Cooling unit
Climatiseur
Koelaggregaat
Kylaggregat
Condizionatore per armadi
Refrigerador para armarios
エンクロージャー用
クーリングユニット
SK 3307xxx
SK 3310xxx
Danger!
Immediate danger to life and limb!
Caution!
Potential threat to the product
and its environment.
Note:
Useful information
and special features.
External circuit
Internal circuit
Temperature
control
Note:
In order to ensure perfect operation of the
climate control door, an enclosure base/
plinth at least 100 mm high is required.
Note:
Take care to ensure that the hinges labelled
“S” are mounted on the top and bottom of
the section door.
CMC
X1 X1 X1 X1
X2 X3 X2 X3 X2 X3 X2 X3
X2 X2 X2 X2 X2
Bu. St. Bu. St. Bu.
3
X2 X2 X2 X2 X2 X2
X10
NPE 1 2 3 4 5
L2
L1
Adr.: 16
1 2 3 4 5 6
3 4 4 3 2
Fig. 20: Connection example: Door limit switch and master-slave operation
Key
1 Master cooling unit
2 Slave cooling units
3 2-door enclosure with two door limit switches
4 Enclosure with door limit switch
SK 3307.700/.710, SK 3310.700/.710
21
PE
Mains S1
5
22
X1 L1 L2
N PE 1 2 3 4 5
X2 X3 A2
T1
3 6
F11
E1
MS1 Serial
12 3 1 2 3 2 1 2
NTC I red B1
L N K1 2
K2
Power S1 NTC E blue B2
Kx 2
NTC C white B3
PE
2
A1 NTC A yellow B4
2
Level green B5
4
Term
F2
2
M1 M2 M4
1 P
3 2 1 1 2 3 1 2 3
A1 F2
A3
1 C4
C12
2 C11
5
S R C2
M M
1~ 1~
C
M1
M2 M4
22
S1
EN
PE
5 A2
X1 L1 L2 L3 PE 1 2 3 4 5
PE
T1 L1 L2 L3
X2 X3
F11 F12 3 8 4
E1
1 3 5 95
F3 2
96
2 4 6
U V P
F2 5 TW 5 TW
W
3~ 3~
M1 M2 M4
Legend
A1 Power PCB Note:
A2 e-Comfort controller For technical data refer to the rating plate.
A3 Starter relay and RC element
B1 Temperature sensor, internal temperature
B2 Icing hazard temperature sensor AC DC
B3 Condenser temperature sensor cos f = 1 L/R = 20 ms
B4 Ambient temperature sensor
B5 Condensate warning sensor (optional) I max. = 2 A I min. = 100 mA
C1.2 Start-up capacitor U max. = 250 V U max. = 200 V
C1.1, U min. = 18 V
C2 – C4 Running capacitors I max. = 2 A
E1 Condensate evaporator
F2 PSAH pressure-operated switch Tab. 2: Contact data
(33xx.1x0 has a jumper instead of a pressostat)
F3 Contact overload protection
F11/F12 Miniature fuses, condensate evaporator
K1 Relay collective fault 1
K2 Relay collective fault 2
M1 Compressor
M2 Condenser fan
M4 Evaporator fan
S1 Door limit switch
(without door limit switch: terminal 1, 2 open)
T1 Transformer (optional)
X1 Main terminal strip
X2 Master-slave connection
X3 Optional interface
EN
= 5 sec.
= 5 sec.
The system messages A1 – A19 may additionally be The NO definition refers to the de-energised state.
evaluated via two floating system message relays. In As soon as power is applied to the cooling unit, the
this way, one of the two system message relays may system message relay picks up, so that the relay
be allocated to each system message. contacts change status (contact 3 – 4 closed; con-
System alarm relay with normally open contact: tact 4 – 5 closed). This is the normal operating state
See wiring diagrams at section “4.5.2 Installing the of the cooling unit. As soon as a system message
power supply”, page 14: occurs or the power supply is interrupted, the relay
– Terminal 3: NO (normally open) K2 drops out.
– Terminal 4: C (connection of the supply voltage to
the system message relay) Program system messages with the value
– Terminal 5: NO (normally open) K1 0: System message is not sent to the system
message relays, but merely appears in the
display
1: System message is evaluated by relay 1
2: System message is evaluated by relay 2
Notes:
– Only one unit may be configured as Master Slave Slave
02 11 12
master, and its identifier must match the
number of connected slave units.
– The slave units must have different Fig. 27: Master-slave connection (example)
identifiers. For further connection examples, see “4.5.1 Bus
– The identifiers must be numbered in connection (only in conjunction with several units
ascending order without any gaps. with an e-Comfort controller)”, page 12.
For details of how to set the identifier, see “6.1.5
Editable parameters”, page 19 or “6.1.6 Program-
On the master cooling unit (00 = factory setting),
ming overview”, page 20, parameter “Ad“.
set the number of slave units present in the network:
01: Master with 1 slave cooling unit 6.1.9 Evaluating system messages
02: Master with 2 slave cooling units In the e-Comfort controller, system messages are in-
03: Master with 3 slave cooling units dicated by a number in the display.
04: Master with 4 slave cooling units Following the appearance of messages A03, A06
05: Master with 5 slave cooling units and A07 and after rectifying their cause, you will
06: Master with 6 slave cooling units need to reset the e-Comfort controller (see “6.1.10
07: Master with 7 slave cooling units Resetting the e-Comfort controller”, page 24).
08: Master with 8 slave cooling units
09: Master with 9 slave cooling units
7.1 General
The cooling circuit is designed in the form of a main-
tenance-free, hermetically sealed system. The cool-
ing unit is filled with the required quantity of refriger-
ant at the factory, checked for leaks, and subjected
to a functional test run.
The installed maintenance-free fans are mounted on
ball bearings, protected against moisture and dust,
and fitted with a temperature monitor. The life ex-
pectancy is at least 30,000 operating hours. The
cooling unit is thus largely maintenance-free. All that
may be required from time to time is to clean the
components of the external air circuit using a vacu-
um cleaner or compressed air if they become visibly Fig. 28: Disconnect the mains plug
dirty. Any stubborn, oily stains may be removed us-
ing a non-flammable detergent, such as degreaser.
Maintenance interval: 2000 operating hours. De-
pending on the level of contamination in the ambient
air, the maintenance interval may be reduced to suit
the air pollution intensity.
Caution!
Risk of fire!
Never use flammable liquids
for cleaning.
Note:
On the right of the climate control module, Fig. 29: Disconnect the connector from the display
below the socket strip, there is a cover plate
to allow easy access to the controller board
for maintenance purposes.
EN
SK 3307.xxx, SK 3310.xxx
EN
75
41
10
55 40
20
90
100
76 30
25 5
71
1 15
101
80
Key
Note:
1 Compressor
5 Condenser fan As well as the spare part number, when or-
10 Evaporator fan dering spare parts the following information
15 Dispatch bag must be provided:
20 Expansion valve – Unit model
25 Filter dryer – Fabrication number
30 PSAH pressure-operated switch – Date of manufacture
40 Controller box
This information may be found on the rating
41 Fuse set, condensate evaporator
55 Display (controller) plate.
71 Temperature sensor
75 Enclosure tray
76 Enclosure tray, fan
80 Transformer
90 Evaporator coil
100 Condenser
101 Condensate evaporator