential seal. This flow is monitored by pressure
indicators, PDI 35122 to the inlet end and PDI differential indicators, PDI 35145 from the inlet
35123 to the drive end. end seal and PDI 35148 from the drive end seal.
An alarm, PDAH 35145 on the inlet end seal and
Some seal leakage is expected and will be PDAH 35148 on the drive end seal, sounds if the
vented to the atmosphere from the second leakage flow becomes greater than 1 psid across
most inner ‘chamber’ in the seal. This leakage is the orifice. A second alarm PAHH 35144 for the
guaranteed to be less than 1.0 scfm for each inlet end and PAHH 35147 for the drive end,
seal. This flow is monitored by pressure sounds if the pressure in the vent lines exceeds
differential indicators by PDI 35125 from the 15 psig and will trip the machine. The vent lines
inlet end seal and PDI 35128 from the drive end are protected by rupture discs PSE 35146, on
seal. An alarm, PDAH 35125 on the inlet end the inlet end vent, and PSE 35149, on the drive
seal and PDAH 35128 on the drive end seal, end vent, which will rupture at 21 psig. The
sounds if the leakage flow becomes 1 psid ammonia vented is returned to the low case
across the orifice. A second alarm PAHH 35124 suction of 105 J through line NH1119 4".
for the inlet end and PAHH 35127 for the drive
end, sounds if the pressure in the vent lines The third ‘chamber’ in the seal vents leakage,
exceeds 15 psig and will trip the machine. The that is trying to flow toward the outer, lower
vent lines are protected by rupture discs PSE pressure portion of the seal, to the atmosphere.
35126, on the inlet end vent, and PSE 35129, on Nitrogen, at 10 psig and an expected flow of 4.2
the drive end vent, which ruptures at 21 psig. scfm, is pressure controlled in the fourth and
The ammonia vented is returned to the low case outer most ‘chamber’ of the seal to force any
suction of 105 J through line NH1119 third ‘chamber’ leakage out the vent line and
4". not allow it to leak out of the end of the seal
housing. The nitrogen is controlled by PCV 150
The third ‘chamber’ in the seal vents leakage from the plant nitrogen header. PDI 152
that is trying to flow toward the outer, lower measures and indicates locally the difference
pressure portion of the seal, to the atmosphere. between the nitrogen pressure and the vent
Nitrogen, at 10 psig and an expected flow of 4.2 header backpressure. If this pressure should
scfm, is pressure controlled in the fourth and drop below 3 psig, an alarm PDAL 35152 sounds.
outer most ‘chamber’ of the seal to force any This 3 psig is a start permissive and resetting of
third ‘chamber’ leakage out the vent line and the turbine governor will not be possible until
not allow it to leak out of the end of the seal this pressure is met. Flow indicators have been
housing. The nitrogen is controlled by PCV added to each nitrogen seal supply line to allow
35130 from the plant nitrogen header. PDI the operators to visibly confirm that nitrogen is
35132 measures and indicates locally the flowing. 
difference between the nitrogen pressure and
the vent header backpressure. If this pressure
should drop below 3 psig, an alarm PDAL 35132
sounds. This 3 psig is a start permissive and
resetting of the turbine governor will not be
possible until this pressure is met. Flow
indicators have been added to each nitrogen

You might also like