Professional Documents
Culture Documents
EX-1673-2
KING-GAGE ®
D/P Transmitter
4–20 mA Pressure Transmitter
Operation/Calibration
Manual
page 2
KING-GAGE D/P Transmitters EX-1673-2
Thermal Effects
(over compensated temp. range)
less than .007° F (.011%° C) span shift—sensitivity 1/2 -14
NPSF
less than .007° F (.011%° C) span shift—zero
OUTPUT
SIGNAL
Environmental Limits
-40° F to 180° F / -40° C to 82° C operating
(-60° F to 185° F / -51° C to 85° C storage) 1/4 in.
NPT
page 3
KING-GAGE D/P Transmitters EX-1673-2
1 2 3 4
Span
Load Capacity = (Supply Voltage − 12 Volts)
METER
+ Adjustment (ohms) .02
–
TP1 TP2
+
– Zero Load Capacity at Supplied Voltage
Adjustment
20 Vdc 24 Vdc 28 Vdc 32 Vdc 36 Vdc 40 Vdc
- +
400 ohms 600 ohms 800 ohms 1000 ohms 1200 ohms 1400 ohms
Signal Cabling
The 4–20 mA signal loop needs to be run using twisted pair
+VA Vcom (two conductor) cable. “Noise” or EMI (electromagnetic
interference) does not generally create a problem since it
is common to both wires in the pair and essentially cancels
itself out. In most applications, non-shielded twisted pair
instrumentation cable (20–22 awg) will be suitable for
the signal loop between the LP2 and sensor/transmitter.
+ –
Transmitter
+24V
4-20 mA
1 2
– +
page 4
KING-GAGE D/P Transmitters EX-1673-2
Sensor Control V P
P P
page 5
KING-GAGE D/P Transmitters EX-1673-2
Internal Signal Connections 3. Next step is to re-check the zero output and slightly
Screw clamp terminals are provided for positive (+ Signal) adjust if necessary.
and negative (− Signal) or common sides of the signal loop
circuit. As is typical of two-wire transmitters, all electrical
In-Process Zero/Span Adjustment
power is supplied through the signal loop wiring. Refer to
It is possible to make adjustments to the zero setting while
the Current Loop diagram for proper wiring of the circuit
the D/P transmitter is installed at the tank. The meter terminal
with polarity to the external power (+V) source.
posts permit in-process monitoring without disturbing the
loop wiring. Confirm that the tank is empty (or liquid level
Test Point Terminals (TP1, TP2)—Test meter terminals
is below sensor). Measure the transmitter output using a
are provided within the transmitter housing (see diagram)
milliammeter (multimeter) and adjust zero potentiometer
for measuring the output signal without disturbing the
as required.
signal loop. Do not connect any device or meter whose
internal resistance exceeds 20 ohms across these test DIP Switch
points. Also refer to “In-Process Zero/Span Adjustment”
in the following section.
1 2 3 4
Adjusting Zero Setting Using Multimeter: Set multimeter for DC current, using
Check zero by measuring the output using the meter mA or .001 amp scale. The internal resistance of the meter
terminal posts (TP1 & TP2) on the transmitter board. must be 20 ohms or less since higher resistance values will
create incorrect readings. Connect the meter leads to the
1. Adjust zero potentiometer as necessary to TP1 and TP2 posts on the internal circuit board.
increase output (clockwise) or decrease output
(counterclockwise) until the signal displays as 4.00 Adjusting span settings of an installed transmitter is not a
or 4.01 mA on the test meter. very precise method for calibration (since the hydrostatic
pressure may not be accurately determined). In-process
Adjusting Span Setting span adjustment is not recommended for this reason.
This requires applying pressure to the "S" port of the D/P
transmitter equivalent to the maximum depth (hydrostatic)
pressure. Measure the output using the meter terminal
posts on the transmitter board.
page 6
KING-GAGE D/P Transmitters EX-1673-2
1 2 3 4
The four (4) switches provide 16 increments of coarse
adjustment. Prior to changing any switch setting, check ON
the current output of the transmitter at the desired upper
pressure value. Also note the existing switch setting. 1 2 3 4
ON
1. Apply the desired maximum pressure to the sensing
diaphragm of the D/P transmitter (requires a pressure 1 2 3 4
page 7
KING-GAGE D/P Transmitters EX-1673-2
17.0
ON
02
1
2
3 Meter Sensor
4
DIP Switch
P2
DIP Switch—Coarse Adjustment
19.9
ON
70
1
2
Surface of Liquid
3 Meter
4
DIP Switch
P1
Sensor
S E
P1 + P2
S E
High Low
Pressure Pressure
P1 + P2 P2
(P1 + P2) - P2 = P1
page 8
KING-GAGE D/P Transmitters EX-1673-2
DC POWER SUPPLY
+VA
Precision S
Pressure
Regulator
Precision
Compressed 0 160 Pressure
Air Indicator
page 9
KING-GAGE D/P Transmitters EX-1673-2
(382 − 30) × 1.00 = 352" water When Output will be Less Than 20 mA . . .
■ Other Ranges
Figure 1
The above formula may also be used for other nominal
range transmitters if maximum applied pressure will be
less than the adjustment range allows. Merely divide by
the lower span limit psid value (see page 3) in place of the
“3.0” shown in the formula.
page 10
Milk
KING-GAGE D/P Transmitters EX-1673-2
Troubleshooting
No signal
• Check that Vdc power is connected to the signal loop
circuit (V+ at transmitter + signal terminal).
• Polarity reversed—check by reversing the + and − leads
at the input terminals.
The O-ring application is based on the size of the machined groove on the underside of the cover (top plate).
These can be identified by the number of “steps” seen on the top plate. Refer to the illustrations for details.
page 11
KING-GAGE D/P Transmitters EX-1673-2
page 12