1500 600 3000 2850

COLUMNS C1 (22Nos),

790 2210 790 2060

COLUMNS DETAILS (SCALE 1:30)


kicker

kicker
Size:230X230mm

450
A

A
A

200 200
75 75
12T8-00-150 17T8-00-150 17T8-00-150

Roof beam
4T16-04

4T16-04
1st Floor
Ground floor

A
A

A
4T16-03

G.L

1500 600 3000 2850


790 2210 790 2060
COLUMNS C2 (5Nos),

kicker

kicker
450
B

B
B
Size:Ø230mm

200 200
75 75
14T8-00-125 20T8-00-125 20T8-00-125

Roof beam
6T12-04

6T12-04
1st Floor
Ground floor

B
B

B
6T12-03

G.L

SECTION DETAILS
230

(SCALE 1:20)

SECTION A-A
SECTION B-B

03

03

03

03

230
03

03

03

03
03

03

Ø2
30
NOTES: 1. All dimensions are in millimeters unless otherwise stated. Drawn by: ENG. JOSEPH DAMIAN
2. Foundation might change to suit the subsoil condition of the area as directed by the Engineer.
PROJECT: CLIENT: Drawing Title: Drawing number
Mob: 0762796522 Email: jozedamian@gmail.com
3. The minimum tensile strength of steel reinforcements is 460N/mm² (recommended use of BS 500 Steel Reinforcements, test should be done) PROPOSED NURSERY SCHOOL BUILDING TO BE BUILT AT ANNA LIBERATA DEOGRATIAS
4. The minimum compressive strength of the construction blocks should be 5N/mm² for load bearing wall and 2.5N/mm² for non load bearing wall.
5. The mortar for construction should be of designation (iii)
6. Reinforced concrete shall be of grade C25 (1:1.5:3), and blinding of grade C15 (1:3:6)

YOMBO-KIWALANI, PLOT No.......... BLOCK ........


TEMEKE DISTRICT IN DAR ES SALAAM
P.O BOX ........................
DAR ES SALAAM
COLUMNS DETAILS
Checked by:
Scale:
Date:
AS SHOWN 05
7. Minimum cover to reinforcement shall be as; slabs and beams 25mm, columns 30mm, and foundation in dry soil 40mm OCTOBER, 2022 Revised: Nil