Professional Documents
Culture Documents
TYPICAL SYSTEM
The diagram below shows a typical air-conditioning loop with the chiller producing a chilled water
supply to the air handling units and the cooling tower cooling the excess chiller cooling water.
Chilled Water
Loop
Warm Water return
Dump valve
Typ 14 degC
Chiller
The main areas that apply to cost saving come from the Chilled water reticulation pumps, Cooling
tower pump and Air handling unit fans. Savings in running cost of up to 80% can be generated by
use of VFD technology in these areas.
GENERAL
The physics of mass transfer and heat exchange is described by the formula:
P = m x Cp x ∆T
P= power kW
m = mass transfer kg/s
Cp = 4.186 (constant)
∆T = temperature differential degC
The formula details the relationship between mass flow and temperature change.
The pump within any cooling loop will input power into the system equivalent to the efficiency loss
of the pump. This is transferred into heat in the pumped liquid which is undesirable in cooling water
lines. When a pump operates it has an efficiency for any specific duty. The measure of efficiency is
based on the formula:
eff = Head x Flow
102 x power
The excess power input into the pump is dispelled as noise and heat. The proportion of energy loss
dispelled as heat is approximately 98% of this energy. Virtually all of the energy lost as pump
efficiency goes into the pumped liquid and is dissipated into the Chilled water line. This can be very
significant if the pump is not operating at the optimum duty.
e.g. If a chilled water loop is operating at a variable flow rate from 5 to 40 l/s at 30m head with the
water temp at 3 deg C. The table below shows the temperature increase based on heat inserted
into the system due to pump efficiency at different flow rates. The pump used is a 100 x 80 x 160
15Kw.
Flow rate Act Head Pump Efficiency Power used Temperature increase
l/s m % kW degC
1 41 10 4.02 0.96
5 41 25 8.04 0.38
10 41 46 8.74 0.21
15 40 60 9.80 0.16
20 39 70 10.92 0.13
30 35 80.5 12.79 0.10
40 30 82.5 14.26 0.09
The table above shows that the increase water Temp Increase
temperature is significant when the pump is
operating outside its optimum efficiency range. 1.00
When the pump is down in the very low end flows 0.90
0.80
the temperature increase is in excess of 30% of 0.70
the required temperature. 0.60
Head
0.50
0.30
energy loss as the chiller will have to provide
0.20
more energy to reduce the temperature caused by 0.10
the pump losses. In addition to this energy loss 0.00
The perfect system would only transfer enough liquid into heat exchangers to satisfy the need for
heat transfer. The practicality of normal system does not allow for the optimization of the heat
transfer process as the feedback information is only used in a banded situation. The operator tells
the appliances to run within specified temperature levels, which in some instance can be very
broad.
3.50
3.00
2.50
2.00
$A/hr
Cost
Temp Control
1.50
VFD System
1.00
0.50
0.00
0 5 10 15 20 25 30
Flow
l/s
This graph shows the extra running cost of a system controlled by temperature switches compared
to a pump system controlled by a Variable Speed Drive (VFD). The VFD controller varies the pump
speed according to the heat load within the system and can maintain the system within the
temperature requirement very accurately and also holds the cooling water pump within its optimum
efficiency range.
SUMMARY OF LOSSES
The losses incurred by poor control over thermal transfer lines is a significant part of the design of
the systems which cam be minimized by use of smarter control based on system feedback. The
optimum system for thermal lines is a VFD controlled system where the pump automatically varies
in speed based on the thermal load required. The rest of this paper deals with the setting up and
selection of these systems for specific parts of air-conditioning systems.
COOLING TOWER PUMPS
The cooling tower pumps take heat from the CHILLER and
circulate the hot water through the Cooling Tower to dissipate
Chiller Cooling Tower the heat to the atmosphere. The cool water is then re-
circulated to the Chiller to remove excess heat from this
appliance.
one very large pump and motor. This is due to the capacity of the system to maintain the optimum
efficiency at all times.
The capital costs of the smaller VFD is also significant as the cost of VFD’s is based on the current
draw. The Marlin system uses only one pump on the VFD so the size of the drive is only required
to be the sizes of the largest motor within the system.
CHILLED WATER LINE
As with the cooling Tower Line the Chilled Water Line Air Handling
Unit
requirements are dependent upon the heat load generated
within the building.
With this part of the cooling system the Chiller has generally Chilled Water
Loop
Air Handling Warm Water return
got STOP/START control based on a broad temperature band Unit
CHILLER
Building
requirements
The Building heat load is a given based on the design and use of the building but the lines losses
are subject to design optimization.
The areas that can be addressed are the pump efficiency and the Heat input from the pump. The
example shown for a typical chilled water line shows that the losses for this line are significant if the
pump duty and operation does not match the required flow and head requirement of the air-
conditioning system. This will always be the case if the chilled water pump is not capable of
changing is operating capacity based on the heat demand from the building.
Some chillers operate on a staged system that operate smaller compressors for lower heat loads.
This certainly assists in minimizing losses but the best method is full variation capacity that is
achieved with variable speed technology.
COST COMPARISONS
The VFD systems operate are always a more expensive capital cost item compared to a fixed
speed system. The only justification that can be bought forward to use a VFD system is that the
capital cost increase is generally paid back by running cost savings within the first 8 - 12 months.
This is based on theoretical calculation and supported by numerous case studies.
The building industry is generally a very capital cost sensitive market so the inclusion of cost
saving appliances is generally not considered by the builders who are driven by the need to
maintain a low initial capital cost. It is up to building owners and tenants to drive the inclusion of the
cost saving benefits that can be gained by using VFD technology.