Professional Documents
Culture Documents
November 2008
Re-liquefaction Unit,
GCU, etc.
Reduction Gear
~ D/E BOG
Propeller BOG Compressor
Propulsion
Motor ~ D/E
~ D/E
F. O.
D/E Tank Cargo Tank
~
November 2008
Copyright © 2008
All rights reserved
These Guidelines describe the construction and applicable rules for dual-fuel diesel engines, the application of
which is anticipated to increase henceforth. The IGC Code and Chapter 16, Part N of the Society's Rules
prescribe the requirements related to the "Use of cargo as fuel", which should apply to dual-fuel diesel engines.
Furthermore, “Annex 3” and “Annex 4”, Part N of the Guidance to the Society’s Rules describe the detailed
requirements for high pressure and low pressure dual-fuel diesel engines, respectively. These Guidelines are
not mandatory, but serve as Guidelines for the Society’s Rules and Guidance to be applied.
Dual-fuel diesel engines are necessarily installed together with other boil-off gas treatment equipment such as
re-liquefaction units and boil-off gas combustion units. This is because, when the ship is in port or during
low-load operation, the dual fuel diesel engines can not use up the generated boil-off gas, and excess boil-off gas
will be consumed by other treatment systems. For this reason, considerations of redundancy are described in
detail in these Guidelines, with space devoted especially to equipment such as re-liquefaction units and boil-off
gas combustion units.
These Guidelines incorporate descriptions given in manufacturer brochures and documents related to the
construction and arrangement of boil-off gas treatment equipment including dual-fuel diesel engines, and are
designed such that the Rules and Guidance of the Society can be easily understood when read in conjunction
with these brochures and documents. We hope that these Guidelines will assist not only surveyors but also
designers, shipbuilders and shipowners in understanding the new designs of equipment related to the treatment
and use of boil-off gas. It should be noted, however, that adequate discussions are necessary between all
parties concerned before the actual design and application of the Rules is to be undertaken.
November 2008
Nippon Kaiji Kyokai
This page has been intentionally left blank.
Table of Contents
4 Re-liquefaction units 29
4.1 Construction 29
4.2 Arrangement 30
4.3 Requirements related to re-liquefaction units 31
4.3.1 Processing ability and redundancy of re-liquefaction units 31
4.3.2 Cargo / BOG circuit 31
4.3.3 Refrigerant circuit 33
4.3.4 Monitoring, alarms and safety devices 34
8 Redundancy 52
8.1 Redundancy of propulsion system 52
8.2 Capacity and redundancy of BOG treatment equipment 53
References 55
Chapter 1 Boil-off gas treatment equipment
The cargo carried in a liquefied gas carrier is a gaseous substance under normal temperature and atmospheric
pressure. This gaseous substance can be transported in bulk in large volumes by liquefying it. In
low-temperature liquefied gas carriers, the substance is cooled down to below its saturated steam temperature at
atmospheric pressure, based on the saturated steam pressure-temperature diagrams of the said substance to
liquefy it. This temperature is -42.1˚C for propane, one of the substances carried onboard low-temperature
LPG carriers, and is -161.5 ˚C for methane, another substance commonly carried onboard LNG carriers.
Low-temperature liquefied gas carriers transport cargo at such very low temperatures and at the boiling point
state of normal pressure (not overcooled state). Accordingly, when heat from outside enters the liquid cargo
after permeating through the insulating material provided around the cargo tank, it causes a rise in the
temperature of the liquid cargo, which in turn generates evaporative gas, that is, boil-off gas (hereafter referred
to as "BOG"). This process is also accompanied by a rise in pressure in the cargo tank.
The design pressure of the cargo tank of a low-temperature liquefied gas carrier is generally about 0.25 bar. To
ensure that the pressure in the tank does not exceed the design pressure, the IGC Code and classification society
rules require the installation of a suitable cargo pressure and/or temperature control system.
Paragraph 7.1.1, Chapter 7 of the IGC Code classifies pressure and/or temperature control systems as follows:
(a) A system that regulates the pressure in the cargo tanks by the use of mechanical refrigeration
This refers to what is commonly referred to as the re-liquefaction unit.
(b) A system whereby the BOG is utilized as fuel for shipboard use or waste heat system
Combustion by dual fuel boiler or dual fuel diesel engine and BOG combustion unit, etc.
(c) A system allowing the product to warm up and to increase in pressure
Design wherein insulating material and/or the design pressure of the cargo tank have adequate margin in
terms of usage hours and temperatures encountered
Until now, BOG has been burned as fuel in the main boiler to drive a steam turbine for propulsion. However,
presently, the re-liquefaction unit of (a) and the BOG combustion unit of (b) are also actually used. When
combined together with the adoption of the dual fuel diesel engine, the number of such units installed is likely to
increase. On the other hand, the system referred to in (c) above has a low probability of being used in
low-temperature LNG carriers because of economic reasons.
The total capacity of BOG treatment equipment fitted onboard ships should not be greater than the designed
BOG rate under the conditions of sea water temperature of 32˚C and an atmospheric temperature of 45˚C
(paragraph 7.1.2 of the IGC Code). In existing standard LNG carriers, the boil-off rate (BOR) is planned to be
in the range of 0.1 to 0.15% per day, considering the cost of insulating work and other economic reasons.
1
Chapter 2 BOG utilization systems
In this chapter examples in which BOG is used as fuel for propulsion or generator engines are introduced.
Although BOG can be fully utilized only by the main boiler and dump condenser in steam turbine systems
provided with the same equipment, in other systems, the complete system is constructed by combining
re-liquefaction unit, BOG combustion unit and other components as required. Here, examples are given of
heavy fuel oil-fired diesel propulsion engines with re-liquefaction units, electric propulsion system using dual
fuel diesel generator engines, and dual fuel diesel propulsion engines, in addition to a steam turbine system.
The steam turbine system including equipment on the cargo tank side is described, and overviews of other
systems are given with the focus on the propulsion system.
When the required propulsive force is not obtained by natural BOG alone, either multi-fuel combustion that is
continued while replenishing any shortfall with heavy fuel oil, or BOG mono fuel combustion that relies on
forcibly vaporized LNG may be used to operate the main boiler. Generally, a forcing vaporizer is installed for
this purpose (see Figure 2.1).
To vent mast
Gas Heater
BOG Line
L.D. Compressor
F.O. Cargo
Boiler Tank
Forcing Vaporizer
Pump
Turbine Dump
Condenser
In a steam turbine system, steam is generally used for power generation in addition to propulsion. Two
generators driven by a steam turbine and one generator driven by a diesel engine are popular configurations.
Excess BOG is generated during low-load operation of the main engine or while the ship is in port. In this case,
excess steam generated during combustion in the main boiler is disposed of by the dump condenser, and excess
heat is disposed of by sea water (see Figure 2.2).
Compared to a diesel engine system, a steam turbine system has a considerably low plant efficiency; thus, this
system has almost never been used in general merchant ships other than LNG ships where the main boiler was
used as the BOG treatment system. It is also true that crew members familiar with steam turbines are in short
supply; therefore, training and educating crew members has also become an important area of concern.
2
Chapter 2 BOG utilization systems
However, in recent years, steam turbine systems with efficiency levels equivalent to those of diesel engines are
being developed, which employ a reheating system that increases the temperature and pressure of the steam.
Main boiler
Electric
Load
Dump Condenser
Reduction
Gear
BOG Compressor BOG
~ S/T
H. P. Turbine
~ S/T
F. O.
L. P. Turbine Tank
Cargo Tank
~ D/E
3
Chapter 2 BOG utilization systems
Electric
Load
BOG
Re-liquefaction
Units
2-stroke ~ D/E
Main Engine
~ D/E
2-stroke
Main Engine F. O.
~ D/E Cargo Tank
Tank
Figure 2.3 Oil-fired diesel engine propulsion system with re-liquefaction unit.
4
Chapter 2 BOG utilization systems
2.3 Electric propulsion system using dual fuel diesel generator engines
A system that uses BOG as fuel for power generating diesel engines and driving propulsion motors is the most
common system replacing the steam turbine system. In this case, two propulsion motors and four generating
sets are generally provided. The generating sets are installed as two independent groups in a gastight generator
room, or all four sets are installed in one generator room with gas fuel supply piping made of double wall pipes.
A four-stroke electronically-controlled engine is used as the principal power generating engine. Marine diesel
oil is supplied for igniting the engine, and either marine diesel oil or heavy fuel oil is supplied as back-up fuel
(see Figure 2.4).
In this system only the minimum quantity of heavy fuel oil required may be provided as fuel; thus, the ship's
weight can be reduced, and as a result, a greater quantity of LNG can be transported. Moreover, since this is an
electric propulsion system, the advantages are that both vibration and noise are minimal, and plant efficiency is
higher than that of a steam turbine propulsion system.
However, a re-liquefaction unit or a BOG combustion unit must be provided in such a system to treat the excess
BOG generated while the ship is in port or during low-load operation. Redundancy is required in both cases,
similar to the system described in Section 2.2 above. The reliability and maintainability of the power
generating engines are also problems in this system. When the sealing effect of piston rings degrades in a
trunk-piston type dual fuel diesel engine used as a power generating engine, BOG leaks into the crankcase, and
the risk of crankcase explosion arises due to blow-by and bearing failure. Accordingly, equipment such as gas
leak alarms need to be installed in the crankcase, and more meticulous maintenance of the piston rings and liners
than for general diesel engines is necessary.
Reduction
Gear ~ D/E BOG Compressor BOG
(if a reliquefaction
Propulsion unit is installed)
Motor ~ D/E
~ D/E
F. O.
Tank Cargo Tank
~ D/E
Figure 2.4 Electric propulsion system using dual fuel diesel generator engines.
5
Chapter 2 BOG utilization systems
The BOG treatment system includes a re-liquefaction unit and/or a BOG combustion unit, similar to those
mentioned in Section 2.3, for treatment of excess BOG generated while the ship is in port or during low-load
operation.
(if a reliquefaction
2-stroke ~ D/E unit is installed)
Main Engine
~ D/E
2-stroke
Main Engine F. O.
~ D/E Cargo Tank
Tank
6
Chapter 3 Dual fuel diesel engines
3.1 General
To be effective, dual fuel diesel engine (hereafter called "DFD engine”) must be capable of maintaining stable
combustion of gas fuel under any circumstance. Unlike fuel oil, methane gas does not ignite even when
injected by itself into a cylinder. For this reason, whatever be the load, fuel oil is used for ignition. Presently,
this kind of ignition method is considered a basic requirement for ensuring stable combustion of gas fuel.
A DFD engine must continue stable operation even under the following conditions.
Fuel oil is used not only for ignition during gas combustion but also as back-up fuel. A DFD engine must
satisfy the general requirements below related to fuel use.
- Only oil fuel is, in principle, to be used when the operation of a DFD engine is unstable, and/or during
maneuvering and port operations.
- DFD engines must be capable of being transferred quickly from the mode of simultaneous combustion of
both gas and fuel oils to the mode of combustion on fuel oil only.
The method of gas injection in a DFD engine is basically classified into two types: low pressure type and high
pressure type. The low pressure method is generally used in four-stroke trunk piston-type engines. Gas fuel
is injected during the intake stroke of the engine. After suction into the cylinders in the air-mixed condition,
ignition and combustion of the gas fuel occur after the pilot fuel oil is injected and ignited at the final stage of
the compression stroke. The design is such that gas fuel supply pressure is always greater than the charged air
pressure since gas fuel is supplied to the combustion chamber or to the air inlet pipe just before the air inlet
valve. Generally, a low-pressure DFD engine is used as a power generating engine.
On the other hand, the high pressure method is generally used in two-stroke low speed crosshead-type engines.
In this case, the pilot fuel oil is injected in the final stage of the compression stroke, and immediately afterward,
the high pressure gas is injected directly into the cylinders so that ignition and combustion occur at this time.
Generally, a high-pressure DFD engine is used as a direct-coupling type of propulsion engine.
7
Chapter 3 Dual fuel diesel engines
3.2.1 Combustion
The combustion cycle of the Wärtsilä 50 DF engine 1) is shown in Figure 3.1 as an example of a four-stroke
DFD engine. This engine can operate by switching between two operating modes, namely the gas mode and
diesel mode, with the combustion cycles corresponding to the Otto cycle and the Diesel cycle, respectively.
Air
Gas is injected at a low pressure of about 5 bar during the intake stroke in the gas mode. The mixture of gas
and air is compressed, and a small quantity of pilot fuel oil is then injected into the cylinder near the top dead
center to ignite the mixture. The pilot fuel oil consists of commonly used marine diesel oil. Operation in the
diesel mode is the same as the operation of the typical diesel cycle.
Figure 3.2 shows the transition of operating mode when marine diesel oil is used in the diesel mode; however,
heavy fuel oil may also be used in the 50DF engine. 2)
8
Chapter 3 Dual fuel diesel engines
In the gas mode, abnormal combustion may occur with a rapid rise in pressure or the so-called 'knocking' due to
the air-fuel ratio. A combustion sensor (knocking sensor) is fitted to the top of the cylinder cover to detect the
high frequency vibrations that occur during knocking in the engine. The signal output from the combustion
sensor is input into the control system, and combustion is controlled in each cylinder in such a way as to prevent
knocking.
The effects of the air-fuel ratio on the combustion characteristics of the 50DF engine are shown in Figure 3.4.
As is clear from the figure, the operating window related to the air-fuel ratio is restricted in order to prevent
knocking and misfiring, but controls are implemented in this range in order to optimize the combustion
characteristics; that is, thermal efficiency is high and NOx emissions are minimum.
20
Knocking
BMEP (bar)
18
NOx emissions (g/kWh)
Thermal efficiency (%)
16
14
12
10
Operating
8 window
6
4
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
Air/Fuel ratio
9
Chapter 3 Dual fuel diesel engines
Gas mixed with air is admitted into the combustion chamber in the gas mode. For this reason, the air / fuel
mixture in the combustion chamber becomes homogeneous, and the local formation of NOx can be avoided.
This contributes to reducing NOx emissions from the engine.
To obtain the optimum air-fuel ratio in any operating condition, the quantity of air must be adjusted by
controlling the turbocharger speed as well as adjusting the flow of gas fuel. For this reason, piping to bypass
the turbocharger is arranged for the exhaust pipe, and a valve called the exhaust waste-gate is provided in this
pipeline to adjust the amount of exhaust gas supplied to the turbocharger. The opening / closing of the exhaust
waste-gate is controlled by the engine control system based on the load, rpm, charged air pressure, and the
exhaust temperature (see Figure 3.5).
P I
T
Exhaust
T/C
Air
10
Chapter 3 Dual fuel diesel engines
The gas supply manifold has a full double wall pipe construction. The branch pipe from the manifold to each
cylinder is also provided with an appropriate cover, and thus is of a construction similar to that of a substantial
double-wall pipe construction. The gas fuel pipe also has a double wall construction at the flange connecting
the manifold and the branch pipe. Protective covers are fitted that completely cover the gas admission valves
and bellows. Thanks to these measures, even if gas leaks from the gas admission valve, the leaked gas is
passed through the intermediate space of the branch pipe and the intermediate space of the manifold, where it is
led to a vent pipe and finally emitted from gas-safe areas. (See Figure 3.6)
Double bellows
Flame arrester
Air flow
Filter
Leaking gas way
to air flow
Air space around
gas admission valve
Although the gas fuel supply pipe in the engine room consists of a double wall pipe construction, as described
later in Section 6.7, it has a single wall pipe construction in the gas valve unit room adjacent to the engine room.
The intermediate space of the double wall pipe is ventilated by a mechanical exhaust fan installed for ventilation
of the gas valve unit room. In this case, one of several methods can be used to intake air into the intermediate
space of the double wall pipe.
A typical method is to provide an air intake port at the end of the gas supply manifold (opposite side of the gas
inlet), as shown in Figure 3.7(a), which is generally used in steam turbine ships. Although the existence of an
opening in the engine room is of concern, even if the inner pipe of a double wall pipe is damaged and gas leaks,
the leaked gas will not be emitted into the engine room from the air intake port because the exhaust fan is always
in operation. If gas leaks, and if for some reason, the exhaust fan stops, the leaked gas may be emitted from the
air intake port, but the premise of the IGC Code and classification society rules is basically single fault, and this
kind of situation is not considered.
11
Chapter 3 Dual fuel diesel engines
Other methods include the arrangement of a double wall vent pipe at the end of the manifold up to the outside of
the engine room. This makes it possible to intake air directly from the outside of the engine room into the
intermediate space of the fuel supply pipe. In this case, even if the exhaust fan stops, leaked gas will not be
emitted into the engine room and safety is enhanced; however, additional work is necessary to extend the double
wall vent pipe to the outside of the engine room (see Figure 3.7(b)).
Gas flow
Air flow
Engine room
Air inlet to
intermediate space Vent Air inlet to Vent
intermediate space
(a) (b)
Figure 3.7 Air intake ports to intermediate spaces of gas fuel double wall pipe.
12
Chapter 3 Dual fuel diesel engines
The pilot fuel oil is adjusted to a specific pressure by a radial piston type engine-mounted pump and is led to the
fuel injection valve of each cylinder through a common rail pipe. The common rail pipe serves the role of
accumulating oil pressure and inhibiting fluctuations in pressure. Injection of the pilot fuel oil is electronically
controlled by a solenoid valve mounted in the fuel injection valve. The pilot fuel oil is injected into the
cylinder at a pressure of approximately 900 bar.
On the other hand, the back-up fuel oil is pressurized by a camshaft-driven fuel injection pump, and led to the
fuel injection valve. The fuel injection mechanism is the same as that of the fuel injection valve of diesel
engines generally used.
Solenoid
Fuel injection pumps
Return fuel
Injection
valves
high pressure pilot fuel
Return fuel
Engine control
system
difference
Pressure
Pressure
Booster Pilot
pump fuel
unit unit
Figure 3.8 Control of pilot fuel oil and backup fuel oil.1)
13
Chapter 3 Dual fuel diesel engines
Figure 3.9 shows a cross-sectional view of the construction of the gas injection valve. For fuel oil, the opening
/ closing of valve is controlled according to the injection pressure of the fuel oil, but the opening / closing of the
gas injection valve is controlled by the hydraulic oil (control oil). This valve is in the open condition only
when the pressure of the control oil has increased.
To vent.
Cylinder
cover Control oil
Seal oil
Gas spindle
Gas inlet
To prevent gas at high pressure from mixing with the control oil during the time when the valve is closed,
sealing oil is filled in the clearance of the spindle, and the pressure is set to be higher by about 25-50 bar than
the gas pressure. This sealing oil is used to lubricate the spindle. The consumption of sealing oil is small at
about 0.1 g/bhph. The consumed sealing oil is burnt in the combustion chamber.
To prevent gas leakage from the mounting part of the valve, a seal ring with good durability against high
temperature and gases is provided between the gas injection valve and the cylinder cover. Moreover, even
assuming that gas leaks through this seal ring, any leaked gas will be led to the ventilation space of the double
wall pipe through a hole provided in the cylinder cover and the gas injection valve for this purpose, and the gas
leak will be detected by a gas detector.
14
Chapter 3 Dual fuel diesel engines
Fuel modes of the ME-GI engine may be any of the three types listed below (see Figure 3.10).
Gas Gas
Fuel oil
Fuel
Fuel
Fuel oil
Fuel
Fuel oil
8% 8%
100% load 100% load 100% load
(a) (b) (c)
15
Chapter 3 Dual fuel diesel engines
Gas raised to a pressure of 250-300 bar by a high pressure gas compressor is led to the engine using single wall
gas fuel pipe in the cargo area, and a double wall gas fuel pipe in the engine room. The space between the
inner pipe (gas pipe) and the outer pipe of the double wall pipe, and the space around the valve and flange
connected to this space, are always ventilated. Ventilated air is taken in from gas-safe areas and forcedly
ventilated by exhaust draft fans having an exhaust capacity of 30 air changes per hour. The relevant spaces are
always in a state of negative pressure compared to the engine room.
Pilot oil
V1
V2 Vent air Suction fan for
V3 intake double pipe system
Valve block Compressor
unit
Vent/purge line
V1: Shutdown valve
V2: Blow-off valve
V3: Purge valve Ventilation system Gas supply system
16
Chapter 3 Dual fuel diesel engines
The ME-GI engine is provided with two sets of gas injection valves and two sets of pilot fuel valves per cylinder.
Gas is supplied to the gas injection valve through the valve block. A valve block is a cast steel block
consisting of the elements listed below, and is secured by bolts to the cylinder cover.
- Accumulator
- Gas shut-off valve
- Purge valve
- Blow-off valve
Gas is accumulated into the accumulator via a check valve. The pressure in the accumulator is measured each
time gas is injected. When a pressure drop exceeding 20-30 bar is detected, a gas leak from the seat part of the
gas injection valve or damage to the gas pipe is indicated; therefore subsequently, the safety device activates and
gas injection stops.
Gas accumulated in the accumulator is led to the shut-off valve (V1) through the hole in the valve block. During
the gas injection period, the shut-off valve is maintained in the open condition by the compressed air. The gas
is led to the gas injection valve through a hole in the cylinder cover and through the valve block from the
shut-off valve. A blow-off valve (V2) installed on top of the valve block is used to blow the gas in the gas
passage when necessary. A purge valve (V3) is also installed on top of the valve block. This valve releases
gas in the accumulator, and is used to stop the operation in the gas mode.
The leaked gas from each valve arranged on the valve block is led to the ventilation space of the double wall
pipe through the vent hole in the valve block. The construction is such that the gas detector installed in the
ventilation space can detect a gas leak regardless of the valve from which gas has leaked.
(3) Controlling the gas injection valve and pilot fuel valve
Figure 3.12 shows the change in the control oil pressure for gas injection valves and pilot oil injection pressure
due to the crank angle in the normal dual-fuel mode. Pilot oil is supplied by a fuel oil pressure booster, which
is controlled by an ON/OFF valve known as the electronic fuel injection (ELFI) valve. Gas injection is
controlled by an ON/OFF valve known as the electronic gas injection (ELGI) valve. When the ELGI valve is
open, it increases control oil pressure to open the two gas injection valves fitted on the cylinder cover.
800
Pressure (bar abs)
400
Control oil pressure
200
0
0 5 10 15 20 25 30 35 40 45
Figure 3.12 Pilot oil pressure and control oil pressure (dual-fuel mode).4)
17
Chapter 3 Dual fuel diesel engines
If the pilot oil does not ignite during dual fuel operation for some reason, there is always a risk of unburnt gas
being emitted into the exhaust gas system. However, the design is such that if the injection pressure of the
pilot oil is inappropriate, gas will not be supplied to the gas injection valve.
The ELFI / ELGI valves and their actuators are built into the hydraulic cylinder unit (HCU) together with the
exhaust valve actuator and fuel oil pressure booster, as shown in Figure 3.13. The control oil is supplied by
engine-driven pump and electric pump. The construction of these pumps is similar to that of the general
electronically-controlled engine (ME engine).
Alpha
lubricator Cyl. 1 CCU Cyl. 2 CCU Cyl. 3 CCU Cyl. 4 CCU Cyl. 5 CCU Cyl. 6 CCU
Safety and
accumulator
block
Figure 3.13 ME-GI engine hydraulic oil loop with common rail gas supply.5)
18
Chapter 3 Dual fuel diesel engines
Fuel oil is used to start-up the engine, and the entire quantity of BOG generated is sent to this combustion unit.
Combustion of the fuel oil is continued until the engine load reaches approximately 30%. The high pressure
gas compressor starts together with the start of the engine, and the gas fuel pipe is purged with N2 at 8 bar.
After purging, the gas fuel is sent to the engine. When the gas in the accumulator of each cylinder reaches the
specified pressure and the gas fuel shut-off valve attached to the cylinder opens, preparations for gas injection
are completed.
Gas combustion occurs when the engine load is greater than 30%. The pressure of the gas led from the high
pressure gas compressor is controlled so that it is always constant (250 bar). That is, based on the difference
between the preset value and measured value of gas pressure, the quantity of gas discharged from the high
pressure gas compressor is adjusted so that the preset value is reached.
Engine momentarily
Momentary Gas burned in Recirculation change to HFO when gas
shut off of gas 100%
BOF oxidiser of gas pressure is reduced to less
supply system to buffer tank than 200 bar (Gas pipes and
valves are flushed with N2)
Compressor Compressor
19
Chapter 3 Dual fuel diesel engines
During a ballast voyage, the ship is generally operated by retaining the LNG required just for the voyage to the
cargo loading site in the cargo tanks. In this case, BOG sufficient for 100% engine operation will not be
generated, so operation in the dual-fuel mode is continued while replenishing the shortfall with fuel oil.
Conversely, if more BOG than the quantity required is generated during a full-load voyage, the minimum limit
of fuel oil is used as pilot fuel, and the excess gas is burnt in the BOG combustion unit.
When the gas supply is stopped during engine operation, the master gas fuel valve is closed, and all the gas
generated is burnt in the BOG combustion unit. When the gas fuel pressure drops below 200 bar, the operation
is switched over immediately to the fuel-oil-only mode after the gas fuel shut-off valve fitted to the cylinder is
closed. The gas pipes and valves between the master gas fuel valve and the gas fuel shut-off valve are then
purged with nitrogen.
20
Chapter 3 Dual fuel diesel engines
Table 3.1 shows the items to be monitored according to the Guidance of the Society. Excluding items not
required to be monitored by FMEA and so on, the items listed in Table 3.1 are at a minimum be monitored.
When an abnormality is found, the gas fuel supply to the engine is to be cut off automatically and controls are to
be implemented so that the engine can be operated by fuel oil.
21
Chapter 3 Dual fuel diesel engines
Since an oil film is present on the inner wall of the vent pipe, if a fire or explosion occurs in the crankcase or in
the mist box, there is always the risk that the fire may propagate in the pipes resulting in widespread damage.
In such pipes, a flame arrester is generally provided at the open end of the pipe, but sometimes this flame
arrester may be omitted for any of the following reasons:
- The mist box in the funnel has a low probability of an outbreak of fire.
- There is a low probability that flames due to the explosion in the crankcase will propagate through the vent
pipe.
- The wire gauze (flame arresting screen) becomes clogged with oil.
22
Chapter 3 Dual fuel diesel engines
Since there is a possibility of gas leaks into the crankcase in a DFD engine, any oil mist and leaked gas must
both be led to a safe location using the vent pipe. In this case, considering only the leaked gas, the general
procedure is to lead the gas to the vent mast in the cargo area, but if discharging the oil mist simultaneously is to
be considered, then it may be preferable to lead the gas to the mist box in the funnel instead because of the
reasons mentioned below.
Vent pipes from pressure relief valves of the cargo tanks and the gas fuel supply piping are assembled in the vent
mast, and wire gauze is provided at the open ends of these vent pipes. However, this wire gauze is meant to
prevent the ingress of foreign matter, and is not a flame arresting screen. This is because an outbreak of fire in
the vent mast is unlikely; moreover, ingress of flames from the vent pipe into the vent mast also cannot be
visualized.
On the other hand, in the case of the crankcase vent pipe, flames that occur during an explosion in the crankcase
may propagate through the pipe. In particular, if a gas leak occurs in the crankcase of a DFD engine and leaked
gas is also present in the vent pipe, then the probability of propagation of the fire increases. Such a pipe that
could become the source of fire should preferably not be led to the vent mast, where many vent pipes are
assembled. Even if a flame arrester is fitted to the open end of the vent pipe in the vent mast, the possibility of
igniting the gas discharged from other vent pipes cannot be ruled out. For this reason, and considering the
safety of the cargo tanks, the crankcase vent pipe of a DFD engine should preferably be led to the mist box in the
funnel rather than to the vent mast.
Based on the above considerations, the vent pipe of the crankcase leads to the mist box in the funnel under the
conditions mentioned below (see Figure 3.15).
- The crankcase vent pipes of two or more engines are not to be mutually interconnected.
- A flame arrester is to be fitted to the vent pipe.
23
Chapter 3 Dual fuel diesel engines
MIST BOX
FLAME ARRESTER FUNNEL
TO DRAIN
Figures 3.16(a) and 3.16(b) show examples of safety measures used in a low-pressure DFD engine.
Figure 3.16(a) shows an example of the disposition of equipment related to ensuring the safety of gas fuel piping,
air inlet piping, and exhaust gas piping in a DFD engine. The gas detector is generally installed on the vent exit
side of the double wall pipe intermediate space. This is because gas leaking from a gas pipe, joint flange,
bellows, gas admission valve, etc., is likely to accumulate at this location.
A relief valve (or rupture disk) is generally installed in the air intake manifold and exhaust manifold as a
measure against the occurrence of explosion due to a gas leak. A temperature sensor is fitted to the exhaust
pipe of each cylinder. This sensor is used to control the combustion and diagnose the condition of each
cylinder.
Figure 3.16(b) shows an example of the disposition of equipment related to ensuring the safety of the DFD
engine unit. Various kinds of condition monitoring methods using special sensors may be considered to detect
abnormalities in fuel oil injection valves, air intake valves, and exhaust valves,. However, detection of
abnormalities in most cases can generally be performed by monitoring the exhaust temperature in each cylinder.
Oil mist detectors in the crankcase are required to be installed for engines installed in ships to which the Rules
for Automatic Remote Control Systems apply, and not for DFD engines. The gas detector sensor unit in the
crankcase may be installed in the vent pipe (oil mist pipe), as shown in the figure, only when a splash of
lubricating oil in the crankcase is judged to affect the gas detecting function of the detector.
24
Chapter 3 Dual fuel diesel engines
Cylinder
Gas admission valve
with flame arrester
Compressor
Charge air
Relief valve
GAS FUEL G
Double-wall pipe
Gas sensor
Air flow
Relief valve
Gas sensor
Flame arrester
Oil mist detector O
N2
Figure 3.16 Safety measures for trunk-piston type low-pressure DFD engines.
25
Chapter 3 Dual fuel diesel engines
Table 3.4 Monitoring, Alarms and Safety Devices Required for Gas Compressors
Automatic
Items Monitoring Alarm
shut-down
a. Remote stopping from a position which is always and easily
X
accessible, and also from the engine room (1)
b. Emergency stopping from a local position and from the
X
control station (2)
c. Pressure relief valves of the delivery side (in the case of
volumetric gas compressors) (3)
d. Gas inlet pressure (4) Low Low
(X)
X
e. Gas outlet temperature (5) High High High
(X)
X X
f. Lubricating oil pressure (5) Low Low Low
(X)
X X
g. Sealing liquid pressure of shaft seal assembly (5) Low Low Low
(X)
X (7) X (7)
h. Stopping of cooling water supply or cooling water outlet High High High
(X)
temperature (5) X (7) X (7)
i. Loss of control power (5)
X
26
Chapter 3 Dual fuel diesel engines
The exhaust gas of ordinary oil-fired diesel engines for propulsion may be used as the heat source for the
boiler (exhaust gas boiler and composite boiler). In such cases, a linkage with the exhaust gas pipe may be
allowed (see Paragraph 13.16.1-3, Part D of the Rules). Linkage with the exhaust gas pipe may be allowed
even in DFD engines only when the exhaust gas is used as a heat source for the boiler. However,
precautions must always be taken against mixing gas fuel with exhaust gas during operation of the DFD
engine when the exhaust gas is heated by firing of the boiler.
Moreover, in the case of direct reversing DFD engines, a rupture disk is to be installed at the appropriate location
of the starting air manifold as the final means of releasing air (Paragraph 2.5.3-1.(3), Part D of the Rules).
With regard to the connection of the vent pipes, the vent pipe of the crankcase may be connected to the vent pipe
of the lubricating oil sump tank for each DFD engine, as shown in the example in Figure 3.15. However, vent
pipes after connection are to be led to the mist box in the funnel through a flame arrester. The connection of
each vent pipe of the lubricating oil sump tank may also be accepted if each vent pipe of the crankcase is
separately installed.
27
Chapter 3 Dual fuel diesel engines
The vent pipe may be connected to a vent pipe of the same kind (for example, vent pipe installed in the gas
fuel supply pipe) and need not be led independently.
28
Chapter 4 Re-liquefaction units
4 Re-liquefaction units
4.1 Construction
The construction of a re-liquefaction unit varies depending on whether the cargo is LNG or LPG. In cases
where the cargo is LPG such as propane or ethane, the cargo can be condensed (liquefied) by pressurization even
under normal temperature. However, LNG, in which methane is the main component, cannot be liquefied at
normal temperature. To pressurize and liquefy methane, it needs to be cooled to at least below the critical
temperature (-82.5˚C); in practice, it is usually cooled to approximately -150˚C 6). A system diagram of the
Hamworthy LNG re-liquefaction unit 7) 8) is shown in Figure 4.1. The construction of the re-liquefaction unit is
described here referring to the example presented in this figure.
BOG is led to the cargo machinery room from the cargo tank by a low duty compressor, and is compressed to
4.5 bar by two centrifugal compressors after being passed through the pre-cooler. The pressurized BOG is
condensed by the plate-type heat exchanger in the cold box, where it is cooled to about -160˚C, and led to the
gas-liquid separator. The LNG in the gas-liquid separator is returned to the cargo tank. On the other hand, N2
does not condense at a pressure of 4.5 bar, and exists as air bubbles in LNG. Therefore, after separation in the
gas-liquid separator, it is discharged to the atmosphere from the vent mast, or sent to the BOG combustion unit
where it is burned.
M BOG compressor
(-60˚C)
(+25˚C)
To vent or GCU
reservoir
Nitrogen
(+40˚C)
(-140˚C)
Pre-Cooler
BOG
(-110˚C)
Recycling Separator
(-160˚C)
2 3 By-pass
(+90˚C)
1 M E (-160˚C)
29
Chapter 4 Re-liquefaction units
The cryogenic condition needed for BOG re-liquefaction is generated by the compression / expansion cycle
using N2 as the refrigerant. Nitrogen gas at a pressure of 13.5 bar is compressed to a pressure of 57 bar by a
three-stage set of centrifugal compressors. The N2 gas is cooled by sea water or fresh water after compression
at each stage, then led to the pre-cooling unit of a plate-type heat exchanger for cooling to a temperature of about
-110˚C at the relevant part, and then sent to an expander. The N2 gas, which is expanded to a cryogenic
temperature of about -163˚C and a pressure of 14.5 bar, is sent to the supercooling unit of the heat exchanger,
and BOG is liquefied here. Subsequently, the N2 gas is passed through the pre-cooling unit of the heat
exchanger, and returned to the inlet side of the three-stage compressor.
4.2 Arrangement
Figure 4.2 shows an example arrangement of the equipment constituting the re-liquefaction unit illustrated in
Figure 4.1. The re-liquefaction unit is installed in the cargo machinery room in the cargo area. It is necessary
for the BOG compressors and the refrigerant compressors / expanders and related equipment constituting the
re-liquefaction unit to be completely duplicated (100% redundancy), including their drive sources, as described
in section 4.3.1 later. Duplication of the plate-type heat exchanger used for cooling LNG with excess capacity
and the piping is not required. The plate-type heat exchanger consists of the N2 pre-cooler, BOG condensing
unit and LNG supercooler. The plate-type heat exchanger and gas-liquid separator are equipment used under
cryogenic temperatures. Since these items are to be kept segregated from heat in the surrounding areas, they
are enclosed in a special insulated box commonly referred to as a “cold box”.
Equipment in direct contact with cargo, that is, BOG pre-cooler, BOG compressors, and cold box, are arranged
in gas-hazardous areas partitioned by bulkheads. On the other hand, refrigeration equipment (compressors,
expanders, and motors), motors for BOG compressors, etc., are arranged in gas-safe areas.
M
M
M
Pre-cooler
M
BOG compressors
and electric motors
N2 reservoir
30
Chapter 4 Re-liquefaction units
i) A re-liquefaction unit is to be provided with a stand-by affording spare capacity at least equal to the
largest required single unit. A stand-by unit is to consist of a compressor with its driving motor,
control system and any necessary fittings to permit operation independently of the normal service.
ii) A stand-by LNG / refrigerant heat exchanger need not be provided and the fitted LNG / refrigerant
heat exchanger will not be required to have 25% excess capacity over that for normal requirements,
considering that corrosion and fouling problems are not expected in the heat exchangers.
iii) Other heat exchangers utilizing water cooling should have a stand-by or have at least 25 percent
excess capacity.
iv) Separate piping systems are not required.
According to the requirements mentioned above, it is a general practice that one plate-type heat exchanger for
cooling LNG and one gas-liquid separator are provided whereas BOG compressors, N2 gas compressors /
expanders, and N2 gas coolers, etc., are duplicated, as shown in Figure 4.2.
Table 4.1 NK Rules and Guidance Applicable to a Piping System for Re-liquefaction of BOG
Process pressure vessels Chapter 4, Part N of the Rules (Chapter 4 of the IGC Code),
(Pre-coolers, separators, etc.) Requirements related to type C independent tanks described in Chapter
N4, Part N of the Guidance
BOG compressors, LNG pumps Annex 1, Part N of the Guidance
(return pumps), etc
Cryogenic heat exchangers Annex 1, Part N of the Guidance, ASME Section VIII, etc.
(Plate-type heat exchangers)
General requirements on Chapter 6, Part N of the Rules (Chapter 6 of the IGC Code),
materials Chapter N6, Part N of the Guidance
31
Chapter 4 Re-liquefaction units
i) Protection from excessive stresses due to thermal expansion and contraction (Paragraph 5.2.1.2 of the
IGC Code):
Provision is to be made by the use of offsets, loops, bends, mechanical expansion joints such as
bellows, slip joints and ball joints or similar suitable means to protect the piping, piping system
components from excessive stresses due to thermal movement. Where mechanical expansion joints
are used in piping, they are to be kept to a minimum and are to be of the bellows type.
ii) Thermal isolation of low-temperature piping from the hull structure (Paragraph 5.2.1.3 of the IGC
Code):
Low-temperature piping is to be thermally isolated from the adjacent hull structure, where necessary,
to prevent the temperature of the hull from falling below the design temperature of the hull material.
Where liquid piping is dismantled regularly, or where liquid leakage may be anticipated, such as at
pump seals, suitable protection for the hull beneath is to be provided.
iii) Electrical bonding (Paragraph 5.2.1.4 of the IGC Code):
Where piping is separated from the ship’s structure by thermal isolation, provision is to be made for
electrically bonding both the piping and the structure. All gasketed pipe joints and hose connections
are to be electrically bonded.
iv) Relief valves (Paragraph 5.2.1.6 of the IGC Code):
All pipelines or components* which may be isolated in a liquid full condition are to be provided with
relief valves.
* Note:
For example, this refers to following pipelines (Paragraph 5.2.1-7, Part N of the Guidance to the
Rules).
- Pipeline between two adjacent stop valves.
- Pipeline between stop valve and compressor or pump likely to be liquid full. However, where
the relief valve mounted on the compressor or pump is in an effective condition, this requirement
may be dispensed with.
v) Discharging from relief valves (Paragraph 5.2.1.7 of the IGC Code):
Relief valves discharging liquid cargo from the cargo piping system are to discharge into the cargo
tanks, alternatively they may discharge to the cargo vent mast if means are provided to detect and
dispose of any liquid cargo which may flow into the vent system. Relief valves on cargo pumps are
to discharge to the pump suction.
32
Chapter 4 Re-liquefaction units
i) At least two cooling water pumps are be provided and arranged such that they can be switched over
and used when necessary. In this case, one of the pumps may be used for other purposes; however,
even if a pump is being used for other services, it is to be capable of supplying the required quantity
of water.
ii) If sea water is used, the cooling water is to be taken in from at least two sea connections (suctions).
These sea connections are to be arranged on both the port and starboard sides as far from each other
as possible.
33
Chapter 4 Re-liquefaction units
Table 4.2 Monitoring, Alarm and Safety Devices Required for Equipment in Cargo / BOG Circuits
Automatic
Items Monitoring Alarm
shut-down (1)
a. BOG compressors See Table 3.4 of these Guidelines (except for item a. )
High, Low
b. Liquid level in gas-liquid separators
X
30% LEL 60% LEL
c. Gas detection in cold boxes
X X
N2 inlet temperature in cryogenic heat High
d. X
exchangers X
Notes:
(1) Automatic shut-down of BOG compressors.
(2) LEL: Lower explosion limit (or Lower flammable limit).
The monitoring, alarms and safety devices listed in Table 4.3 are required for the N2 compressor (or expander)
used in the refrigerant circuit.
Table 4.3 Monitoring, Alarms and Safety Devices Required for N2 Compressors (or Expanders)
Automatic
Items Monitoring Alarm
shut-down
Pressure relief valves of the delivery side (in
a.
the case of volumetric N2 compressors) (1)
Lubricating oil pressure (in the case of forced Low Low Low
b. (X)
lubricating system) (2) X X
c. N2 inlet pressure X
N2 inlet temperature (in the case of N2 High
d. X
compressors) X
e. Loss of control power (3) X X
Low Low Low
f. Sealing gas pressure (3) (X)
X (5) X (5)
g. Safety systems for the driving units (3) (4) X X
Notes:
(1) See Paragraph 3.2.10 of the Rules for Cargo Refrigerating Installations and Paragraph 16.4.2 of the
IGC Code.
(2) See Paragraph 3.2.1-2 of the Rules for Cargo Refrigerating Installations.
(3) See Paragraph 2.4.2, Annex 1, Part N of the Guidance to the Rules.
(4) See Section 3.3 (steam turbine) and Section 4.3 (gas turbine), Part D, and Section 2.3, Part H of the
Rules.
(5) To be provided with alarms or safety devices.
(6) (x)-marked monitoring may be omitted if alarms or safety devices are installed.
34
Chapter 5 BOG combustion units
5.1 Construction
The BOG combustion unit (generally called the “Gas Combustion Unit“ or “Thermal Oxidiser”; hereafter
referred to as the “GCU“) burns BOG generated in cargo tanks, and is generally installed as a stand-by for the
re-liquefaction unit or the DFD engines. The GCU is required to have compact construction because space for
installing large equipment is limited onboard ship. The GCU should have closed combustion so that flames are
not emitted from the ship and, considering safety, the surface temperature should be restricted to a low level.
Figure 5.1 shows a GCU 9) produced by SAACKE GmbH, and the overall construction of the GCU is described
here referring to this GCU as an example. The GCU consists of a combustion chamber (inner chamber) and an
outer casing. The burners of this GCU consist of one main burner for BOG combustion, two BOG pilot
burners, and two fuel oil pilot burners. The main burner is a swirl-type burner that supplies excess air and
lowers the mean temperature within the combustion chamber; moreover, it also contributes to reducing NOx
emissions.
The combustion gas is discharged into the space between the combustion chamber and the casing through
several nozzles in the upper part of the combustion chamber. Cooling air is supplied by dilution fans fitted to
cool this space; as a result, the temperature at the combustion unit outlet can be restricted to approximately 450
degrees. Strength members are used for the casing of the combustion chamber since thermal deformation could
otherwise occur, and a ceramic lining is provided on the inner surface of the casing. By adopting a ceramic
lining and introducing cooling air, the temperature of the outer surface of the casing is restricted to a low level so
that the surface can even be touched by hand.
450˚C
Nozzle
GI OI
Dilution Air Dilution Air
Gas pipe 1
BOG Combustion Air
Gas pipe 2
Ignition Air
Fuel Oil
35
Chapter 5 BOG combustion units
The pressure of the BOG is about 5 bar. The BOG is supplied through piping installed within a special gastight
room. In addition to the usual “BOG combustion mode”, the operational modes of this GCU also include a
“stand-by mode”, a “stand-by eco mode”, and a “tank purging mode”. Furthermore, it can also burn the vent
gas discharged from the re-liquefaction unit.
5.2 Arrangement
Figure 5.2 shows an example of the arrangement of a GCU. The GCU is generally installed in the funnel space
that extends over four tiers of decks.
BOG supply piping and valves, burners, control system and draft fans for combustion are installed on the lowest
deck. Burners, BOG valves, and associated components are arranged in a gastight burner room, where gas
detectors and fire extinguishing systems, etc., are installed. A self-closing type door is also installed in this
burner room. Since the burner room is kept under negative pressure, the door is fitted so as to open outward
from the room. This arrangement prevents the door from being kept in an open condition.
Axial dilution fans for cooling and an exhaust fan for ventilating the burner room are installed on the deck above
the lowest deck. Air is supplied with practically no pressure loss from the ventilation port on the starboard and
port sides to the dilution fans. The two decks above this deck include spaces for exhaust gas piping.
Burner room
Central air
36
Chapter 5 BOG combustion units
However, considering the construction of GCU, it is possible to ensure sufficient reliability even in the case of
single unit. A GCU has a comparatively simple construction, and components that are likely to fail are
restricted to fans, burners and the like. Considering this, even if the GCU has one casing, the reliability of the
GCU having multiple components shown in Table 5.1 may be treated as being equivalent to that of two GCUs
with 100% processing ability.
In addition, regardless of the redundancy of GCU and its components, at lease one spare set of consumables such
as nozzle tips and movable parts of the burners are also to be provided onboard the ship.
(1) Arrangement
The GCU is to be installed at a gas-safe location such as the funnel space.
37
Chapter 5 BOG combustion units
ii) The burner room is to be provided with a mechanical exhaust ventilation system. If one burner
room is arranged in the ship, the burner room is in principle to be provided with at least two sets of
ventilation fans.
iii) The burner room is to be provided with a gas detecting system of fixed type. If one burner room is
arranged in the ship, the burner room is to be provided with at least two units of gas sensors.
However, one unit of gas sensor may be accepted if the gas sensor is provided with a self-monitoring
function.
iv) The ventilation inlet and discharge for the required ventilation systems are to be respectively from
and to a safe location (Paragraph 16.3.5 of the IGC Code).
v) Access provided from a gas safe space to the burner room is to be achieved by means of a
self-closing door.
(3) Uptake
i) The uptake of the GCU is to be independent of the uptakes of other GCUs, boilers and the like
(Paragraph 16.5.1 of the IGC Code).
ii) The temperature of exhaust gas emitted from the GCU is not to exceed 535˚C (Paragraph 154.703
(b), (1) of CFR 46, USCG).
iii) Measures are to be taken to ensure that flames from the combustion chamber are not visible from
outside the ship (Paragraph 154.703 (b), (2) of CFR 46, USCG).
i) Gas nozzles for combustion are to be fitted in such a way that gas fuel is ignited by an electric
ignition device or pilot fuel oil burner.
ii) A flame scanner is to be installed and arranged to assure that gas flow to the burner is cut off unless
satisfactory ignition has been established and maintained.
iii) Each burner is to be provided with at least two flame detectors. However, one flame detector may
be accepted if the detector is provided with a self-diagnostic function.
iv) Gas fuel supply pipes to each burner are to be provided with a manually operable shut-off valve.
v) Gas fuel supply pipes to each burner are to be purged with inert gas in the event of flame failure of
the same burners.
38
Chapter 5 BOG combustion units
BOG is sent to the GCU by the low-duty compressor in the compressor room. As stated in paragraph 16.3.7 of
the IGC Code, a master gas fuel valve that can be closed from the machinery space is required to be installed in
the gas fuel supply piping on the upstream side (cargo area) of the burner room. If only one GCU is installed
as the BOG treatment equipment, the master gas fuel valve is to be capable of closing automatically when a gas
leak is detected or when the ventilating ability for the burner room is lost.
However, as shown in Figure 5.3, if the GCU is installed together with the DFD engines onboard the ship,
automatic gas shut-off valves may be installed between the master gas fuel valve and the GCU and between the
master gas fuel valve and each respective DFD engine. In this case, for example, if a fault occurs in one DFD
engine, closing of the automatic gas shut-off valve of the relevant line can ensure the safety of the remaining
DFD engines, and gas can be continuously supplied to the GCU and other DFD engines (for details, see Chapter
6 of these Guidelines).
Burner
To vent mast
Automatic gas
shut-off valve
N2
Master gas fuel valve
39
Chapter 5 BOG combustion units
Table 5.2 Monitoring, alarms and Safety Devices Required for GCUs and Relevant Equipment
Automatic
Item Monitoring Alarm
shut-off (1)
a. Stopping of draft fan for combustion (2) X
X (3)
d. Flame failure of burner X (3) (4)
GCU High
e. Exhaust gas temperature
X
Low Low Low
f. Gas supply pressure
X X
Low
g. Pilot fuel oil supply pressure
X
h. Loss of burner control power X
40
Chapter 6 Gas fuel supply piping
(1) Gas fuel piping is to consist of a double wall piping system with the gas fuel contained in the inner pipe.
The space between the concentric pipes is to be pressurized with inert gas at a pressure greater than the gas
fuel pressure. (See Paragraph 16.3.1.1 of the IGC Code.)
(2) Gas fuel piping is to be installed within a ventilated pipe or duct. The air space between the gas fuel
piping and inner wall of this pipe or duct is to be equipped with mechanical exhaust ventilation. (See
Paragraph 16.3.1.2 of the IGC Code.)
(3) Gas fuel piping is to consist of a double wall piping system with the gas fuel contained in the inner pipe.
The space between the concentric pipes is to be pressurized constantly with inert gas at a pressure greater
than 0.025 MPa, and this pressure is to be maintained and continuously monitored.
However, the protective measure presently being considered for gas fuel piping in spaces where DFD engines
are installed generally consists of mechanically exhaust ventilating the intermediate space of the gas fuel piping,
which comprises a double wall pipe construction for both a low pressure and high pressure system (i.e. the
method described in (2) above). Requirements related to the method in (2) are given in Table 6.1.
Moreover, in the event that a gas leak occurs, the gas fuel supply is not to be restored until the leak has been
found and repaired. Instructions to this effect are to be placed in a prominent position in the machinery space.
(See Paragraph 16.3.2 of the IGC Code.)
The requirements for ventilation hoods, casing, gas control unit room, or similar spaces are given in Table 6.2.
41
Chapter 6 Gas fuel supply piping
Table 6.1 Protection against Gas Leaks from Gas Fuel Piping
Requirements
a. The air space between the gas fuel piping and inner wall of a protective pipe or duct is to be equipped
with mechanical exhaust ventilation having a capacity of at least 30 air changes per hour.(1) The
capacity of mechanical ventilating systems for use in high-pressure DFD engines is to be determined
considering the flow rate of gas fuel and construction and arrangement of protective pipes or ducts, as
deemed appropriate by the Society.(2)
b. The ventilation system is to be arranged to maintain a pressure less than the atmospheric pressure.(1)
c. The fan motors are to be placed outside the ventilated pipe or duct.(1)
d. The ventilation outlet is to be placed in a position where no flammable gas-air mixture may be ignited.(1)
e. The ventilation is to always be in operation when there is gas fuel in the piping.(1)
f. Continuous gas detection is to be provided to indicate leaks and to shut down the gas fuel supply to the
machinery space. The systems are to activate the alarm at 30% of the lower flammable limit and to shut
down the master gas fuel valve before the gas concentration reaches 60% of the lower flammable limit.(1)
g. The master gas fuel valve is to close automatically, if the required air flow is not established and
maintained by the exhaust ventilation system.(1)
h. Materials, construction and strength of protection pipes or ducts and mechanical ventilating systems are
to be sufficiently durable against bursting and rapid expansion of high-pressure gases following an inner
pipe failure.(2)
i. The air intakes of mechanical ventilating systems are to be provided with non-return devices effective for
gas fuel leaks. However, if the air intakes are opened directly to exposed spaces and located at places
free from risk of ignition of leaked gas fuel, these requirements may be dispensed with.(2)
j. The number of flange joints of protective pipes or ducts is to be minimized.(2)
k. It is to be so arranged that the inside of the gas fuel supply piping system between the master gas fuel
valve and the high-pressure DFD engines is to be automatically purged with inert gas, when the master
gas fuel valve is closed.(2)
Notes:
(1) See Paragraph 16.3.1.2 of the IGC Code.
(2) Additional requirements for high-pressure DFD engines. (See Paragraph 3.2.3-2(2), Annex 3, Part N of
the Guidance to the Rules.)
Table 6.2 Protection against Gas Leaks from Gas Utilization units (Paragraph 16.3.4 of the IGC Code)
Requirements
a. The ventilation hood or casing is to be equipped with an exhaust ventilation system (1) and a continuous
gas detecting system (1).
b. The ventilation hood or casing is to be installed or mounted to permit the ventilating air to sweep across
the gas utilization unit and be exhausted at the top of the ventilation hood or casing.
Note:
(1) The exhaust ventilation system and continuous gas detecting system may be systems used for the air space
of double wall gas fuel pipes for DFD engines.
42
Chapter 6 Gas fuel supply piping
i) High-pressure gas fuel piping system used in large two-stroke DFD engines for propulsion not only
have high gas pressure, but are also exposed to external loads due to vibration of the engine.
Therefore, the system is to be ensured to have sufficient structural strength by stress analysis
considering the weight of the pipes, acceleration loads if significant, internal pressure, thermal
contraction, loads induced by hogging and sagging of the ship, and vibration of the engine.
ii) Joints between the gas fuel lines are to be butt-welded joints with full penetration, except where
specially approved by the Society, and for all butt-welded joints, post-weld heat treatment is to be
performed, in principle.
iii) Valves and expansion joints are to be of a type approved by the Society. The provisions of
Paragraph 5.3.2.2 of the IGC Code are to apply to the bellows expansion joints, and prototype tests,
described in Table 6.3, are to be carried out for the bellows expansion joints used for two-stroke
cycle DFD engines for propulsion.
Note:
(1) This test is applicable to expansion joints used for two-stroke cycle DFD engines for propulsion.
43
Chapter 6 Gas fuel supply piping
Inert gas
V3
Gas inlet Gas
Figure 6.1 Arrangement of automatic valves (double block and bleed valves).
The IGC Code prescribes requirements only for the three automatic valves described above. However, in an
actual system, a vent pipe with a control valve is also installed in the gas supply piping on the inlet side of the
V1 and on the outlet side of the V2 allowing gas to be discharged from these parts, as well, in the event of a fault
or gas leak. The vent piping need not be independent; gas may be led to the vent mast through connections, as
shown in Figure 6.1.
Each BOG treatment system is to include valves such as a pressure regulating valves and automatic valves
(hereafter referred to as "control valve units") in the gas fuel supply piping. As mentioned in Section 6.2, the
IGC Code requires that the control valve units be enclosed by a ventilation hood or casing, or that these units be
installed in special gastight rooms as a measure against gas leaks. In this case, manually operated stop valve
(for maintenance), filter, pressure regulating valve, automatic valves, and so on, are sequentially arranged in the
gas fuel piping from the inlet side in this space.
44
Chapter 6 Gas fuel supply piping
Figure 6.2 shows an example of the arrangement of the master gas fuel valve and control valve unit for the main
boiler installed in a steam turbine ship. The general practice onboard a steam turbine ship is to accommodate
the control valve units for two main boilers in one ventilation hood, as shown in this figure. In this case, the
master gas fuel valve must always close automatically when a gas leak is detected in the ventilation hood. If
one of the two exhaust ventilation fans (100% x 2) has a breakdown, automatic changeover to the other fan
should be provided, but if both fans have broken down, then shut-down of the master gas fuel valve is necessary.
Exhaust fan
Ventilation hood
No. 1 Burner
To vent mast No. 1
Master gas fuel valve No. 2 Burner Main boiler
BOG No. 3 Burner
No. 1 Burner
Cargo area No. 2
No. 2 Burner
Main boiler
No. 3 Burner
Air intake
Figure 6.2 Arrangement of master gas fuel valve (for steam turbine ships).
Figure 6.3 shows an example of the gas fuel supply to four DFD engines (power generating engines) and one
GCU. In this example, the control valve units of the No. 1 and No. 2 DFD engines, the control units of the No.
3 and No. 4 DFD engines, and the GCU control units are installed in independent gas valve unit rooms (or
burner rooms). In addition, automatic gas shut-off valves are independently arranged in the gas pipe lines led
to each room.
For instance, if a gas leak is detected in the No. 1 gas valve unit room, the No. 1 automatic gas shut-off valve
will close, and the automatic valves (double block and bleed valves) in the No. 1 gas valve unit room will
activate. In this case, the No. 3 and the No. 4 DFD engines can be operated under the open conditions of the
master gas fuel valve and the No. 2 automatic gas shut-off valve.
45
Chapter 6 Gas fuel supply piping
GCU
No. 1 Gas valve unit room
No.1 DFD
2
Cargo area No.3 DFD
Automatic gas shut-off valves
(need not to be located in the cargo area)
No.4 DFD
Figure 6.3 Arrangement of master gas fuel valve and automatic gas shut-off valves.
The automatic gas shut-off valves are to be installed outside the gas valve unit room and the burner room
(generally above the open weather deck); however, they need not to be located in the cargo area. The IGC
Code does not take into consideration the redundancy of BOG treatment equipment. Consequently, it
prescribes shut-down of the master gas fuel valve as a measure against gas leaks, etc., as described in Section 6.5
of these Guidelines. However, by additionally installing an automatic gas shut-off valve, and by providing this
valve with the same functions required as the master gas fuel valve, the system may be treated as satisfying the
requirements of the IGC Code.
Situations in which the master gas fuel valve is to be shut down under the arrangement of the automatic gas
shut-off valves may include cases where abnormalities such as a fault in the compressor or fire in the compressor
room are confirmed on the upstream side of the gas supply piping, or where a fault occurs in the control system
of the automatic gas shut-off valve. Under such circumstances, the master gas fuel valve and the automatic
valves (double block and bleed valves) for the equipment in operation are to be capable of being activated to
shut down the gas supply. At the same time, gas accumulated between the master gas fuel valve and the
automatic valves is to be released from the vent pipe.
46
Chapter 6 Gas fuel supply piping
6.4.
If the gas fuel piping is of double-wall pipe construction, the space within the generator room is ventilated by the
supply-type ventilation fan. If all power generating systems are installed in one generator room, two
ventilation fans are generally installed. In this case, even if one ventilation fan fails, the other fan switches on
automatically. If the generator room is divided into two parts, as noted above, one ventilation fan may be
installed in each room, which ensures redundancy.
On the other hand, if gas fuel is supplied through single-wall piping to the DFD engine, the generator room must
be divided into at least two parts, from the view point of redundancy. An exhaust type ventilation system is to
be installed in each room to discharge the leaked gas outside the generator room (see Table 6.4).
Table 6.4 Type and Number of Ventilation Fans for Generator Rooms
Structure of gas piping for DFD engines Single wall Double wall
Number of generator rooms Multiple One Multiple
Ventilation fan Type Exhaust Supply
Number At least one set At least two sets At least one set
per each room per each room
The intermediate space of the gas fuel double wall piping for the DFD engine (space between the gas pipe and
protective pipe) is connected to the gas valve unit room without installing partitions, which means that the
pressure in this space is below atmospheric pressure. In contrast, the space in the generator room is pressurized
to a pressure above atmospheric pressure by the supply-type ventilation system. Accordingly, even if a gas
leak occurs from the gas fuel pipe, the leaked gas does not leak outside the double wall pipe (within the
generator room). The leaked gas is always passed through this intermediate space, delivered to the gas valve
unit room, and led to the vent pipe by the exhaust-type ventilation system.
Gas leaks from the gas fuel double wall pipe are detected by gas detection sensors installed at the end of the
double wall pipe on the side of the gas valve unit room. Gas leaks from the control valve units are detected by
gas detection sensors installed on either the upper part of the gas valve unit room or at the inlet of the exhaust
type ventilation system, or at both locations. The location of a gas leak can be identified from the gas
concentration detected by each of the gas sensors. In this way, at least two gas detection sensors are necessary
in one room to identify the location of a gas leak. When a gas leak is detected, the automatic gas shut-off valve
arranged before the gas valve unit room where the gas leak was detected automatically closes, and at the same
time, the automatic valves (double block and bleed valves) in the room also activate, as explained in Section 6.6
of these Guidelines.
The gas detectors are to be of a type approved by the Society. Visual and audible alarms are to be activated
when the gas concentration reaches 30% of the lower flammable limit, and the automatic gas shut-off valve and
automatic valves are to activate automatically before the gas concentration reaches 60% of the lower flammable
limit.
47
To vent mast
Chapter 6
G
No. 1 DF diesel engine
Figure 6.4
Gas fuel supply piping
G Supply fan
G
N2
No. 2 DF diesel engine
G
N2
48
No. 3 DF diesel engine
G
i) Leaked gas can enter the gas valve unit room for both the No. 1 and No. 2 DFD engines.
ii) An automatic gas shut-off valve is provided for both the No. 1 and No. 2 DFD engines.
In contrast, if a gas valve unit room and automatic gas shut-off valve are installed for each DFD engine as
shown in Figure 6.5, only the engine in which the gas leak occurred may be stopped. This means that
redundancy of the system is improved, while bulkheads, automatic gas shut-off valves and gas detection sensors
have to be added. Such an issue of partitioning and arrangement is determined by the relationship between
which engine can be used in the various failure modes and the cost aspects involved.
2
G
No. 2 DFD
Master gas fuel valve
G
3
G
No. 3 DFD
4
G
No. 4 DFD
Figure 6.5 Arrangement of independent gas valve unit rooms for each DFD engine.
49
Chapter 7 Requirements for automatic and remote control systems
Safety measures required for a DFD engine that uses double wall gas fuel piping are shown in Table 7.1.
50
Chapter 7 Requirements for automatic and remote control systems
Table 7.2 Monitoring, Alarms and Safety Devices Required for Gas Compressors
Automatic
Items Monitoring Alarm
shut-down
Monitoring, alarms and safety devices specified in Table
a. X X X
3.4 of these Guidelines
Low Low Low
b. Gas outlet temperature of boil off gas heaters (1)
X X
High High High
c. Gas outlet pressure (1)
X X
51
Chapter 8 Redundancy
8 Redundancy
However, regardless of the above points, redundancy of a propulsion engine for LNG carriers is required in
practice because of their special features, as shown below.
i) Regular operation required as part of the LNG supply chain
ii) Requirements of stand-by of an propulsion engine while at terminal
For this reason, except for equipment (such as shafts, reduction gears, etc.) considered to have especially high
reliability, redundancy for the propulsion system is generally required, as summarized in Table 8.1.
52
Chapter 8 Redundancy
i) Additional treatment equipment is not required for main boilers with dual fuel burners because BOG
can be burnt with only the main boiler (case a).
ii) When a re-liquefaction unit or GCU is installed as the only means of treating BOG, the treatment
capacity and redundancy for this equipment are given in Paragraphs 4.3.1 and 5.3.1 of these
Guidelines. If redundancy of a part of the components is ensured, then only one set of the equipment
may be accepted. If one re-liquefaction unit and one GCU are installed, a stand-by for each unit is
not required.
iii) Two sets of low-duty compressors including a stand-by are required to supply gas.
iv) When DFD engines for propulsion are installed onboard the ship, BOG cannot be consumed with the
DFD engines while the ship is in port unless the ship is equipped with CPP. Therefore,
re-liquefaction units or GCUs having a treatment capacity of 100% are required. A stand-by
high-pressure gas compressor for a high-pressure DFD propulsion engine is not required, because
HFO is supplied to the engine as backup fuel (case b).
v) When DFD engines for power generation are used, gas consumption by the DFD engines becomes
minimum while the ship is in port or during low-load operation, and minimum gas consumption rate is
to be determined based on such condition. The capacity of additional BOG treatment equipment is
required to be the amount obtained by subtracting this minimum gas consumption rate from the
planned boil-off gas rate.
For instance, if the minimum gas consumption rate is assumed as being 30%, the treatment capacity
required for one GCU with redundant components becomes 70% of the total capacity. If redundancy
in components is not provided, the minimum requirement becomes GCU (70%) x 2 sets, or GCU
(35%) x 3 sets and so on, which means that the treatment capacity of 70% is required even if one set of
GCUs has failed (case c).
53
Chapter 8 Redundancy
b. DE x 2 DG x 3 RL (100%) x1
or For redundancy of components, see Paragraph
DFD x2 (0% in port) 4.3.1 of these Guidelines.
GCU (100%) x1
For redundancy of components, see Paragraph
5.3.1 of these Guidelines.
RL (100%) x1 and GCU(100%) x1
Stand-by unit is not required.
c. Propulsion motor x 2 DFD x4 (min. 30%) RL (70%) x1
For redundancy of components, see Paragraph
4.3.1 of these Guidelines.
GCU (70%) x1
For redundancy of components, see Paragraph
5.3.1 of these Guidelines.
GCU (70%) x2
Stand-by unit is not required.
GCU(35%) x3
Stand-by unit is not required.
RL(70%) x1 and GCU(70%) x1
Stand-by unit is not required.
Notes:
(1) Underlined equipment: BOG treatment equipment. Values in brackets indicate BOG treatment capacity.
(2) DE: Oil-fired diesel engine, DFD: DFD engine, DG: Generator driven by oil-fired diesel engine,
TG: Turbo generator, RL: Re-liquefaction unit, GCU: Gas combustion unit.
(3) In any case, two sets of LD compressors (100% x 2) including a stand-by are required.
54
References
References
55
NIPPON KAIJI KYOKAI